2015-03-09 14:13:31BUILDING PLAN REVIEW
 PERMIT: 14120686 BLDG # 2 / 50 UNITS
 ADD: 906 GRANT ST.
 CONT: T. B. D. /AYALA MANUEL
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 2ND REVIEW
 DATE: MON. MARCH 09/ 2015
 ACTION: DENIED
  
 NOTICE: !!!!!!!!!!!!!!! THE PERMIT APPLICATIONS NEED TO
 REFLECT THE CORRECT ADDRESS. THE PERMIT APPLICATIONS
 DOES NOT STATE BLDG. # 1 / 49 UNITS OR BLDG # 2 / 50
 UNITS. MY PLAN REVIEWS ARE AS FOLLOWS UNDER PERMIT #
 14120680 BLDG #1/ 49 UNITS AND PERMIT # 14120686 BLDG #
 2 /50 UNITS. CURRENTLY IT LOOKS LIKE THE BLDG COMMENTS
 FOR EACH BUILDING ARE UNDER THE WRONG PERMIT NUMBER
 SINCE WE TOOK BLDG # 1 WITH THE LOWER PERMIT NUMBER AS
 BLDG # 114120680 AND BLDG # 2 AS PERMIT # 14120686.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL.CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION OF WORK TO BE
 COMPLETED UNDER THIS PERMIT.
  
 THE ONLY DIFFERENCE IN THE COMMENTS WILL BE IN THE UNIT
 WILL AFFECT THE COMMENT 4A)(1-2) , THIS COMMENT DEALS
 WITH THE ASSEMBLY OCCUPANCY IN THE 49 UNIT APPRTMENT
 BUILDING.
  
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL.CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION OF WORK TO BE
 COMPLETED UNDER THIS PERMIT.
  
 1-2) COMPLIED.
  
 2ND REQUEST. 3) THIS PROJECT QUALIFIES FOR A RESIDENT
 INSPECTOR UNDER 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING
 OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE
 INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT
 REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION
 SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS
 SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A
 CERTIFICATE CALLED FOR BY ANY PROVISION OF THE
 TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS
 UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A
 RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING
 OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION
 SERVICE IN THE FOLLOWING INSTANCES:
 FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE FOOT
 FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION, TUNNEL FORM
  
 RESIDENT INSPECTOR BOOKLET & FORMS WILL BE E-MAILED TO:
 /AYALA MANUEL, E-MAIL: [email protected] SENT AT
 8:15 AM 01/12/2015
 THE RESIDENT INSPECTOR FORMS ARE TO BE COMPLETED AND
 RETURNED BACK TO THE CONSTRUCTION SERVICES DIVISION
 BEFORE PERMIT ISSUANCE.
  
 2ND REQUEST. 3A) DIGITAL REVIEW, ONCE THE PLANS ARE
 BATCH STAMPED, THE PERMIT IS ISSUED, PLEASE NOTIFY THE
 PERMIT LIBRIAN CAROLINE PUELL TO DOWN LOAD THE PLANS TO
 THE CONTACT PERSON, NOTE (2) COLOR SETS OF PLANS WILL
 NEED TO BE PRINTED, ONE FOR THE RESIDENT INSPECTOR THE
 OTHER FOR THE CITY MEP INSPECTORS.
  
 2ND REQUEST. 3B) PLEASE REMEMBER TO CALL IN ALL
 STRUCTURAL INSPECTIONS SINCE KEN CONRAD WILL BE
 AUDITING INSPECTIONS, ALSO IF THERE IS NO RECORD OF
 CALLED IN INSPECTIONS AFTER 6 MONTHS OF NO ACTIVITY THE
 PERMIT WILL EXPIRE. WPB ADMINISTRATIVE CODE 110.5
 INSPECTION REQUESTS. IT SHALL BE THE DUTY OF THE HOLDER
 OF THE BUILDING PERMIT OR THEIR DULY AUTHORIZED AGENT
 TO NOTIFY THE BUILDING OFFICIAL WHEN WORK IS READY FOR
 INSPECTION. IT SHALL BE THE DUTY OF THE PERMIT HOLDER
 TO PROVIDE ACCESS TO AND MEANS FOR INSPECTIONS OF SUCH
 WORK THAT ARE REQUIRED BY THIS CODE
  
 2ND REQUEST. 3C) 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 110.3.9 OTHER INSPECTIONS SERVICES. SUCH INSPECTORS
 SHALL BE ADEQUATELY PRESENT AT TIMES WORK IS UNDERWAY
 ON THE STRUCTURAL ELEMENTS OF THE BUILDING. SUCH
 INSPECTORS SHALL BE A REGISTERED ARCHITECT, OR
 ENGINEER, OR A PERSON LICENSED UNDER CHAPTER 468, PART
 XII, FLORIDA STATUTES. SUCH INSPECTORS SHALL SUBMIT
 WEEKLY PROGRESS REPORTS INCLUDING THE DAILY INSPECTIONS
 TO THE BUILDING OFFICIAL, AND INCLUDING A CODE
 COMPLIANCE OPINION OF THE RESIDENT INSPECTOR.
  
 4) PAGE 043 FIRST FLOOR LIFE SAFETY:
  
 4A) 2ND REQUEST!!! OCCUPANCY COUNT:
  
 EXAMPLE 1: COMPLIED. UNIT 111 IS 793 SQ. FT./ 200=
 3.965IN EVERY CASE THE DESIGNER HAS DROPPED THE
 FRACTION OF AN OCCUPANT, YOU ROUND UP NOT DOWN TO THE
 NEXT WHOLE
 NUMBER. FBC-B 1004.1. ALSO SEE BOAF INFORMAL
 INTERPRETATION 5479.
  
 4A) (1)2ND REQUEST. EXAMPLE 2: UNIT 110 IS LISTED AS A
 R OCCUPANCYFOR THIS BUILDING THIS IS A A-3 ASSEMBLY
 USAGE WITH A OCCUPANT LOADING FACTOR OF 15= 40
 OCCUPANTS. THIS UNIT STILL SHOWS AS A (R) RESIDENTIAL
 UNIT AND OCCUPANT LOADING @ 200 SQ. FT/ OCCUPANT.
  
 4A)(2) NEW NOTE. THE COMMOM WALL BETWEEN UNIT 110 (A3
 ASSEMBLY) & UNIT 111 (R2) IS A OCCUPANCY SEPARATION
 WALL. 2010 FBC-B TABLE 508.4 REQUIRES A 2 HR FIRE
 SEPARATION WALL, NO REDUCTION IS GIVEN FOR A R-13 FIRE
 SPRINKLER SYSTEM. SEE FOOTNOTE S.
  
  
 4B) SEMI-COMPLIED. UNITS 103 & 116 THE WINDOWS & DOORS
 IN THE FRONT OF THE UNIT WILL NEED TO BE 3/4 HR FIRE
 RATED EVEN THOUGH THERE IS 2 MEANS OF EGRESS, PLEASE
 SEE THE UNITS
 ON THE 2ND & 3RD FLOOR WITH DEAD END CONDITIONS.
 NEW NOTE: WITH THE 3/4 HR. FIRE RATING FOR THE WINDOWS
 THE REQUIREMENT FOR LARGE MISSILE RESISTANT RATED
 WINDOWS STILL EXIST. THE DESIGNER OF RECORD HAS THE
 CHOICE FOR THE FIRE
 RATED GLAZING & TESTING FOR LARGE MISSILE IMPACT
 GLAZING (VERY, VERY EXSPENSIVE) OR STORM SHUTTERS, IF
 STORM SHUTTERS ARE THE OPTION TO MEET CODE COMPLIANCE
 THE CITY WILL ALSO
 NEED PRODUCT APPROVAL TESTING FOR THE SHUTTER SYSTEM
 AND A SHUTTER SCHEDULE.
  
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.2.
  
 FL BLD CODE 2010 SECTION 107.2.5., & 1609.1.2, 1715.8
 PROCEDURES: A COMPLETE INSTALLATION SCHEDULE
 SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS,
 UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR
 REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
  
 5) PAGE 044 2ND FLOOR LIFE SAFETY:
 5A) COMPLIED. UPDATE OCCUPANT LOADS.
  
 5B) SEMI-COMPLIED. UNITS 203 & 216, 3/4 HR FIRE RATING
 & STORM SHUTTERS (IF ELECTING STORM SHUTTERS). SEE
 COMMENT 4B.
  
 6) PAGE 045 3RD FLOOR LIFE SAFETY:
  
 5A) COMPLIED. UPDATE OCCUPANT LOADS.
  
 6B) SEMI-COMPLIED. UNIT 316, DEAD END CORRIDORS THE
 WINDOWS IN THE FRONT OF THE UNIT WILL NEED TO BE 3/4 HR
 FIRE RATED. IF ELECTING STORM SHUTTERS PROVIDE STORM
 PANEL INFORMATION WITH INSTALLATION SCHEDULE AND KEY
 PLAN WITH SPECIFIC ANCHORS AND MOUNTING TO BE USED FOR
 ALL NON-IMPACT GLAZING. FBC 1609.1.2.
  
 7) PAGE 49 SHEET 1A-0.40 ROOF ACCESS & ROOF PLAN:
 7A-C) COMPLIED.
  
 7D) 2ND REQUEST. RESPOSE SEE PAGE 109 - M5.2 DETAIL #
 4. THIS DETAIL SHOWS THE ROOF TOP CONDENSOR STAND BASE
 PLATE BEING INSTALLED ON TOP OF THE BUILT UP ROOF, TWO
 ISSUES, ONE THERE IS NO PITCH PAN NOR IS THERE SHOWN
 THE ROOF TOP INSULATION AND HOW THIS EFFECTS THE
 FASTENING TO THE DECK.
 1507.1 SCOPE.
 ROOF COVERINGS SHALL BE APPLIED IN ACCORDANCE WITH THE
 APPLICABLE PROVISIONS OF THIS SECTION AND THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS.
 COMMENT FROM 1ST REVIEW. PLEASE PROVIDE HOW THE A/C
 CONDENSOR ROOF TOP UNITS ARE GOING TO BE SECURED TO THE
 ROOF RACKS AND HOW THE ROOF RACKS ARE GOING TO BE
 SECURED TO THE CONCRETE ROOF DECK. PLEASE ALSO BE AWARE
 OF FBC-B TABLE 1509.7.
  
 7E) DEFERRED SUBMITTAL, ROOF TOP INSULATION PROVIDE THE
 ROOFTOP PRODUCT APPROVAL FOR INSULATION, LAYOUT SHEET
 FOR SLOPE AND ANCHORS TO BE SUBMITTED TO THE DESIGNER
 OF RECORD, REVIEWED, AND SHOP DRAWING STAMP OF APPROVAL
 AND OR WITH NOTES BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT.
  
  
 7F) NEW COMMENT, DEALING WITH THE ROOF TOP ACCESS AND
 THE CENTER STAIRWAY. PLEASE REVIEW PAGES 056/ A1-1.04,
 076-A1.401 DETAIL # 3 & 093-A-9.01 THE FLOORS 1-3 SHOW
 A OPEN STAIRWAY BUT THE STAIR GOING TO THE 4TH FLOOR
 ROOF TOP FLOOR SHOWS THE STAIR AS AN ENCLOSED
 STAIRWELL. PLEASE REVIEW:
 2010 FBC-B 1026.3 OPEN SIDE. EXTERIOR EXIT RAMPS AND
 STAIRWAYS SERVING AS AN ELEMENT OF A REQUIRED MEANS OF
 EGRESS SHALL NOT LESS THAN 50 PERCENT OPEN ON ONE SIDE.
 OUTSIDE STAIRS SHALL BE ARRANGED TO RESTRICT THE
 ACCUMULATION OF SMOKE.
  
 8) 2ND REQUEST. NEW SHEET084-1/ 1A-6.02 PLEASE PROVIDE
 THE ACTUAL TESTING REPORTS FOR THE KNAUF BATT
 INSULATION IN ACCORDANCE WITH 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
  
  
  
  
 9) 2ND REQUEST. A NEW SHEET 084-1/ 1A-6.02 PROVIDES
 THAT EASY MAT WITH SOUNDGUARD 5MM TO BE USED FOR THE
 INSTALLATION. THE TEST THIS PRODUCT WAS TESTED ASTM
 E-2179-03 IS THE WRONG TEST , IT IS TO BE TESTED TO
 EITHER ASTM E 90 WITH A STC RATING OF NOT LESS THAN 50
 OR ASTM E 492 IMPACT INSULATION OF NO TLESS THAN 50
 (IIC). PROVIDE THE ACTUAL TESTING REPORT.
  
 THE PLANS DO NOT SHOW COMPLIANCE WITH IS 2010 FBC-B
 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES
 BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A
 PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE
 AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE
 WITH ASTM E 492.
  
 10) PAGE 085 1A-7.01 WINDOW BUCK DETAIL # 4 IS ACTUALLY
 DRAWN WRONG, THE CODE SECTION DIRECTLY ABOVE IR STATES
 UNLESS OTHERWISE TWESTED BUCKS SHALL EXTEND BEYOND THE
 INTERIOR SURFACE OF THE WINDOE OR DOOR FRAME. FBC-B
 1715.5.4.2.
  
 11) PAGE 87 1A-7.03 DETAIL 3 INDICATES THE HAND RAIL @
 34 IN. A.F.F. PLEASE REVIEW FBC-B 1012.2 THE HEIGHT IS
 TO BE MEASURED FROM THE TREAD NOSING.
  
 12) THE PRESSURES FOR THE ROOF FLAT SECTION ARE GOOD,
 NO ROOF ZONE 3 THE PAARAPET IS AT LEAST 3'-0" HIGH
 ELIMINATING ZONE 3. WINDOW AND DOOR PRESSURES ARE GOOD
 FOR A MEAN ROOF HEIGHT OF 32.5 FT. THE ISSUE WILL BE
 THE ROOF LEVEL OF THE PENTHOUSE SINCE THE LOCATION IS
 ABOVE 33 FT, NO SHINGLES MAY BE PUT ON A ROOF WITH A
 MEAN ROOF HEIGTH OF 33 FT, SEE NOA LIMITATION. IF THE
 WHOLE ROOFING STYLE IS TO CHANGE FROM SHINGLES THEN
 PRESSURES FOR A 4/12 ROOF WILL BE NEEDED FOR BOTH A
 MEAN ROOF HEIGHT OF 32.5 FT AND PENTHOUSE AT APPROX
 41.0. FT.
  
 13) THE PRODUCT APPROVALS DO NOT HAVE TO BE SUBMITTED
 AT THIS TIME. AS LONG AS THE WIND DESIGN AND PRESSURES
 ARE CORRECT, THE PRODUCT APPROVALS CAN BE SUBMITTED
 AFTER PERMIT ISSUANCE AS A DEFERRED SUBMITTAL, NO COST
 TO CONTRACTOR. THERE IS NO CONTRACTOR SIGNED ON, THEY
 THEN BID THE JOBS OUT, THE PRODUCT APPROVALS SUBMITTED
 TODAY MAY NOT BE WHAT IS ACTUAL SUBMITTED TO BE BUILT.
 IF THE DESIGNER OF RECORD WOULD PREFER TO HAVE THE
 PRODUCT APPROVALS DEFERRRED IN THE RESPONCE JUST NOTE
 SO.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.3.4.2 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL
 ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE
 BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND
 FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF THE
 BUILDING. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE
 INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN APPROVED BY THE BUILDING OFFICIAL.
  
 13A) NOA 12-0320.07 SUNSHINE 2000 SERIES SINGLE HUNG,
 LMI PLEASE CIRCLE THE UNITS HEIGHT, WIDTH, PRESSURES &
 ANCHORAGE.
  
 13B) NOA 13-0122.05 SUNSHINE 8000 SERIES STOREFRONT,
 LMI PLEASE CIRCLE THE UNITS HEIGHT, WIDTH, PRESSURES &
 ANCHORAGE.
  
 13C) NOA 11-1216.02 SUNSHINE MULLION CIRCLE WIDTH,
 SPAN, MULLION SIZE PRESSURES AND TYPE OF ANCHORS.
  
 13D) NOA 14-0109.06 SUNSHINE ALUMINUM, OUTSWING FRENCH
 DOORS NOTE FLUSHBOLTS WILL NEED TO WORK FROM A WHEEL
 CHAIR POSITION, PLEASE CIRCLE THE UNITS HEIGHT, WIDTH,
 PRESSURES & ANCHORAGE.
  
 13E) FL. 14237-R1 FLEMING BARON CIRCLE IF SINGLE OR
 PAIR, INSWEING OR OUT, TYPE OF LATCH ANCHORAGE AND
 ASSOCIATED PRESSURES.
  
 13F) JOHN MANSVILLE TPO SINGLE PLY ROOFING OVER
 LIGHTWEIGHT CONCRETE DECK. NOA 14-0618.05 CIRCLE WHICH
 SUB-SYSTEM TO BE INSTALLED AND ASSOCIATED PRESSURES.
  
 13G) NOA 13-1104.12 GAF TIMBERLINE ULTRA HD
 SHINGLESNOTE THIS PRODUCT UNDER LIMITATIONS IS NOT TO
 BE INSTALLED ABOVE 33 FT. THE PENTHOUSE ROOF IS WELL
 ABOVE THE 33 FT MEAN ROOF HEIGHT.
  
 13H) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 14A) THE ENERGY CALCULATIONS INDICATE A VENTED ATTIC
 AND R-19 INSULATION, LOCATED WHERE?
  
 14B) ROOF VENTILATION PAGE 049, 1A-0.40 THE PLANS
 INDICATE THE USE OF SOFFIT VENTILATION BUT DO NOT
 INDICATE COMPLIANCE WITH FBC-B 1203.2 50 PERCENT OF THE
 REQUIRED VENTILATING AREA PROVIDED BY VENTILATORS
 LOCATED IN THE UPPER PORTION OF THE SPACE TO BE
 VENTILATED AT LEAST 3 FEET (914 MM) ABOVE EAVE OR
 CORNICE VENTS WITH THE BALANCE OF THE REQUIRED
 VENTILATION PROVIDED BY EAVE OR CORNICE VENTS.
  
 15) THE ENERGY CALCULATIONS WILL NEED TO REFLECT THE
 VALUES FOR A1 END UNIT, B UNIT INTERIOR AS WELL AS A
 END UNIT, AND A A2 INTERIOR UNIT, ALL ON GRADE, THEN
 FOR 2ND FLOOR SUROUNDED ABOVE AND BELOW WITH A/C AND
 THE 3RD FLOOR UNITS WITH ROOF INSULATION OVERHEAD.
  
 16) PLEASE PROVIDE THE WINDOW AND DOOR SHGC OF 0.5
 FBC-ENERGY 402.3.
  
 17) LIFE SAFETY SHEETS TO SHOW AREA OF RESCUE
 ASSISTANCE 2010 FBC-ACCESSIBILITY CODE 207.1. SEE
 SECTION 1007 OF THE 2003 IBC 107.6 AREA OF REFUGE.
  
 18) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 19) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  