2015-03-10 16:34:373/10/2015
 PROJECT: GRANT ST
 PERMIT#: 14120686
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 SHEET ES1.1
 CLARIFY THE NOTES BY THE TRASH COMPACTOR. ONE NOTE
 CALLS FOR A 30AMP DISCONNECT FUSED AT 20AMPS. AND THE
 SECOND CALLS FOR A 100AMP DISCONNECT FUSED AT 60AMP.
 THERE IS ONLY REFERENCE TO ONE CIRCUIT NUMBER IN PANEL
 H1. IS THERE ANOTHER CIRCUIT REQUIRED?
  
 SHEET E1.1B
 PROVIDE NORMAL AND EMERGENCY LIGHTING FOR STAIRWAY #1,
 AT 1ST AND SND FL LANDING. NEC 700.16
  
 SHEET E1.1C
 A) REVISE THE GFI RECEPTACLE SYMBOL INDICATED BY THE
 KITCHEN SINK. ONE OF THE GFI OUTLETS IS INDICATED AS AN
 ABOVE COUNTER RECEPTACLE AND THE OTHER IS NOT. ARE BOTH
 RECEPTACLES PROPOSED TO BE INSTALLED AT THE COUNTERTOP
 ELEVATION? REVISE ACCORDINGLY.
 B) ONLY A MICROWAVE AND REFRIGERATOR OUTLET ARE SHOWN.
 ARE ANY ADDITIONAL OUTLETS PROPOSED FOR THE COUNTERTOP
 ELEVATION?
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 PLANS AND ENGINEERING ARE REQUIRED FOR SITE LIGHTING,
 GENERATORS. FIRE ALARM, ACCESS CONTROL SYSTEM,
 SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, AND,
 COMMUNICATION.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  