| 2015-01-04 04:19:19 | 1) SUBMIT ROOF DRAINAGE CALCULATION FOR 1/2 THE AREA OF |
| | THE PARAPET WALL THAT IS TO BE INCLUDED WHEN SIZING THE |
| | ROOF DRAINAGE SYSTEM. |
| | 2010 FL. PLBG. CODE SEC. 1106.4 VERTICAL WALLS. |
| | IN SIZING ROOF DRAINS AND STORM DRAINAGE PIPING, |
| | ONE-HALF OF THE AREA OF ANY VERTICAL WALL THAT DIVERTS |
| | RAINWATER TO THE ROOF SHALL BE ADDED TO THE PROJECTED |
| | ROOF AREA FOR INCLUSION IN CALCULATING THE REQUIRED |
| | SIZE OF VERTICAL CONDUCTORS, LEADERS AND HORIZONTAL |
| | STORM DRAINAGE PIPING. |
| | 2) SHT. 1A-5.30 - DETAILS #1-3 - THE ELEVATIONS APPEAR |
| | TO SHOW CONFLICTING HEIGHT DETAILS FOR THE WATER CLOSET |
| | FROM THE FINISH FLOOR TO THE TOP OF THE WATER CLOSET |
| | SEAT. ONE VIEW SHOWS THE DISTANCE AS 17-19 INCHES TO |
| | THE TOP OF SEAT AND THE OTHER ELEVATION APPEARS TO SHOW |
| | THE HEIGHT TO THE TOP OF THE WATER CLOSET. CLARIFY. |
| | COMPLY WITH 2010 FAC SEC.604.4. REVIEW ELEVATIONS 2 A & |
| | 2B & 3A & 3B. |
| | 3) SHT. P1.1A & P1.1B - SHOW SUMP DISCHARGE PIPING FOR |
| | THE ELEVATIOR SHAFT. SUBMIT A DETAIL SHOWING THE PUMP |
| | AND ALL ASSOCIATED PIPING. WPB AMEND. TO 2010 FBC |
| | SEC.107.2.1. |
| | 4) FLOOR DRAINS ARE SHOWN IN THE LOBBY AREA BUT ARE NOT |
| | SHOWN ON THE SANITARY RISER. CLARIFY. FLOOR DRAINS |
| | SHALL BE EQUIPPED WITH TRAP PRIMERS PER THE 2010 FPC |
| | SEC.1002.4. |
| | 5) A WELL PERMIT WILL BE REQUIRED FROM THE PALM BEACH |
| | COUNTY HEALTH DEPT. FOR THE IRRIGATION WELL. |
| | 6) SHT.S-1.1 REFERS TO SHT.S-5.1 FOR THE ELEVATOR PIT |
| | DETAIL. THERE IS NO ELEVATOR PIT DETAIL ON SHT.S-5.1. |
| | THE DETAIL IS ON SHT. S-5.2. REVISE THE NOTE TO |
| | REFERENCE THE CORRECT SHEET. |
| | |
| | FIRE PROTECTION |
| | |
| | 1) JOB SPECIFICATION 211313 - PART 3- SEC. 3.4 (B) |
| | STATES THAT THE INSTALLATION OF THE SPRINKLER SYSTEM |
| | SHALL COMPLY WITH NFPA 13 BUT THE PLANS ARE FOR A 13R |
| | SYSTEM. CLARIFY. |
| | 2) SHOW THE SIZE OF THE FDC LINE ON SHT.FPS.1. |
| | 3) THE FIRE PROTECTION PLANS REFER TO THE 2007 EDITION |
| | OF NFPA 13R YET THE DESIGN AREA BOXES ON SHTS.FP2.2 & |
| | FP3.2 REFER TO THE 2010 EDITION. CLARIFY. |
| | 4) CLEARLY IDENTIFY THE UNIT ON THE PLANS WHERE THE |
| | DESIGN AREAS ARE LOCATED. THE UNIT IS NOT IDENTIFIED ON |
| | THE PLANS ALTHOUGH THE UNIT NUMBER IS GIVEN. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |