| 2014-12-29 08:42:32 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. PROVIDE MULLION AND DOOR PRODUCT APPROVALS, FBC 107, |
| | FBC 2010 RESIDENTIAL 301. |
| | |
| | 2. REVISE FLOOR PLAN TO INCLUDE ROOM DESIGNATIONS. |
| | |
| | 3. FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN |
| | HEIGHT, NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND |
| | OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1. THE |
| | CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%. |
| | |
| | TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION |
| | NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN |
| | HEIGHT: |
| | |
| | STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS |
| | - AWNING, CASEMENT, SINGLE HUNG? |
| | |
| | STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE. |
| | CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE |
| | WINDOW IS FULLY OPEN. |
| | |
| | 4. FOR THE IMPACT PROTECTION, COMPLETE THE SAMPLE |
| | INSTALLATION SCHEDULE OR PROVIDE ALL INFORMATION TO |
| | SHOW CODE COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC |
| | R301, FBC1609. TWO SETS REQUIRED. THIS FORM IS |
| | AVAILABLE IN THE LOBBY OR ON THE INTERNET AT |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/SCHEDULE_FOR_INSTALLATION.PDF |
| | |
| | 5. VALUE IS TOO LOW AND HAS BEEN ADJUSTED, FBC 109. IF |
| | CONTRACTOR OBJECTS TO NEW VALUATION, PROVIDE EVIDENCE |
| | (MATERIAL RECEIPTS, ETC) TO SUPPORT THE VALUE OF $2400 |
| | STATED FOR THE 11 WINDOWS, 2 DOORS, AND SHUTTERS. |
| | |
| | 6. PLAN PROVIDED INDICATES THAT THE STRUCTURE IS MULTI |
| | FAMILY. REVISE FLOOR PLAN TO SHOW TENANT SEPARATION, |
| | FBC 107. |
| | |
| | |
| | |
| | |