Plan Review Notes
Plan Review Notes For Permit 14120686
Permit Number 14120686
Review Stop P
Sequence Number 1
Notes
Date Text
2015-01-04 04:19:191) SUBMIT ROOF DRAINAGE CALCULATION FOR 1/2 THE AREA OF
 THE PARAPET WALL THAT IS TO BE INCLUDED WHEN SIZING THE
 ROOF DRAINAGE SYSTEM.
 2010 FL. PLBG. CODE SEC. 1106.4 VERTICAL WALLS.
 IN SIZING ROOF DRAINS AND STORM DRAINAGE PIPING,
 ONE-HALF OF THE AREA OF ANY VERTICAL WALL THAT DIVERTS
 RAINWATER TO THE ROOF SHALL BE ADDED TO THE PROJECTED
 ROOF AREA FOR INCLUSION IN CALCULATING THE REQUIRED
 SIZE OF VERTICAL CONDUCTORS, LEADERS AND HORIZONTAL
 STORM DRAINAGE PIPING.
 2) SHT. 1A-5.30 - DETAILS #1-3 - THE ELEVATIONS APPEAR
 TO SHOW CONFLICTING HEIGHT DETAILS FOR THE WATER CLOSET
 FROM THE FINISH FLOOR TO THE TOP OF THE WATER CLOSET
 SEAT. ONE VIEW SHOWS THE DISTANCE AS 17-19 INCHES TO
 THE TOP OF SEAT AND THE OTHER ELEVATION APPEARS TO SHOW
 THE HEIGHT TO THE TOP OF THE WATER CLOSET. CLARIFY.
 COMPLY WITH 2010 FAC SEC.604.4. REVIEW ELEVATIONS 2 A &
 2B & 3A & 3B.
 3) SHT. P1.1A & P1.1B - SHOW SUMP DISCHARGE PIPING FOR
 THE ELEVATIOR SHAFT. SUBMIT A DETAIL SHOWING THE PUMP
 AND ALL ASSOCIATED PIPING. WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 4) FLOOR DRAINS ARE SHOWN IN THE LOBBY AREA BUT ARE NOT
 SHOWN ON THE SANITARY RISER. CLARIFY. FLOOR DRAINS
 SHALL BE EQUIPPED WITH TRAP PRIMERS PER THE 2010 FPC
 SEC.1002.4.
 5) A WELL PERMIT WILL BE REQUIRED FROM THE PALM BEACH
 COUNTY HEALTH DEPT. FOR THE IRRIGATION WELL.
 6) SHT.S-1.1 REFERS TO SHT.S-5.1 FOR THE ELEVATOR PIT
 DETAIL. THERE IS NO ELEVATOR PIT DETAIL ON SHT.S-5.1.
 THE DETAIL IS ON SHT. S-5.2. REVISE THE NOTE TO
 REFERENCE THE CORRECT SHEET.
  
 FIRE PROTECTION
  
 1) JOB SPECIFICATION 211313 - PART 3- SEC. 3.4 (B)
 STATES THAT THE INSTALLATION OF THE SPRINKLER SYSTEM
 SHALL COMPLY WITH NFPA 13 BUT THE PLANS ARE FOR A 13R
 SYSTEM. CLARIFY.
 2) SHOW THE SIZE OF THE FDC LINE ON SHT.FPS.1.
 3) THE FIRE PROTECTION PLANS REFER TO THE 2007 EDITION
 OF NFPA 13R YET THE DESIGN AREA BOXES ON SHTS.FP2.2 &
 FP3.2 REFER TO THE 2010 EDITION. CLARIFY.
 4) CLEARLY IDENTIFY THE UNIT ON THE PLANS WHERE THE
 DESIGN AREAS ARE LOCATED. THE UNIT IS NOT IDENTIFIED ON
 THE PLANS ALTHOUGH THE UNIT NUMBER IS GIVEN.
  