| 2015-03-09 14:13:31 | BUILDING PLAN REVIEW |
| | PERMIT: 14120686 BLDG # 2 / 50 UNITS |
| | ADD: 906 GRANT ST. |
| | CONT: T. B. D. /AYALA MANUEL |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| | NAMING CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| | AVAILABLE |
| | |
| | 2ND REVIEW |
| | DATE: MON. MARCH 09/ 2015 |
| | ACTION: DENIED |
| | |
| | NOTICE: !!!!!!!!!!!!!!! THE PERMIT APPLICATIONS NEED TO |
| | REFLECT THE CORRECT ADDRESS. THE PERMIT APPLICATIONS |
| | DOES NOT STATE BLDG. # 1 / 49 UNITS OR BLDG # 2 / 50 |
| | UNITS. MY PLAN REVIEWS ARE AS FOLLOWS UNDER PERMIT # |
| | 14120680 BLDG #1/ 49 UNITS AND PERMIT # 14120686 BLDG # |
| | 2 /50 UNITS. CURRENTLY IT LOOKS LIKE THE BLDG COMMENTS |
| | FOR EACH BUILDING ARE UNDER THE WRONG PERMIT NUMBER |
| | SINCE WE TOOK BLDG # 1 WITH THE LOWER PERMIT NUMBER AS |
| | BLDG # 114120680 AND BLDG # 2 AS PERMIT # 14120686. |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE |
| | MATERIAL.CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION OF WORK TO BE |
| | COMPLETED UNDER THIS PERMIT. |
| | |
| | THE ONLY DIFFERENCE IN THE COMMENTS WILL BE IN THE UNIT |
| | WILL AFFECT THE COMMENT 4A)(1-2) , THIS COMMENT DEALS |
| | WITH THE ASSEMBLY OCCUPANCY IN THE 49 UNIT APPRTMENT |
| | BUILDING. |
| | |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE |
| | MATERIAL.CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION OF WORK TO BE |
| | COMPLETED UNDER THIS PERMIT. |
| | |
| | 1-2) COMPLIED. |
| | |
| | 2ND REQUEST. 3) THIS PROJECT QUALIFIES FOR A RESIDENT |
| | INSPECTOR UNDER 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING |
| | OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE |
| | INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT |
| | REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION |
| | SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS |
| | SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A |
| | CERTIFICATE CALLED FOR BY ANY PROVISION OF THE |
| | TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS |
| | UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A |
| | RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING |
| | OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION |
| | SERVICE IN THE FOLLOWING INSTANCES: |
| | FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE FOOT |
| | FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| | FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| | METHODS OF CONSTRUCTION, TUNNEL FORM |
| | |
| | RESIDENT INSPECTOR BOOKLET & FORMS WILL BE E-MAILED TO: |
| | /AYALA MANUEL, E-MAIL: [email protected] SENT AT |
| | 8:15 AM 01/12/2015 |
| | THE RESIDENT INSPECTOR FORMS ARE TO BE COMPLETED AND |
| | RETURNED BACK TO THE CONSTRUCTION SERVICES DIVISION |
| | BEFORE PERMIT ISSUANCE. |
| | |
| | 2ND REQUEST. 3A) DIGITAL REVIEW, ONCE THE PLANS ARE |
| | BATCH STAMPED, THE PERMIT IS ISSUED, PLEASE NOTIFY THE |
| | PERMIT LIBRIAN CAROLINE PUELL TO DOWN LOAD THE PLANS TO |
| | THE CONTACT PERSON, NOTE (2) COLOR SETS OF PLANS WILL |
| | NEED TO BE PRINTED, ONE FOR THE RESIDENT INSPECTOR THE |
| | OTHER FOR THE CITY MEP INSPECTORS. |
| | |
| | 2ND REQUEST. 3B) PLEASE REMEMBER TO CALL IN ALL |
| | STRUCTURAL INSPECTIONS SINCE KEN CONRAD WILL BE |
| | AUDITING INSPECTIONS, ALSO IF THERE IS NO RECORD OF |
| | CALLED IN INSPECTIONS AFTER 6 MONTHS OF NO ACTIVITY THE |
| | PERMIT WILL EXPIRE. WPB ADMINISTRATIVE CODE 110.5 |
| | INSPECTION REQUESTS. IT SHALL BE THE DUTY OF THE HOLDER |
| | OF THE BUILDING PERMIT OR THEIR DULY AUTHORIZED AGENT |
| | TO NOTIFY THE BUILDING OFFICIAL WHEN WORK IS READY FOR |
| | INSPECTION. IT SHALL BE THE DUTY OF THE PERMIT HOLDER |
| | TO PROVIDE ACCESS TO AND MEANS FOR INSPECTIONS OF SUCH |
| | WORK THAT ARE REQUIRED BY THIS CODE |
| | |
| | 2ND REQUEST. 3C) 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | 110.3.9 OTHER INSPECTIONS SERVICES. SUCH INSPECTORS |
| | SHALL BE ADEQUATELY PRESENT AT TIMES WORK IS UNDERWAY |
| | ON THE STRUCTURAL ELEMENTS OF THE BUILDING. SUCH |
| | INSPECTORS SHALL BE A REGISTERED ARCHITECT, OR |
| | ENGINEER, OR A PERSON LICENSED UNDER CHAPTER 468, PART |
| | XII, FLORIDA STATUTES. SUCH INSPECTORS SHALL SUBMIT |
| | WEEKLY PROGRESS REPORTS INCLUDING THE DAILY INSPECTIONS |
| | TO THE BUILDING OFFICIAL, AND INCLUDING A CODE |
| | COMPLIANCE OPINION OF THE RESIDENT INSPECTOR. |
| | |
| | 4) PAGE 043 FIRST FLOOR LIFE SAFETY: |
| | |
| | 4A) 2ND REQUEST!!! OCCUPANCY COUNT: |
| | |
| | EXAMPLE 1: COMPLIED. UNIT 111 IS 793 SQ. FT./ 200= |
| | 3.965IN EVERY CASE THE DESIGNER HAS DROPPED THE |
| | FRACTION OF AN OCCUPANT, YOU ROUND UP NOT DOWN TO THE |
| | NEXT WHOLE |
| | NUMBER. FBC-B 1004.1. ALSO SEE BOAF INFORMAL |
| | INTERPRETATION 5479. |
| | |
| | 4A) (1)2ND REQUEST. EXAMPLE 2: UNIT 110 IS LISTED AS A |
| | R OCCUPANCYFOR THIS BUILDING THIS IS A A-3 ASSEMBLY |
| | USAGE WITH A OCCUPANT LOADING FACTOR OF 15= 40 |
| | OCCUPANTS. THIS UNIT STILL SHOWS AS A (R) RESIDENTIAL |
| | UNIT AND OCCUPANT LOADING @ 200 SQ. FT/ OCCUPANT. |
| | |
| | 4A)(2) NEW NOTE. THE COMMOM WALL BETWEEN UNIT 110 (A3 |
| | ASSEMBLY) & UNIT 111 (R2) IS A OCCUPANCY SEPARATION |
| | WALL. 2010 FBC-B TABLE 508.4 REQUIRES A 2 HR FIRE |
| | SEPARATION WALL, NO REDUCTION IS GIVEN FOR A R-13 FIRE |
| | SPRINKLER SYSTEM. SEE FOOTNOTE S. |
| | |
| | |
| | 4B) SEMI-COMPLIED. UNITS 103 & 116 THE WINDOWS & DOORS |
| | IN THE FRONT OF THE UNIT WILL NEED TO BE 3/4 HR FIRE |
| | RATED EVEN THOUGH THERE IS 2 MEANS OF EGRESS, PLEASE |
| | SEE THE UNITS |
| | ON THE 2ND & 3RD FLOOR WITH DEAD END CONDITIONS. |
| | NEW NOTE: WITH THE 3/4 HR. FIRE RATING FOR THE WINDOWS |
| | THE REQUIREMENT FOR LARGE MISSILE RESISTANT RATED |
| | WINDOWS STILL EXIST. THE DESIGNER OF RECORD HAS THE |
| | CHOICE FOR THE FIRE |
| | RATED GLAZING & TESTING FOR LARGE MISSILE IMPACT |
| | GLAZING (VERY, VERY EXSPENSIVE) OR STORM SHUTTERS, IF |
| | STORM SHUTTERS ARE THE OPTION TO MEET CODE COMPLIANCE |
| | THE CITY WILL ALSO |
| | NEED PRODUCT APPROVAL TESTING FOR THE SHUTTER SYSTEM |
| | AND A SHUTTER SCHEDULE. |
| | |
| | PROVIDE STORM PANEL INFORMATION WITH INSTALLATION |
| | SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND |
| | MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC |
| | 1609.1.2. |
| | |
| | FL BLD CODE 2010 SECTION 107.2.5., & 1609.1.2, 1715.8 |
| | PROCEDURES: A COMPLETE INSTALLATION SCHEDULE |
| | SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS, |
| | UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR |
| | REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT |
| | TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT |
| | APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | |
| | 5) PAGE 044 2ND FLOOR LIFE SAFETY: |
| | 5A) COMPLIED. UPDATE OCCUPANT LOADS. |
| | |
| | 5B) SEMI-COMPLIED. UNITS 203 & 216, 3/4 HR FIRE RATING |
| | & STORM SHUTTERS (IF ELECTING STORM SHUTTERS). SEE |
| | COMMENT 4B. |
| | |
| | 6) PAGE 045 3RD FLOOR LIFE SAFETY: |
| | |
| | 5A) COMPLIED. UPDATE OCCUPANT LOADS. |
| | |
| | 6B) SEMI-COMPLIED. UNIT 316, DEAD END CORRIDORS THE |
| | WINDOWS IN THE FRONT OF THE UNIT WILL NEED TO BE 3/4 HR |
| | FIRE RATED. IF ELECTING STORM SHUTTERS PROVIDE STORM |
| | PANEL INFORMATION WITH INSTALLATION SCHEDULE AND KEY |
| | PLAN WITH SPECIFIC ANCHORS AND MOUNTING TO BE USED FOR |
| | ALL NON-IMPACT GLAZING. FBC 1609.1.2. |
| | |
| | 7) PAGE 49 SHEET 1A-0.40 ROOF ACCESS & ROOF PLAN: |
| | 7A-C) COMPLIED. |
| | |
| | 7D) 2ND REQUEST. RESPOSE SEE PAGE 109 - M5.2 DETAIL # |
| | 4. THIS DETAIL SHOWS THE ROOF TOP CONDENSOR STAND BASE |
| | PLATE BEING INSTALLED ON TOP OF THE BUILT UP ROOF, TWO |
| | ISSUES, ONE THERE IS NO PITCH PAN NOR IS THERE SHOWN |
| | THE ROOF TOP INSULATION AND HOW THIS EFFECTS THE |
| | FASTENING TO THE DECK. |
| | 1507.1 SCOPE. |
| | ROOF COVERINGS SHALL BE APPLIED IN ACCORDANCE WITH THE |
| | APPLICABLE PROVISIONS OF THIS SECTION AND THE |
| | MANUFACTURER?S INSTALLATION INSTRUCTIONS. |
| | COMMENT FROM 1ST REVIEW. PLEASE PROVIDE HOW THE A/C |
| | CONDENSOR ROOF TOP UNITS ARE GOING TO BE SECURED TO THE |
| | ROOF RACKS AND HOW THE ROOF RACKS ARE GOING TO BE |
| | SECURED TO THE CONCRETE ROOF DECK. PLEASE ALSO BE AWARE |
| | OF FBC-B TABLE 1509.7. |
| | |
| | 7E) DEFERRED SUBMITTAL, ROOF TOP INSULATION PROVIDE THE |
| | ROOFTOP PRODUCT APPROVAL FOR INSULATION, LAYOUT SHEET |
| | FOR SLOPE AND ANCHORS TO BE SUBMITTED TO THE DESIGNER |
| | OF RECORD, REVIEWED, AND SHOP DRAWING STAMP OF APPROVAL |
| | AND OR WITH NOTES BEFORE SUBMITTAL TO THE BUILDING |
| | DEPARTMENT. |
| | |
| | |
| | 7F) NEW COMMENT, DEALING WITH THE ROOF TOP ACCESS AND |
| | THE CENTER STAIRWAY. PLEASE REVIEW PAGES 056/ A1-1.04, |
| | 076-A1.401 DETAIL # 3 & 093-A-9.01 THE FLOORS 1-3 SHOW |
| | A OPEN STAIRWAY BUT THE STAIR GOING TO THE 4TH FLOOR |
| | ROOF TOP FLOOR SHOWS THE STAIR AS AN ENCLOSED |
| | STAIRWELL. PLEASE REVIEW: |
| | 2010 FBC-B 1026.3 OPEN SIDE. EXTERIOR EXIT RAMPS AND |
| | STAIRWAYS SERVING AS AN ELEMENT OF A REQUIRED MEANS OF |
| | EGRESS SHALL NOT LESS THAN 50 PERCENT OPEN ON ONE SIDE. |
| | OUTSIDE STAIRS SHALL BE ARRANGED TO RESTRICT THE |
| | ACCUMULATION OF SMOKE. |
| | |
| | 8) 2ND REQUEST. NEW SHEET084-1/ 1A-6.02 PLEASE PROVIDE |
| | THE ACTUAL TESTING REPORTS FOR THE KNAUF BATT |
| | INSULATION IN ACCORDANCE WITH 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| | ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| | CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| | EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| | OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| | THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| | ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| | FITTING TO THE FRAME AND SILL. |
| | |
| | |
| | |
| | |
| | |
| | 9) 2ND REQUEST. A NEW SHEET 084-1/ 1A-6.02 PROVIDES |
| | THAT EASY MAT WITH SOUNDGUARD 5MM TO BE USED FOR THE |
| | INSTALLATION. THE TEST THIS PRODUCT WAS TESTED ASTM |
| | E-2179-03 IS THE WRONG TEST , IT IS TO BE TESTED TO |
| | EITHER ASTM E 90 WITH A STC RATING OF NOT LESS THAN 50 |
| | OR ASTM E 492 IMPACT INSULATION OF NO TLESS THAN 50 |
| | (IIC). PROVIDE THE ACTUAL TESTING REPORT. |
| | |
| | THE PLANS DO NOT SHOW COMPLIANCE WITH IS 2010 FBC-B |
| | 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES |
| | BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A |
| | PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE |
| | AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS |
| | THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE |
| | WITH ASTM E 492. |
| | |
| | 10) PAGE 085 1A-7.01 WINDOW BUCK DETAIL # 4 IS ACTUALLY |
| | DRAWN WRONG, THE CODE SECTION DIRECTLY ABOVE IR STATES |
| | UNLESS OTHERWISE TWESTED BUCKS SHALL EXTEND BEYOND THE |
| | INTERIOR SURFACE OF THE WINDOE OR DOOR FRAME. FBC-B |
| | 1715.5.4.2. |
| | |
| | 11) PAGE 87 1A-7.03 DETAIL 3 INDICATES THE HAND RAIL @ |
| | 34 IN. A.F.F. PLEASE REVIEW FBC-B 1012.2 THE HEIGHT IS |
| | TO BE MEASURED FROM THE TREAD NOSING. |
| | |
| | 12) THE PRESSURES FOR THE ROOF FLAT SECTION ARE GOOD, |
| | NO ROOF ZONE 3 THE PAARAPET IS AT LEAST 3'-0" HIGH |
| | ELIMINATING ZONE 3. WINDOW AND DOOR PRESSURES ARE GOOD |
| | FOR A MEAN ROOF HEIGHT OF 32.5 FT. THE ISSUE WILL BE |
| | THE ROOF LEVEL OF THE PENTHOUSE SINCE THE LOCATION IS |
| | ABOVE 33 FT, NO SHINGLES MAY BE PUT ON A ROOF WITH A |
| | MEAN ROOF HEIGTH OF 33 FT, SEE NOA LIMITATION. IF THE |
| | WHOLE ROOFING STYLE IS TO CHANGE FROM SHINGLES THEN |
| | PRESSURES FOR A 4/12 ROOF WILL BE NEEDED FOR BOTH A |
| | MEAN ROOF HEIGHT OF 32.5 FT AND PENTHOUSE AT APPROX |
| | 41.0. FT. |
| | |
| | 13) THE PRODUCT APPROVALS DO NOT HAVE TO BE SUBMITTED |
| | AT THIS TIME. AS LONG AS THE WIND DESIGN AND PRESSURES |
| | ARE CORRECT, THE PRODUCT APPROVALS CAN BE SUBMITTED |
| | AFTER PERMIT ISSUANCE AS A DEFERRED SUBMITTAL, NO COST |
| | TO CONTRACTOR. THERE IS NO CONTRACTOR SIGNED ON, THEY |
| | THEN BID THE JOBS OUT, THE PRODUCT APPROVALS SUBMITTED |
| | TODAY MAY NOT BE WHAT IS ACTUAL SUBMITTED TO BE BUILT. |
| | IF THE DESIGNER OF RECORD WOULD PREFER TO HAVE THE |
| | PRODUCT APPROVALS DEFERRRED IN THE RESPONCE JUST NOTE |
| | SO. |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.3.4.2 DEFERRED |
| | SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| | BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL |
| | ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW |
| | THEM AND FORWARD THEM TO THE |
| | BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND |
| | FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF THE |
| | BUILDING. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE |
| | INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | 13A) NOA 12-0320.07 SUNSHINE 2000 SERIES SINGLE HUNG, |
| | LMI PLEASE CIRCLE THE UNITS HEIGHT, WIDTH, PRESSURES & |
| | ANCHORAGE. |
| | |
| | 13B) NOA 13-0122.05 SUNSHINE 8000 SERIES STOREFRONT, |
| | LMI PLEASE CIRCLE THE UNITS HEIGHT, WIDTH, PRESSURES & |
| | ANCHORAGE. |
| | |
| | 13C) NOA 11-1216.02 SUNSHINE MULLION CIRCLE WIDTH, |
| | SPAN, MULLION SIZE PRESSURES AND TYPE OF ANCHORS. |
| | |
| | 13D) NOA 14-0109.06 SUNSHINE ALUMINUM, OUTSWING FRENCH |
| | DOORS NOTE FLUSHBOLTS WILL NEED TO WORK FROM A WHEEL |
| | CHAIR POSITION, PLEASE CIRCLE THE UNITS HEIGHT, WIDTH, |
| | PRESSURES & ANCHORAGE. |
| | |
| | 13E) FL. 14237-R1 FLEMING BARON CIRCLE IF SINGLE OR |
| | PAIR, INSWEING OR OUT, TYPE OF LATCH ANCHORAGE AND |
| | ASSOCIATED PRESSURES. |
| | |
| | 13F) JOHN MANSVILLE TPO SINGLE PLY ROOFING OVER |
| | LIGHTWEIGHT CONCRETE DECK. NOA 14-0618.05 CIRCLE WHICH |
| | SUB-SYSTEM TO BE INSTALLED AND ASSOCIATED PRESSURES. |
| | |
| | 13G) NOA 13-1104.12 GAF TIMBERLINE ULTRA HD |
| | SHINGLESNOTE THIS PRODUCT UNDER LIMITATIONS IS NOT TO |
| | BE INSTALLED ABOVE 33 FT. THE PENTHOUSE ROOF IS WELL |
| | ABOVE THE 33 FT MEAN ROOF HEIGHT. |
| | |
| | 13H) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 14A) THE ENERGY CALCULATIONS INDICATE A VENTED ATTIC |
| | AND R-19 INSULATION, LOCATED WHERE? |
| | |
| | 14B) ROOF VENTILATION PAGE 049, 1A-0.40 THE PLANS |
| | INDICATE THE USE OF SOFFIT VENTILATION BUT DO NOT |
| | INDICATE COMPLIANCE WITH FBC-B 1203.2 50 PERCENT OF THE |
| | REQUIRED VENTILATING AREA PROVIDED BY VENTILATORS |
| | LOCATED IN THE UPPER PORTION OF THE SPACE TO BE |
| | VENTILATED AT LEAST 3 FEET (914 MM) ABOVE EAVE OR |
| | CORNICE VENTS WITH THE BALANCE OF THE REQUIRED |
| | VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. |
| | |
| | 15) THE ENERGY CALCULATIONS WILL NEED TO REFLECT THE |
| | VALUES FOR A1 END UNIT, B UNIT INTERIOR AS WELL AS A |
| | END UNIT, AND A A2 INTERIOR UNIT, ALL ON GRADE, THEN |
| | FOR 2ND FLOOR SUROUNDED ABOVE AND BELOW WITH A/C AND |
| | THE 3RD FLOOR UNITS WITH ROOF INSULATION OVERHEAD. |
| | |
| | 16) PLEASE PROVIDE THE WINDOW AND DOOR SHGC OF 0.5 |
| | FBC-ENERGY 402.3. |
| | |
| | 17) LIFE SAFETY SHEETS TO SHOW AREA OF RESCUE |
| | ASSISTANCE 2010 FBC-ACCESSIBILITY CODE 207.1. SEE |
| | SECTION 1007 OF THE 2003 IBC 107.6 AREA OF REFUGE. |
| | |
| | 18) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 19) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |