Plan Review Notes
Plan Review Notes For Permit 14120686
Permit Number 14120686
Review Stop B
Sequence Number 1
Notes
Date Text
2015-01-13 07:07:59BUILDING PLAN REVIEW
 PERMIT: 14120686
 ADD: 806 GRANT ST.
 CONT: T. B. D. /AYALA MANUEL
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 13/ 2015
 ACTION: DENIED
  
 NOTE, THE PERMIT APPLICATION HAS THE ADDRESS OF 906
 GRANT ST, SHOULDN' T IT BE 806 GRANT ST. THE PCN OF
 74434316230010010 ALSO DOES NOT EXIST!!!!!!
 1) FRAME 42/ 1A-0.03;
  
 1A) PAGE 042 1A-0.03 CODE INFORMATION SHEET. UNDER THE
 HEADING CODE RESEARCH & TABULATION, MAXIMUM AREA FOR
 BLDG. # 1 THE AREA FOR THE 1ST FLOOR IS 17,614 SQ. FT.
 (PROVIDED), 21,000 SQ. FT. (ALLOWED) SINCE THIS IS A
 13R SPRINKLER SPRINKLER INCREASES CAN NOT BE TAKEN,
 PLEASE SHOW CALCULATIONS FOR THE FRONTAGE INCREASES
 TAKEN SEE 2010 FBC-B 506.2.
  
 1B) TABLE FOR RATED FIRE RESISTANCE PERIODS FOR VARIOUS
 WALLS AND PARTITIONS TABLE 720.1(2) PLEASE PROVIDE WHAT
 THE MINIMUM COVERAGE WILL BE FOR WALLS AND SLABS, THE
 INSPECTORS WILL NOT HAVE THEIR CODE BOOKS TO LOOK UP
 THE MINIMUM COVERAGE FOR A REQUIRED 1 HR FIRE RATING.
  
 1C) TABLE FOR RATED FIRE RESISSTANCE PERIODS FOR
 VARIOUS WALLS AND PARTITIONS TABLE 720.1(2) IS THE ONLY
 TABLE LISTED FOR STRUCTURAL ELEMENTS, PLEASE REVIEW THE
 STRUCTURAL SHEETS FOR THE 2ND FLOOR AND 3RD FLOOR, SC-1
 STEEL COLUMNS DO NOT PROVIDE HOW THEY ARE GOING TO BE
 FIRE RESISTANCE PROTECTED, THEY MAY BE ON THE EXTERIOR,
 BUT THEY ARE ALSO WITHIN 10 FT. OF GLAZED OPENINGS THAT
 IN A FIRE INCIDENT WILL BE AFFECTED, PARTOF THE
 STRUCTURAL SYSTEM. TABLE 601.
  
 2) SHEET S4.2 INDICATES THE EXISTANCE OF ASOILS REPORT
 BY ARDAMIN & ASSOC. FILE# 14-1657 MAY 23/ 14TH. PLEASE
 SUBMIT 3 ORIGINAL SIGNED & SEALED REPORTS.
  
 3) THIS PROJECT QUALIFIES FOR A RESIDENT INSPECTOR
 UNDER 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING
 OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE
 INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT
 REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION
 SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS
 SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A
 CERTIFICATE CALLED FOR BY ANY PROVISION OF THE
 TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS
 UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A
 RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING
 OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION
 SERVICE IN THE FOLLOWING INSTANCES:
 FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE FOOT
 FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION, TUNNEL FORM
  
 RESIDENT INSPECTOR BOOKLET & FORMS WILL BE E-MAILED TO:
 /AYALA MANUEL, E-MAIL: [email protected] SENT AT
 8:15 AM 01/12/2015
 THE RESIDENT INSPECTOR FORMS ARE TO BE COMPLETED AND
 RETURNED BACK TO THE CONSTRUCTION SERVICES DIVISION
 BEFORE PERMIT ISSUANCE.
  
 3A) DIGITAL REVIEW, ONCE THE PLANS ARE BATCH STAMPED,
 THE PERMIT IS ISSUED, PLEASE NOTIFY THE PERMIT LIBRIAN
 CAROLINE PUELL TO DOWN LOAD THE PLANS TO THE CONTACT
 PERSON, NOTE (2) COLOR SETS OF PLANS WILL NEED TO BE
 PRINTED, ONE FOR THE RESIDENT INSPECTOR THE OTHER FOR
 THE CITY MEP INSPECTORS.
  
 3B) PLEASE REMEMBER TO CALL IN ALL STRUCTURAL
 INSPECTIONS SINCE KEN CONRAD WILL BE AUDITING
 INSPECTIONS, ALSO IF THERE IS NO RECORD OF CALLED IN
 INSPECTIONS AFTER 6 MONTHS OF NO ACTIVITY THE PERMIT
 WILL EXPIRE. WPB ADMINISTRATIVE CODE 110.5 INSPECTION
 REQUESTS. IT SHALL BE THE DUTY OF THE HOLDER OF THE
 BUILDING PERMIT OR THEIR DULY AUTHORIZED AGENT TO
 NOTIFY THE BUILDING OFFICIAL WHEN WORK IS READY FOR
 INSPECTION. IT SHALL BE THE DUTY OF THE PERMIT HOLDER
 TO PROVIDE ACCESS TO AND MEANS FOR INSPECTIONS OF SUCH
 WORK THAT ARE REQUIRED BY THIS CODE
  
 3C) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. SUCH INSPECTORS SHALL BE
 ADEQUATELY PRESENT AT TIMES WORK IS UNDERWAY ON THE
 STRUCTURAL ELEMENTS OF THE BUILDING. SUCH INSPECTORS
 SHALL BE A REGISTERED ARCHITECT, OR ENGINEER, OR A
 PERSON LICENSED UNDER CHAPTER 468, PART XII, FLORIDA
 STATUTES. SUCH INSPECTORS SHALL SUBMIT WEEKLY PROGRESS
 REPORTS INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
  
 4) PAGE 043 FIRST FLOOR LIFE SAFETY:
 4A) THE LIFE SAFETY LEGEND DEPICT A TAG WITH OCCUPANCY,
 SQUARE FT. , OCCUPANT LOAD FACTOR AND NUMBER OF
 OCCUPANTS, WHEN YOU LOOK AT ANY UNIT YOU WILL SEE THE
 SAME ISSUE,:
 EXAMPLE 1: UNIT 111 IS 793 SQ. FT./ 200= 3.965IN EVERY
 CASE THE DESIGNER HAS DROPPED THE FRACTION OF AN
 OCCUPANT, YOU ROUND UP NOT DOWN TO THE NEXT WHOLE
 NUMBER. FBC-B 1004.1. ALSO SEE BOAF INFORMAL
 INTERPRETATION 5479.
  
 4B) UNITS 103 & 116 THE WINDOWS & DOORS IN THE FRONT OF
 THE UNIT WILL NEED TO BE 3/4 HR FIRE RATED EVEN THOUGH
 THERE IS 2 MEANSA OF EGRESS, PLEASE SEE THE UNITS ON
 THE 2ND & 3RD FLOOR WITH DEAD END CONDITIONS.
 2010 FBC-B 1019.2 WALL SEPARATION. EXTERIOR EGRESS
 BALCONIES SHALL BE SEPARATED FROM THE INTERIOR OF THE
 BUILDING BY WALLS AND OPENING PROTECTIVES AS REQUIRED
 FOR CORRIDORS. EXCEPTION: SEPARATION IS NOT REQUIRED
 WHERE THE EXTERIOR EGRESS BALCONY IS SERVED BY AT LEAST
 TWO STAIRS AND A DEAD-END TRAVEL CONDITION DOES NOT
 REQUIRE TRAVEL PAST AN UNPROTECTED OPENING TO REACH A
 STAIR. 026.6 EXTERIOR RAMPS AND STAIRWAY PROTECTION.
 EXTERIOR EXIT RAMPS AND STAIRWAYS SHALL BE SEPARATED
 FROM THE INTERIOR OF THE BUILDING AS REQUIRED IN
 SECTION 1022.1 ALSO SEE 2007 FBC-B CODE COMMENTARY
 FIGURE 1023.6(1).
  
 5) PAGE 044 2ND FLOOR LIFE SAFETY:
 5A) UPDATE OCCUPANT LOADS TO REFLECT PARTIAL OCCUPANTS
 ROUNDED UP TO WHOLE PEOPLE, SEE COMMENT 4A EXAMPLE 1,
 FBC-B 1004.1 BOAF INFORMAL INTERPRETATION 5479.
  
 5B) UNITS 203 & 216, DEAD END CORRIDORS THE WINDOWS IN
 THE FRONT OF THE UNIT WILL NEED TO BE 3/4 HR FIRE
 RATED.
 2010 FBC-B 1019.2 WALL SEPARATION. EXTERIOR EGRESS
 BALCONIES SHALL BE SEPARATED FROM THE INTERIOR OF THE
 BUILDING BY WALLS AND OPENING PROTECTIVES AS REQUIRED
 FOR CORRIDORS. EXCEPTION: SEPARATION IS NOT REQUIRED
 WHERE THE EXTERIOR EGRESS BALCONY IS SERVED BY AT LEAST
 TWO STAIRS AND A DEAD-END TRAVEL CONDITION DOES NOT
 REQUIRE TRAVEL PAST AN UNPROTECTED OPENING TO REACH A
 STAIR. 026.6 EXTERIOR RAMPS AND STAIRWAY PROTECTION.
 EXTERIOR EXIT RAMPS AND STAIRWAYS SHALL BE SEPARATED
 FROM THE INTERIOR OF THE BUILDING AS REQUIRED IN
 SECTION 1022.1 ALSO SEE 2007 FBC-B CODE COMMENTARY
 FIGURE 1023.6(1).
  
 6) PAGE 045 3RD FLOOR LIFE SAFETY:
 5A) UPDATE OCCUPANT LOADS TO REFLECT PARTIAL OCCUPANTS
 ROUNDED UP TO WHOLE PEOPLE, SEE COMMENT 4A EXAMPLE 1,
 FBC-B 1004.1 BOAF INFORMAL INTERPRETATION 5479.
  
 6B) UNIT 216, DEAD END CORRIDORS THE WINDOWS IN THE
 FRONT OF THE UNIT WILL NEED TO BE 3/4 HR FIRE RATED.
 2010 FBC-B 1019.2 WALL SEPARATION. EXTERIOR EGRESS
 BALCONIES SHALL BE SEPARATED FROM THE INTERIOR OF THE
 BUILDING BY WALLS AND OPENING PROTECTIVES AS REQUIRED
 FOR CORRIDORS. EXCEPTION: SEPARATION IS NOT REQUIRED
 WHERE THE EXTERIOR EGRESS BALCONY IS SERVED BY AT LEAST
 TWO STAIRS AND A DEAD-END TRAVEL CONDITION DOES NOT
 REQUIRE TRAVEL PAST AN UNPROTECTED OPENING TO REACH A
 STAIR. 026.6 EXTERIOR RAMPS AND STAIRWAY PROTECTION.
 EXTERIOR EXIT RAMPS AND STAIRWAYS SHALL BE SEPARATED
 FROM THE INTERIOR OF THE BUILDING AS REQUIRED IN
 SECTION 1022.1 ALSO SEE 2007 FBC-B CODE COMMENTARY
 FIGURE 1023.6(1).
  
 7) PAGE 49 SHEET 1A-0.40 ROOF ACCESS & ROOF PLAN:
 7A) ROOF PLAN AND ROOF ACCESS SHOWS THE ELEVATOR
 CONTROL CLOSET WITHIN THE VERTICAL EXIT.2010 FBC-B AN
 EXIT ENCLOSURE SHALL NOT BE USED FOR ANY PURPOSE OTHER
 THAN MEANS OF EGRESS.
 1022.4 PENETRATIONS. PENETRATIONS INTO AND OPENINGS
 THROUGH AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR
 REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY
 FOR INDEPENDENT VENTILATION OR PRESSURIZATION,
 SPRINKLER PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR
 FIRE DEPARTMENT COMMUNICATION SYSTEMS AND ELECTRICAL
 RACEWAY SERVING THE EXIT ENCLOSURE AND TERMINATING AT A
 STEEL BOX NOT EXCEEDING 16 SQUARE INCHES (0.010 M2).
 SUCH PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 713. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT EXIT ENCLOSURES.
 1022.3 OPENINGS AND PENETRATIONS.EXIT ENCLOSURE OPENING
 PROTECTIVES SHALL BE IN ACCORDANCE WITH THE
 REQUIREMENTS OF SECTION 715. OPENINGS IN EXIT
 ENCLOSURES OTHER THAN UNPROTECTED EXTERIOR OPENINGS
 SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT ACCESS TO
 THE ENCLOSURE FROM NORMALLY OCCUPIED SPACES AND FOR
 EGRESS FROM THE ENCLOSURE.
  
 7B) THE ELEVATOR MACHINE ROOM DOES NOT SHOW ANY FIRE
 RATING ON EITHER THE WALLS OR OPENING PROTECTION.
 PLEASE SHOW COMPLIANCE WITH FBC-B 3006.4.
  
 7C) THIS SHEET INDICATES THE FINISH FLOOR HEIGHT ABOVE
 GRAGE IS 29'-6" THE MEAN ROOF HEIGHT OF THE TOWER
 ENCLOSE IS GREATER THAN 33 FT. THE SUBMITTED ROOFING
 APPROVAL GAF TIMBERLINE ULTRA HD SHINGLES NOA
 13-1104.12 LIMITATION # 2 LIMITS THE INSTALATION OF
 THIS PRODUCT TO 33 FT. MEAN ROOF HEIGHT.THE TOP OF THE
 ELEVATOR SHAFT IS AT 38'-0".
  
 7D) PLEASE PROVIDE HOW THE A/C CONDENSATE ROOF TOP
 UNITS ARE GOING TO BE SECURED TO THE ROOF RACKS AND HOW
 THE ROOF RACKS ARE GOING TO BE SECURED TO THE CONCRETE
 ROOF DECK. PLEASE ALSO BE AWARE OF FBC-B TABLE 1509.7.
  
 7E) HOW WILL THE 3RD FLOOR UNITS BENEATH THE FLAT
 ROOFED AREA ACHIEVE THE R-19 VALUE REQUIRED BY THE
 ENERGY CODE AND SUMMARY REPORT SUBMITTED.
  
 8) THE PLANS DO NOT PROVIDE HOW COMPLIANCE WITH
 AIR-BORNE SOUND, SHEET 1A-7.02 DETAIL #4 SHOWS A PARTY
 WALL TYPE CONFIGURATION BUT NOT SHOWING COMPLIANCE WITH
 2010 FBC-B 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 9) THE OTHER ISSUE THE PLANS DO NOT SHOW COMPLIANCE
 WITH IS 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 10) PAGE 085 1A-7.01 WINDOW BUCK DETAIL # 4 IS ACTUALLY
 DRAWN WRONG, THE CODE SECTION DIRECTLY ABOVE IR STATES
 UNLESS OTHERWISE TWESTED BUCKS SHALL EXTEND BEYOND THE
 INTERIOR SURFACE OF THE WINDOE OR DOOR FRAME. FBC-B
 1715.5.4.2.
  
 11) PAGE 87 1A-7.03 DETAIL 3 INDICATES THE HAND RAIL @
 34 IN. A.F.F. PLEASE REVIEW FBC-B 1012.2 THE HEIGHT IS
 TO BE MEASURED FROM THE TREAD NOSING.
  
 12) THE PRESSURES FOR THE ROOF FLAT SECTION ARE GOOD,
 NO ROOF ZONE 3 THE PAARAPET IS AT LEAST 3'-0" HIGH
 ELIMINATING ZONE 3. WINDOW AND DOOR PRESSURES ARE GOOD
 FOR A MEAN ROOF HEIGHT OF 32.5 FT. THE ISSUE WILL BE
 THE ROOF LEVEL OF THE PENTHOUSE SINCE THE LOCATION IS
 ABOVE 33 FT, NO SHINGLES MAY BE PUT ON A ROOF WITH A
 MEAN ROOF HEIGTH OF 33 FT, SEE NOA LIMITATION. IF THE
 WHOLE ROOFING STYLE IS TO CHANGE FROM SHINGLES THEN
 PRESSURES FOR A 4/12 ROOF WILL BE NEEDED FOR BOTH A
 MEAN ROOF HEIGHT OF 32.5 FT AND PENTHOUSE AT APPROX
 41.0. FT.
  
 13) THE PRODUCT APPROVALS DO NOT HAVE TO BE SUBMITTED
 AT THIS TIME. AS LONG AS THE WIND DESIGN AND PRESSURES
 ARE CORRECT, THE PRODUCT APPROVALS CAN BE SUBMITTED
 AFTER PERMIT ISSUANCE AS A DEFERRED SUBMITTAL, NO COST
 TO CONTRACTOR. THERE IS NO CONTRACTOR SIGNED ON, THEY
 THEN BID THE JOBS OUT, THE PRODUCT APPROVALS SUBMITTED
 TODAY MAY NOT BE WHAT IS ACTUAL SUBMITTED TO BE BUILT.
 IF THE DESIGNER OF RECORD WOULD PREFER TO HAVE THE
 PRODUCT APPROVALS DEFERRRED IN THE RESPONCE JUST NOTE
 SO.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.3.4.2 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL
 ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE
 BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND
 FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF THE
 BUILDING. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE
 INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN APPROVED BY THE BUILDING OFFICIAL.
  
 13A) NOA 12-0320.07 SUNSHINE 2000 SERIES SINGLE HUNG,
 LMI PLEASE CIRCLE THE UNITS HEIGHT, WIDTH, PRESSURES &
 ANCHORAGE.
  
 13B) NOA 13-0122.05 SUNSHINE 8000 SERIES STOREFRONT,
 LMI PLEASE CIRCLE THE UNITS HEIGHT, WIDTH, PRESSURES &
 ANCHORAGE.
  
 13C) NOA 11-1216.02 SUNSHINE MULLION CIRCLE WIDTH,
 SPAN, MULLION SIZE PRESSURES AND TYPE OF ANCHORS.
  
 13D) NOA 14-0109.06 SUNSHINE ALUMINUM, OUTSWING FRENCH
 DOORS NOTE FLUSHBOLTS WILL NEED TO WORK FROM A WHEEL
 CHAIR POSITION, PLEASE CIRCLE THE UNITS HEIGHT, WIDTH,
 PRESSURES & ANCHORAGE.
  
 13E) FL. 14237-R1 FLEMING BARON CIRCLE IF SINGLE OR
 PAIR, INSWEING OR OUT, TYPE OF LATCH ANCHORAGE AND
 ASSOCIATED PRESSURES.
  
 13F) JOHN MANSVILLE TPO SINGLE PLY ROOFING OVER
 LIGHTWEIGHT CONCRETE DECK. NOA 14-0618.05 CIRCLE WHICH
 SUB-SYSTEM TO BE INSTALLED AND ASSOCIATED PRESSURES.
  
 13G) NOA 13-1104.12 GAF TIMBERLINE ULTRA HD
 SHINGLESNOTE THIS PRODUCT UNDER LIMITATIONS IS NOT TO
 BE INSTALLED ABOVE 33 FT. THE PENTHOUSE ROOF IS WELL
 ABOVE THE 33 FT MEAN ROOF HEIGHT.
  
 13H) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 14A) THE ENERGY CALCULATIONS INDICATE A VENTED ATTIC
 AND R-19 INSULATION, LOCATED WHERE?
  
 14B) ROOF VENTILATION PAGE 049, 1A-0.40 THE PLANS
 INDICATE THE USE OF SOFFIT VENTILATION BUT DO NOT
 INDICATE COMPLIANCE WITH FBC-B 1203.2 50 PERCENT OF THE
 REQUIRED VENTILATING AREA PROVIDED BY VENTILATORS
 LOCATED IN THE UPPER PORTION OF THE SPACE TO BE
 VENTILATED AT LEAST 3 FEET (914 MM) ABOVE EAVE OR
 CORNICE VENTS WITH THE BALANCE OF THE REQUIRED
 VENTILATION PROVIDED BY EAVE OR CORNICE VENTS.
  
 15) THE ENERGY CALCULATIONS WILL NEED TO REFLECT THE
 VALUES FOR A1 END UNIT, B UNIT INTERIOR AS WELL AS A
 END UNIT, AND A A2 INTERIOR UNIT, ALL ON GRADE, THEN
 FOR 2ND FLOOR SUROUNDED ABOVE AND BELOW WITH A/C AND
 THE 3RD FLOOR UNITS WITH ROOF INSULATION OVERHEAD.
  
 16) PLEASE PROVIDE THE WINDOW AND DOOR SHGC OF 0.5
 FBC-ENERGY 402.3.
  
 17) LIFE SAFETY SHEETS TO SHOW AREA OF RESCUE
 ASSISTANCE 2010 FBC-ACCESSIBILITY CODE 207.1. SEE
 SECTION 1007 OF THE 2003 IBC 107.6 AREA OF REFUGE.
  
 18) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 19) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  