Plan Review Notes
Plan Review Notes For Permit 14120672
Permit Number 14120672
Review Stop B
Sequence Number 1
Notes
Date Text
2014-12-29 08:42:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE MULLION AND DOOR PRODUCT APPROVALS, FBC 107,
 FBC 2010 RESIDENTIAL 301.
  
 2. REVISE FLOOR PLAN TO INCLUDE ROOM DESIGNATIONS.
  
 3. FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT, NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND
 OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1. THE
 CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%.
  
 TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION
 NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT:
  
 STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS
 - AWNING, CASEMENT, SINGLE HUNG?
  
 STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE.
 CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE
 WINDOW IS FULLY OPEN.
  
 4. FOR THE IMPACT PROTECTION, COMPLETE THE SAMPLE
 INSTALLATION SCHEDULE OR PROVIDE ALL INFORMATION TO
 SHOW CODE COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC
 R301, FBC1609. TWO SETS REQUIRED. THIS FORM IS
 AVAILABLE IN THE LOBBY OR ON THE INTERNET AT
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
 5. VALUE IS TOO LOW AND HAS BEEN ADJUSTED, FBC 109. IF
 CONTRACTOR OBJECTS TO NEW VALUATION, PROVIDE EVIDENCE
 (MATERIAL RECEIPTS, ETC) TO SUPPORT THE VALUE OF $2400
 STATED FOR THE 11 WINDOWS, 2 DOORS, AND SHUTTERS.
  
 6. PLAN PROVIDED INDICATES THAT THE STRUCTURE IS MULTI
 FAMILY. REVISE FLOOR PLAN TO SHOW TENANT SEPARATION,
 FBC 107.
  
  
  
  