| 2015-01-23 10:38:32 | 1/23/2015 |
| | PROJECT: 50 MULTIFAMILY UNITS |
| | PERMIT#: 14120686 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | CLARIFICATION REQUIRED. WPB AMENDMENTS TO FBC 107.3. |
| | PLEASE REVISE THE RISER AND/OR PANEL SCHEDULE FOR PANEL |
| | MDP.SEE NOTES BELOW FOR CLARIFICATION: |
| | |
| | 1) THE RISER INDICATES A 200AMP DISCONNECT FUSED AT |
| | 150AMPS FOR THE ELEVATOR CONTROL CIRCUIT, AND THE PANEL |
| | SCHEDULE CALLS FOR A 125AMP BREAKER FEEDING THIS |
| | CIRCUIT. |
| | |
| | 2) THE RISER INDICATES NOTE 4, A 3/0 FEEDER FEEDING |
| | PANEL H1AND THE PANEL SCHEDULE CALLS FOR A 250AMP |
| | BREAKER WITH A 250MCM FEEDER FOR THIS CIRCUIT. |
| | |
| | 3) ADD A FEEDER SCHEDULE KEY NOTE FOR THE FEEDER FROM |
| | MDP TO THE ELEVATOR CONTROL DISCONNECT.. |
| | |
| | 4) THE RISER INDICATE A 3POLE 30AMP DISCONNECT FUSED AT |
| | 20AMP FOR ELEVATOR CAB LIGHTS BUT THE PANEL SCHEDULE IN |
| | MDP CALLS FOR A 2POLE 20AMP BREAKER FEEDING THIS |
| | CIRCUIT. |
| | |
| | 5) ADD A FEEDER SCHEDULE KEY NOTE FOR THE FEEDER FROM |
| | MDP TO THE ELEVATOR CAB LIGHTS. |
| | |
| | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD |
| | EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY, |
| | CCTV, NETWORK, DATA, AND, COMMUNICATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |