| Plan Review Notes For Permit 14120646 |
| Permit Number |
14120646 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-12-24 05:42:11 | 1) GALVANIZED PIPNG IS NOT PERMITTED BELOW GRADE PER | | | THE 2010 FL. GAS CODE SECS.403.8, 404.9, 404.9.2. | | | 2) ON THE SURVEY, SHOW THE DISTANCE OF THE GENERATOR | | | FROM THE EXTERIOR WALL OF THE STRUCTURE. COMPLY WITH | | | NFPA 37 SEC. 4.1.4. | | | 3) THE GENERATOR EXHAUST SHALL BE A MIN. 10 FT. FROM | | | ANY BUILDING OPENINGS. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|