| 2015-03-10 16:34:37 | 3/10/2015 |
| | PROJECT: GRANT ST |
| | PERMIT#: 14120686 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION |
| | |
| | SHEET ES1.1 |
| | CLARIFY THE NOTES BY THE TRASH COMPACTOR. ONE NOTE |
| | CALLS FOR A 30AMP DISCONNECT FUSED AT 20AMPS. AND THE |
| | SECOND CALLS FOR A 100AMP DISCONNECT FUSED AT 60AMP. |
| | THERE IS ONLY REFERENCE TO ONE CIRCUIT NUMBER IN PANEL |
| | H1. IS THERE ANOTHER CIRCUIT REQUIRED? |
| | |
| | SHEET E1.1B |
| | PROVIDE NORMAL AND EMERGENCY LIGHTING FOR STAIRWAY #1, |
| | AT 1ST AND SND FL LANDING. NEC 700.16 |
| | |
| | SHEET E1.1C |
| | A) REVISE THE GFI RECEPTACLE SYMBOL INDICATED BY THE |
| | KITCHEN SINK. ONE OF THE GFI OUTLETS IS INDICATED AS AN |
| | ABOVE COUNTER RECEPTACLE AND THE OTHER IS NOT. ARE BOTH |
| | RECEPTACLES PROPOSED TO BE INSTALLED AT THE COUNTERTOP |
| | ELEVATION? REVISE ACCORDINGLY. |
| | B) ONLY A MICROWAVE AND REFRIGERATOR OUTLET ARE SHOWN. |
| | ARE ANY ADDITIONAL OUTLETS PROPOSED FOR THE COUNTERTOP |
| | ELEVATION? |
| | |
| | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | PLANS AND ENGINEERING ARE REQUIRED FOR SITE LIGHTING, |
| | GENERATORS. FIRE ALARM, ACCESS CONTROL SYSTEM, |
| | SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, AND, |
| | COMMUNICATION. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |