2015-01-12 16:13:18BUILDING PLAN REVIEW
 PERMIT: 14120688/ CLUBHOUSE
 ADD: 820 GRANT ST.
 CONT: T. B. D. /AYALA MANUEL
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JAN. 12/ 2015
 ACTION: DENIED
  
 1) SHEET S2 INDICATES THE EXISTANCE OF A SOILS REPORT
 BY ARDAMIN & ASSOC. FILE# 14-1657 MAY 23/ 14TH. PLEASE
 SUBMIT 3 ORIGINAL SIGNED & SEALED REPORTS.
  
  
 2) PAGE 007 FIRST FLOOR LIFE SAFETY: GREAT ROOM 1841
 SQ. FT./ 15= 122 THE DESIGNER HAS DROPPED THE FRACTION
 OF AN OCCUPANT, YOU ROUND UP NOT DOWN TO THE NEXT WHOLE
 NUMBER. FBC-B 1004.1. ALSO SEE BOAF INFORMAL
 INTERPRETATION 5479. THIS HAS ALSO OCCURED IN THE
 LOUNGE 177/15= 12.
  
 3) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.4.2
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE
 BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND
 FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF THE
 BUILDING. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE
 INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN APPROVED BY THE BUILDING OFFICIAL.
  
 3A) NOA 12-0320.07 SUNSHINE 2000 SERIES SINGLE HUNG,
 LMI PLEASE CIRCLE THE UNITS HEIGHT, WIDTH, PRESSURES &
 ANCHORAGE.
  
 3B) NOA 13-0122.05 SUNSHINE 8000 SERIES STOREFRONT, LMI
 PLEASE CIRCLE THE UNITS HEIGHT, WIDTH, PRESSURES &
 ANCHORAGE.
  
 3C) NOA 11-1216.02 SUNSHINE MULLION CIRCLE WIDTH, SPAN,
 MULLION SIZE PRESSURES AND TYPE OF ANCHORS.
  
 3D) NOA 14-0109.06 SUNSHINE ALUMINUM, OUTSWING FRENCH
 DOORS NOTE FLUSHBOLTS WILL NEED TO WORK FROM A WHEEL
 CHAIR POSITION, PLEASE CIRCLE THE UNITS HEIGHT, WIDTH,
 PRESSURES & ANCHORAGE.
  
 3E) FL. 14237-R1 FLEMING BARON CIRCLE IF SINGLE OR
 PAIR, INSWEING OR OUT, TYPE OF LATCH ANCHORAGE AND
 ASSOCIATED PRESSURES.
  
 3F) NOA 13-1104.12 GAF TIMBERLINE ULTRA HD SHINGLES .
  
 3G) PLEASE PROVIDE THE WINDOW AND DOOR SHGC OF 0.5
 FBC-ENERGY 402.3.
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) ROOF VENTILATION PAGE 010, A-1.03 THE PLANS INDICATE
 THE USE OF SOFFIT VENTILATION BUT DO NOT INDICATE
 COMPLIANCE WITH FBC-B 1203.2 50 PERCENT OF THE REQUIRED
 VENTILATING AREA PROVIDED BY VENTILATORS LOCATED IN THE
 UPPER PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3
 FEET (914 MM) ABOVE EAVE OR CORNICE VENTS WITH THE
 BALANCE OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR
 CORNICE VENTS. IF THE CUPALO IS AN ACTIVE VENTILATING
 CUPALO PLEASE PROVIDE THE SQ. FT. OF VENTING AND HOW
 THIS UNIT WILL BE FRAMED AND TIED INTO THE ROOF
 FRAMING.
  
 6) PAGE 011/ A-1.04 THERE ARE (3) CODE SECTIONS SECTION
 1817 HIGH VELOCITY HURRICANE- EXCAVATIONS, SECTION 1818
 HIGH VELOCITY HURRICANE ZONES BEARING CAPACITY OF
 SOILS, & SECTION 2326 HIGH VELOCITY HURRICANE ZONES-
 REOTECTION OF WOOD, THESE CODE SECTION WILL NEED TO BE
 REMOVED FROM THE PLANS, THESE CODE SECIONS ARE FOR
 BROWARD AND MIAMI-DADE COUNTY ONLY. PALM BEACH COUNTY
 IS NOT IN THE HVHZ BUT IN A WIND BORN DEBRIS REGION.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8). A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  