| Plan Review Notes For Permit 14120680 |
| Permit Number |
14120680 |
|
| Review Stop |
ENG |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-03-11 11:31:18 | 1. ARE SEPARATE FIRE AND POTABLE LINES PROPOSED? PLAN | | | SHEET PWS-1 SHOWS MULTIPLE CROSS-CONNECTIONS BETWEEN | | | THE 4-INCH AND 8-INCH DIP LINES. THE 4-INCH LINE IS | | | CALLED OUT AS HAVING A FIRE FLOW METER ASSEMBLY WHILE | | | THE 8-INCH LINE IS CALLED OUT WITH A MASTER METER | | | VAULT. TYPICALLY, FIRE LINES ARE LARGER THAN POTABLE | | | LINES TO PROVIDE THE REQUIRED FLOW AT THE HYDRANTS. | | | | | | 2. PLEASE CHANGE THE NOTE FOR THE EXISTING SANITARY | | | MANHOLE CONNECTION (NEAR THE SOUTHEASTERN PORTION OF | | | THE SITE). BASED ON THE AGE OF THE DEVELOPMENT, THE | | | MANHOLE WILL NEED TO BE REHABILITATED (RATHER THAN | | | MAY). | | | | | | 3. PLEASE SHOW THE PROPOSED EASEMENTS FOR THE WATER | | | MAIN AND METERS. | | | | | | 4. PLEASE SPECIFY THE PROPOSED METER SIZES. FEES FOR | | | THE VARIOUS METER SIZES CAN BE VIEWED AT | | | HTTP://WPB.ORG/UTILITIES/RATES/ UNDER "INSTALLATION" | | | | | | 5. PLEASE VERIFY THE ELEVATIONS SHOWN FOR CONFLICT #2. | | | | | | 6. PLEASE PROVIDE A COPY OF THE APPROVED SITE PLAN. | | | | | | KELLY CRANFORD, PE | | | CITY LAND DEVELOPMENT ENGINEER | | | (561)494-1098 | | | [email protected] |
|