2015-03-11 11:31:181. ARE SEPARATE FIRE AND POTABLE LINES PROPOSED? PLAN
 SHEET PWS-1 SHOWS MULTIPLE CROSS-CONNECTIONS BETWEEN
 THE 4-INCH AND 8-INCH DIP LINES. THE 4-INCH LINE IS
 CALLED OUT AS HAVING A FIRE FLOW METER ASSEMBLY WHILE
 THE 8-INCH LINE IS CALLED OUT WITH A MASTER METER
 VAULT. TYPICALLY, FIRE LINES ARE LARGER THAN POTABLE
 LINES TO PROVIDE THE REQUIRED FLOW AT THE HYDRANTS.
  
 2. PLEASE CHANGE THE NOTE FOR THE EXISTING SANITARY
 MANHOLE CONNECTION (NEAR THE SOUTHEASTERN PORTION OF
 THE SITE). BASED ON THE AGE OF THE DEVELOPMENT, THE
 MANHOLE WILL NEED TO BE REHABILITATED (RATHER THAN
 MAY).
  
 3. PLEASE SHOW THE PROPOSED EASEMENTS FOR THE WATER
 MAIN AND METERS.
  
 4. PLEASE SPECIFY THE PROPOSED METER SIZES. FEES FOR
 THE VARIOUS METER SIZES CAN BE VIEWED AT
 HTTP://WPB.ORG/UTILITIES/RATES/ UNDER "INSTALLATION"
  
 5. PLEASE VERIFY THE ELEVATIONS SHOWN FOR CONFLICT #2.
  
 6. PLEASE PROVIDE A COPY OF THE APPROVED SITE PLAN.
  