2015-04-28 15:18:09808 GRANT STREET - BUILDING #1: 49 UNIT APARTMENT
 PERMIT #14120680
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT - SHEET 1A-1.04 & 1A-9.01: THE CENTER
 STAIR APPEARS TO BE COMPLETELY ENCLOSED (WALLS AND
 ROOF) AND COULD RESULT IN AN ACCUMULATION OF SMOKE IN A
 FIRE EVENT. THE STAIR NEEDS TO BE OPEN OR WOULD NEED TO
 BE PROTECTED AS AN ENCLOSED STAIR WITH FIRE RATED
 CONSTRUCTION, PROTECTED OPENINGS/PENETRATIONS AND NOT
 BE OPEN TO OTHER COMBUSTIBLES SUCH AS THE ELEVATOR
 CONTROL CLOSET.
  
 FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT ISSUED
 SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED WITH THE
 WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, ALTER OR
 SET ASIDE ANY OF THE PROVISIONS OF THE TECHNICAL CODES,
 NOR SHALL ISSUANCE OF A PERMIT PREVENT THE BUILDING
 OFFICIAL FROM THEREAFTER REQUIRING A CORRECTION OF
 ERRORS IN PLANS, CONSTRUCTION OR VIOLATIONS OF THIS
 CODE. REVIEW AND APPROVAL BY THE AHJ SHALL NOT RELIEVE
 THE OWNER, CONTRACTOR, ETC. OF THE RESPONSIBILITY OF
 COMPLIANCE WITH CODE (NFPA 1, SECTION 1.14.4).
  