2015-03-06 10:05:34906 GRANT STREET - BUILDING #2: 50 UNIT APARTMENT
 PERMIT #14120686
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT: THE BACKFLOW PREVENTION DEVICES
 (SHUTOFF VALVES) NEED TO BE LOCATED A SAFE DISTANCE
 FROM THE BUILDING TO AVOID FIREFIGHTER INJURIES DUE TO
 FALLING GLASS, COLLAPSING WALLS, FALLING DEBRIS, ETC.
 ORIGINAL COMMENT: SHEET PWS-1: PER NFPA 24 SECTION
 6.2.1, ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS
 FOR FIRE PROTECTION SYSTEMS SHALL BE ARRANGED IN
 ACCORDANCE WITH ONE OF THE FOLLOWING SO THAT THEY CAN
 BE ISOLATED:
 (1) A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 REPEAT COMMENT - SHEET 1A-1.04 & 1A-9.01: THE CENTER
 STAIR APPEARS TO BE COMPLETELY ENCLOSED (WALLS AND
 ROOF) AND COULD RESULT IN AN ACCUMULATION OF SMOKE IN A
 FIRE EVENT. THE STAIR NEEDS TO BE OPEN OR WOULD NEED TO
 BE PROTECTED AS AN ENCLOSED STAIR WITH FIRE RATED
 CONSTRUCTION, PROTECTED OPENINGS/PENETRATIONS AND NOT
 BE OPEN TO OTHER COMBUSTIBLES SUCH AS THE ELEVATOR
 CONTROL CLOSET.
  
 FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT ISSUED
 SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED WITH THE
 WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, ALTER OR
 SET ASIDE ANY OF THE PROVISIONS OF THE TECHNICAL CODES,
 NOR SHALL ISSUANCE OF A PERMIT PREVENT THE BUILDING
 OFFICIAL FROM THEREAFTER REQUIRING A CORRECTION OF
 ERRORS IN PLANS, CONSTRUCTION OR VIOLATIONS OF THIS
 CODE. REVIEW AND APPROVAL BY THE AHJ SHALL NOT RELIEVE
 THE OWNER, CONTRACTOR, ETC. OF THE RESPONSIBILITY OF
 COMPLIANCE WITH CODE (NFPA 1, SECTION 1.14.4).
  