| 2015-01-13 07:07:59 | BUILDING PLAN REVIEW |
| | PERMIT: 14120686 |
| | ADD: 806 GRANT ST. |
| | CONT: T. B. D. /AYALA MANUEL |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JAN. 13/ 2015 |
| | ACTION: DENIED |
| | |
| | NOTE, THE PERMIT APPLICATION HAS THE ADDRESS OF 906 |
| | GRANT ST, SHOULDN' T IT BE 806 GRANT ST. THE PCN OF |
| | 74434316230010010 ALSO DOES NOT EXIST!!!!!! |
| | 1) FRAME 42/ 1A-0.03; |
| | |
| | 1A) PAGE 042 1A-0.03 CODE INFORMATION SHEET. UNDER THE |
| | HEADING CODE RESEARCH & TABULATION, MAXIMUM AREA FOR |
| | BLDG. # 1 THE AREA FOR THE 1ST FLOOR IS 17,614 SQ. FT. |
| | (PROVIDED), 21,000 SQ. FT. (ALLOWED) SINCE THIS IS A |
| | 13R SPRINKLER SPRINKLER INCREASES CAN NOT BE TAKEN, |
| | PLEASE SHOW CALCULATIONS FOR THE FRONTAGE INCREASES |
| | TAKEN SEE 2010 FBC-B 506.2. |
| | |
| | 1B) TABLE FOR RATED FIRE RESISTANCE PERIODS FOR VARIOUS |
| | WALLS AND PARTITIONS TABLE 720.1(2) PLEASE PROVIDE WHAT |
| | THE MINIMUM COVERAGE WILL BE FOR WALLS AND SLABS, THE |
| | INSPECTORS WILL NOT HAVE THEIR CODE BOOKS TO LOOK UP |
| | THE MINIMUM COVERAGE FOR A REQUIRED 1 HR FIRE RATING. |
| | |
| | 1C) TABLE FOR RATED FIRE RESISSTANCE PERIODS FOR |
| | VARIOUS WALLS AND PARTITIONS TABLE 720.1(2) IS THE ONLY |
| | TABLE LISTED FOR STRUCTURAL ELEMENTS, PLEASE REVIEW THE |
| | STRUCTURAL SHEETS FOR THE 2ND FLOOR AND 3RD FLOOR, SC-1 |
| | STEEL COLUMNS DO NOT PROVIDE HOW THEY ARE GOING TO BE |
| | FIRE RESISTANCE PROTECTED, THEY MAY BE ON THE EXTERIOR, |
| | BUT THEY ARE ALSO WITHIN 10 FT. OF GLAZED OPENINGS THAT |
| | IN A FIRE INCIDENT WILL BE AFFECTED, PARTOF THE |
| | STRUCTURAL SYSTEM. TABLE 601. |
| | |
| | 2) SHEET S4.2 INDICATES THE EXISTANCE OF ASOILS REPORT |
| | BY ARDAMIN & ASSOC. FILE# 14-1657 MAY 23/ 14TH. PLEASE |
| | SUBMIT 3 ORIGINAL SIGNED & SEALED REPORTS. |
| | |
| | 3) THIS PROJECT QUALIFIES FOR A RESIDENT INSPECTOR |
| | UNDER 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING |
| | OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE |
| | INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT |
| | REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION |
| | SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS |
| | SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A |
| | CERTIFICATE CALLED FOR BY ANY PROVISION OF THE |
| | TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS |
| | UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A |
| | RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING |
| | OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION |
| | SERVICE IN THE FOLLOWING INSTANCES: |
| | FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE FOOT |
| | FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| | FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| | METHODS OF CONSTRUCTION, TUNNEL FORM |
| | |
| | RESIDENT INSPECTOR BOOKLET & FORMS WILL BE E-MAILED TO: |
| | /AYALA MANUEL, E-MAIL: [email protected] SENT AT |
| | 8:15 AM 01/12/2015 |
| | THE RESIDENT INSPECTOR FORMS ARE TO BE COMPLETED AND |
| | RETURNED BACK TO THE CONSTRUCTION SERVICES DIVISION |
| | BEFORE PERMIT ISSUANCE. |
| | |
| | 3A) DIGITAL REVIEW, ONCE THE PLANS ARE BATCH STAMPED, |
| | THE PERMIT IS ISSUED, PLEASE NOTIFY THE PERMIT LIBRIAN |
| | CAROLINE PUELL TO DOWN LOAD THE PLANS TO THE CONTACT |
| | PERSON, NOTE (2) COLOR SETS OF PLANS WILL NEED TO BE |
| | PRINTED, ONE FOR THE RESIDENT INSPECTOR THE OTHER FOR |
| | THE CITY MEP INSPECTORS. |
| | |
| | 3B) PLEASE REMEMBER TO CALL IN ALL STRUCTURAL |
| | INSPECTIONS SINCE KEN CONRAD WILL BE AUDITING |
| | INSPECTIONS, ALSO IF THERE IS NO RECORD OF CALLED IN |
| | INSPECTIONS AFTER 6 MONTHS OF NO ACTIVITY THE PERMIT |
| | WILL EXPIRE. WPB ADMINISTRATIVE CODE 110.5 INSPECTION |
| | REQUESTS. IT SHALL BE THE DUTY OF THE HOLDER OF THE |
| | BUILDING PERMIT OR THEIR DULY AUTHORIZED AGENT TO |
| | NOTIFY THE BUILDING OFFICIAL WHEN WORK IS READY FOR |
| | INSPECTION. IT SHALL BE THE DUTY OF THE PERMIT HOLDER |
| | TO PROVIDE ACCESS TO AND MEANS FOR INSPECTIONS OF SUCH |
| | WORK THAT ARE REQUIRED BY THIS CODE |
| | |
| | 3C) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER |
| | INSPECTIONS SERVICES. SUCH INSPECTORS SHALL BE |
| | ADEQUATELY PRESENT AT TIMES WORK IS UNDERWAY ON THE |
| | STRUCTURAL ELEMENTS OF THE BUILDING. SUCH INSPECTORS |
| | SHALL BE A REGISTERED ARCHITECT, OR ENGINEER, OR A |
| | PERSON LICENSED UNDER CHAPTER 468, PART XII, FLORIDA |
| | STATUTES. SUCH INSPECTORS SHALL SUBMIT WEEKLY PROGRESS |
| | REPORTS INCLUDING THE DAILY INSPECTIONS TO THE BUILDING |
| | OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF |
| | THE RESIDENT INSPECTOR. |
| | |
| | 4) PAGE 043 FIRST FLOOR LIFE SAFETY: |
| | 4A) THE LIFE SAFETY LEGEND DEPICT A TAG WITH OCCUPANCY, |
| | SQUARE FT. , OCCUPANT LOAD FACTOR AND NUMBER OF |
| | OCCUPANTS, WHEN YOU LOOK AT ANY UNIT YOU WILL SEE THE |
| | SAME ISSUE,: |
| | EXAMPLE 1: UNIT 111 IS 793 SQ. FT./ 200= 3.965IN EVERY |
| | CASE THE DESIGNER HAS DROPPED THE FRACTION OF AN |
| | OCCUPANT, YOU ROUND UP NOT DOWN TO THE NEXT WHOLE |
| | NUMBER. FBC-B 1004.1. ALSO SEE BOAF INFORMAL |
| | INTERPRETATION 5479. |
| | |
| | 4B) UNITS 103 & 116 THE WINDOWS & DOORS IN THE FRONT OF |
| | THE UNIT WILL NEED TO BE 3/4 HR FIRE RATED EVEN THOUGH |
| | THERE IS 2 MEANSA OF EGRESS, PLEASE SEE THE UNITS ON |
| | THE 2ND & 3RD FLOOR WITH DEAD END CONDITIONS. |
| | 2010 FBC-B 1019.2 WALL SEPARATION. EXTERIOR EGRESS |
| | BALCONIES SHALL BE SEPARATED FROM THE INTERIOR OF THE |
| | BUILDING BY WALLS AND OPENING PROTECTIVES AS REQUIRED |
| | FOR CORRIDORS. EXCEPTION: SEPARATION IS NOT REQUIRED |
| | WHERE THE EXTERIOR EGRESS BALCONY IS SERVED BY AT LEAST |
| | TWO STAIRS AND A DEAD-END TRAVEL CONDITION DOES NOT |
| | REQUIRE TRAVEL PAST AN UNPROTECTED OPENING TO REACH A |
| | STAIR. 026.6 EXTERIOR RAMPS AND STAIRWAY PROTECTION. |
| | EXTERIOR EXIT RAMPS AND STAIRWAYS SHALL BE SEPARATED |
| | FROM THE INTERIOR OF THE BUILDING AS REQUIRED IN |
| | SECTION 1022.1 ALSO SEE 2007 FBC-B CODE COMMENTARY |
| | FIGURE 1023.6(1). |
| | |
| | 5) PAGE 044 2ND FLOOR LIFE SAFETY: |
| | 5A) UPDATE OCCUPANT LOADS TO REFLECT PARTIAL OCCUPANTS |
| | ROUNDED UP TO WHOLE PEOPLE, SEE COMMENT 4A EXAMPLE 1, |
| | FBC-B 1004.1 BOAF INFORMAL INTERPRETATION 5479. |
| | |
| | 5B) UNITS 203 & 216, DEAD END CORRIDORS THE WINDOWS IN |
| | THE FRONT OF THE UNIT WILL NEED TO BE 3/4 HR FIRE |
| | RATED. |
| | 2010 FBC-B 1019.2 WALL SEPARATION. EXTERIOR EGRESS |
| | BALCONIES SHALL BE SEPARATED FROM THE INTERIOR OF THE |
| | BUILDING BY WALLS AND OPENING PROTECTIVES AS REQUIRED |
| | FOR CORRIDORS. EXCEPTION: SEPARATION IS NOT REQUIRED |
| | WHERE THE EXTERIOR EGRESS BALCONY IS SERVED BY AT LEAST |
| | TWO STAIRS AND A DEAD-END TRAVEL CONDITION DOES NOT |
| | REQUIRE TRAVEL PAST AN UNPROTECTED OPENING TO REACH A |
| | STAIR. 026.6 EXTERIOR RAMPS AND STAIRWAY PROTECTION. |
| | EXTERIOR EXIT RAMPS AND STAIRWAYS SHALL BE SEPARATED |
| | FROM THE INTERIOR OF THE BUILDING AS REQUIRED IN |
| | SECTION 1022.1 ALSO SEE 2007 FBC-B CODE COMMENTARY |
| | FIGURE 1023.6(1). |
| | |
| | 6) PAGE 045 3RD FLOOR LIFE SAFETY: |
| | 5A) UPDATE OCCUPANT LOADS TO REFLECT PARTIAL OCCUPANTS |
| | ROUNDED UP TO WHOLE PEOPLE, SEE COMMENT 4A EXAMPLE 1, |
| | FBC-B 1004.1 BOAF INFORMAL INTERPRETATION 5479. |
| | |
| | 6B) UNIT 216, DEAD END CORRIDORS THE WINDOWS IN THE |
| | FRONT OF THE UNIT WILL NEED TO BE 3/4 HR FIRE RATED. |
| | 2010 FBC-B 1019.2 WALL SEPARATION. EXTERIOR EGRESS |
| | BALCONIES SHALL BE SEPARATED FROM THE INTERIOR OF THE |
| | BUILDING BY WALLS AND OPENING PROTECTIVES AS REQUIRED |
| | FOR CORRIDORS. EXCEPTION: SEPARATION IS NOT REQUIRED |
| | WHERE THE EXTERIOR EGRESS BALCONY IS SERVED BY AT LEAST |
| | TWO STAIRS AND A DEAD-END TRAVEL CONDITION DOES NOT |
| | REQUIRE TRAVEL PAST AN UNPROTECTED OPENING TO REACH A |
| | STAIR. 026.6 EXTERIOR RAMPS AND STAIRWAY PROTECTION. |
| | EXTERIOR EXIT RAMPS AND STAIRWAYS SHALL BE SEPARATED |
| | FROM THE INTERIOR OF THE BUILDING AS REQUIRED IN |
| | SECTION 1022.1 ALSO SEE 2007 FBC-B CODE COMMENTARY |
| | FIGURE 1023.6(1). |
| | |
| | 7) PAGE 49 SHEET 1A-0.40 ROOF ACCESS & ROOF PLAN: |
| | 7A) ROOF PLAN AND ROOF ACCESS SHOWS THE ELEVATOR |
| | CONTROL CLOSET WITHIN THE VERTICAL EXIT.2010 FBC-B AN |
| | EXIT ENCLOSURE SHALL NOT BE USED FOR ANY PURPOSE OTHER |
| | THAN MEANS OF EGRESS. |
| | 1022.4 PENETRATIONS. PENETRATIONS INTO AND OPENINGS |
| | THROUGH AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR |
| | REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY |
| | FOR INDEPENDENT VENTILATION OR PRESSURIZATION, |
| | SPRINKLER PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR |
| | FIRE DEPARTMENT COMMUNICATION SYSTEMS AND ELECTRICAL |
| | RACEWAY SERVING THE EXIT ENCLOSURE AND TERMINATING AT A |
| | STEEL BOX NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). |
| | SUCH PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH |
| | SECTION 713. THERE SHALL BE NO PENETRATIONS OR |
| | COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT, |
| | BETWEEN ADJACENT EXIT ENCLOSURES. |
| | 1022.3 OPENINGS AND PENETRATIONS.EXIT ENCLOSURE OPENING |
| | PROTECTIVES SHALL BE IN ACCORDANCE WITH THE |
| | REQUIREMENTS OF SECTION 715. OPENINGS IN EXIT |
| | ENCLOSURES OTHER THAN UNPROTECTED EXTERIOR OPENINGS |
| | SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT ACCESS TO |
| | THE ENCLOSURE FROM NORMALLY OCCUPIED SPACES AND FOR |
| | EGRESS FROM THE ENCLOSURE. |
| | |
| | 7B) THE ELEVATOR MACHINE ROOM DOES NOT SHOW ANY FIRE |
| | RATING ON EITHER THE WALLS OR OPENING PROTECTION. |
| | PLEASE SHOW COMPLIANCE WITH FBC-B 3006.4. |
| | |
| | 7C) THIS SHEET INDICATES THE FINISH FLOOR HEIGHT ABOVE |
| | GRAGE IS 29'-6" THE MEAN ROOF HEIGHT OF THE TOWER |
| | ENCLOSE IS GREATER THAN 33 FT. THE SUBMITTED ROOFING |
| | APPROVAL GAF TIMBERLINE ULTRA HD SHINGLES NOA |
| | 13-1104.12 LIMITATION # 2 LIMITS THE INSTALATION OF |
| | THIS PRODUCT TO 33 FT. MEAN ROOF HEIGHT.THE TOP OF THE |
| | ELEVATOR SHAFT IS AT 38'-0". |
| | |
| | 7D) PLEASE PROVIDE HOW THE A/C CONDENSATE ROOF TOP |
| | UNITS ARE GOING TO BE SECURED TO THE ROOF RACKS AND HOW |
| | THE ROOF RACKS ARE GOING TO BE SECURED TO THE CONCRETE |
| | ROOF DECK. PLEASE ALSO BE AWARE OF FBC-B TABLE 1509.7. |
| | |
| | 7E) HOW WILL THE 3RD FLOOR UNITS BENEATH THE FLAT |
| | ROOFED AREA ACHIEVE THE R-19 VALUE REQUIRED BY THE |
| | ENERGY CODE AND SUMMARY REPORT SUBMITTED. |
| | |
| | 8) THE PLANS DO NOT PROVIDE HOW COMPLIANCE WITH |
| | AIR-BORNE SOUND, SHEET 1A-7.02 DETAIL #4 SHOWS A PARTY |
| | WALL TYPE CONFIGURATION BUT NOT SHOWING COMPLIANCE WITH |
| | 2010 FBC-B 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| | ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| | CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| | EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| | OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| | THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| | ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| | FITTING TO THE FRAME AND SILL. |
| | |
| | 9) THE OTHER ISSUE THE PLANS DO NOT SHOW COMPLIANCE |
| | WITH IS 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 10) PAGE 085 1A-7.01 WINDOW BUCK DETAIL # 4 IS ACTUALLY |
| | DRAWN WRONG, THE CODE SECTION DIRECTLY ABOVE IR STATES |
| | UNLESS OTHERWISE TWESTED BUCKS SHALL EXTEND BEYOND THE |
| | INTERIOR SURFACE OF THE WINDOE OR DOOR FRAME. FBC-B |
| | 1715.5.4.2. |
| | |
| | 11) PAGE 87 1A-7.03 DETAIL 3 INDICATES THE HAND RAIL @ |
| | 34 IN. A.F.F. PLEASE REVIEW FBC-B 1012.2 THE HEIGHT IS |
| | TO BE MEASURED FROM THE TREAD NOSING. |
| | |
| | 12) THE PRESSURES FOR THE ROOF FLAT SECTION ARE GOOD, |
| | NO ROOF ZONE 3 THE PAARAPET IS AT LEAST 3'-0" HIGH |
| | ELIMINATING ZONE 3. WINDOW AND DOOR PRESSURES ARE GOOD |
| | FOR A MEAN ROOF HEIGHT OF 32.5 FT. THE ISSUE WILL BE |
| | THE ROOF LEVEL OF THE PENTHOUSE SINCE THE LOCATION IS |
| | ABOVE 33 FT, NO SHINGLES MAY BE PUT ON A ROOF WITH A |
| | MEAN ROOF HEIGTH OF 33 FT, SEE NOA LIMITATION. IF THE |
| | WHOLE ROOFING STYLE IS TO CHANGE FROM SHINGLES THEN |
| | PRESSURES FOR A 4/12 ROOF WILL BE NEEDED FOR BOTH A |
| | MEAN ROOF HEIGHT OF 32.5 FT AND PENTHOUSE AT APPROX |
| | 41.0. FT. |
| | |
| | 13) THE PRODUCT APPROVALS DO NOT HAVE TO BE SUBMITTED |
| | AT THIS TIME. AS LONG AS THE WIND DESIGN AND PRESSURES |
| | ARE CORRECT, THE PRODUCT APPROVALS CAN BE SUBMITTED |
| | AFTER PERMIT ISSUANCE AS A DEFERRED SUBMITTAL, NO COST |
| | TO CONTRACTOR. THERE IS NO CONTRACTOR SIGNED ON, THEY |
| | THEN BID THE JOBS OUT, THE PRODUCT APPROVALS SUBMITTED |
| | TODAY MAY NOT BE WHAT IS ACTUAL SUBMITTED TO BE BUILT. |
| | IF THE DESIGNER OF RECORD WOULD PREFER TO HAVE THE |
| | PRODUCT APPROVALS DEFERRRED IN THE RESPONCE JUST NOTE |
| | SO. |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.3.4.2 DEFERRED |
| | SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| | BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL |
| | ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW |
| | THEM AND FORWARD THEM TO THE |
| | BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND |
| | FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF THE |
| | BUILDING. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE |
| | INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | 13A) NOA 12-0320.07 SUNSHINE 2000 SERIES SINGLE HUNG, |
| | LMI PLEASE CIRCLE THE UNITS HEIGHT, WIDTH, PRESSURES & |
| | ANCHORAGE. |
| | |
| | 13B) NOA 13-0122.05 SUNSHINE 8000 SERIES STOREFRONT, |
| | LMI PLEASE CIRCLE THE UNITS HEIGHT, WIDTH, PRESSURES & |
| | ANCHORAGE. |
| | |
| | 13C) NOA 11-1216.02 SUNSHINE MULLION CIRCLE WIDTH, |
| | SPAN, MULLION SIZE PRESSURES AND TYPE OF ANCHORS. |
| | |
| | 13D) NOA 14-0109.06 SUNSHINE ALUMINUM, OUTSWING FRENCH |
| | DOORS NOTE FLUSHBOLTS WILL NEED TO WORK FROM A WHEEL |
| | CHAIR POSITION, PLEASE CIRCLE THE UNITS HEIGHT, WIDTH, |
| | PRESSURES & ANCHORAGE. |
| | |
| | 13E) FL. 14237-R1 FLEMING BARON CIRCLE IF SINGLE OR |
| | PAIR, INSWEING OR OUT, TYPE OF LATCH ANCHORAGE AND |
| | ASSOCIATED PRESSURES. |
| | |
| | 13F) JOHN MANSVILLE TPO SINGLE PLY ROOFING OVER |
| | LIGHTWEIGHT CONCRETE DECK. NOA 14-0618.05 CIRCLE WHICH |
| | SUB-SYSTEM TO BE INSTALLED AND ASSOCIATED PRESSURES. |
| | |
| | 13G) NOA 13-1104.12 GAF TIMBERLINE ULTRA HD |
| | SHINGLESNOTE THIS PRODUCT UNDER LIMITATIONS IS NOT TO |
| | BE INSTALLED ABOVE 33 FT. THE PENTHOUSE ROOF IS WELL |
| | ABOVE THE 33 FT MEAN ROOF HEIGHT. |
| | |
| | 13H) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 14A) THE ENERGY CALCULATIONS INDICATE A VENTED ATTIC |
| | AND R-19 INSULATION, LOCATED WHERE? |
| | |
| | 14B) ROOF VENTILATION PAGE 049, 1A-0.40 THE PLANS |
| | INDICATE THE USE OF SOFFIT VENTILATION BUT DO NOT |
| | INDICATE COMPLIANCE WITH FBC-B 1203.2 50 PERCENT OF THE |
| | REQUIRED VENTILATING AREA PROVIDED BY VENTILATORS |
| | LOCATED IN THE UPPER PORTION OF THE SPACE TO BE |
| | VENTILATED AT LEAST 3 FEET (914 MM) ABOVE EAVE OR |
| | CORNICE VENTS WITH THE BALANCE OF THE REQUIRED |
| | VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. |
| | |
| | 15) THE ENERGY CALCULATIONS WILL NEED TO REFLECT THE |
| | VALUES FOR A1 END UNIT, B UNIT INTERIOR AS WELL AS A |
| | END UNIT, AND A A2 INTERIOR UNIT, ALL ON GRADE, THEN |
| | FOR 2ND FLOOR SUROUNDED ABOVE AND BELOW WITH A/C AND |
| | THE 3RD FLOOR UNITS WITH ROOF INSULATION OVERHEAD. |
| | |
| | 16) PLEASE PROVIDE THE WINDOW AND DOOR SHGC OF 0.5 |
| | FBC-ENERGY 402.3. |
| | |
| | 17) LIFE SAFETY SHEETS TO SHOW AREA OF RESCUE |
| | ASSISTANCE 2010 FBC-ACCESSIBILITY CODE 207.1. SEE |
| | SECTION 1007 OF THE 2003 IBC 107.6 AREA OF REFUGE. |
| | |
| | 18) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 19) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |