| 2014-12-31 14:15:34 | 1) SHT. A2.0 - SUBMIT ROOF DRAINAGE CALCULATIONS. ROOF |
| | GUTTERS SHALL BE SIZED PER TABLE 1106.6 OF THE 2010 |
| | FL.PLUMBING CODE. INDICATE THE SLOPE OF THE GUTTERS ON |
| | THE PLAN. THE SIZE OF THE VERTICAL CONDUCTORS SHALL |
| | COMPLY WITH TABLE 1106.2(1) OR 1106.2(2). |
| | 2) SHT.A7.1ELEV.#3 THE BOTTOM OF THE REFLECTING SURFACE |
| | OF THE MIRROR SHALL BE A MAX. OF 40 INCHES ABOVE THE |
| | FINISH FLOOR PER THE2010 FL. ACCESSIBILITY CODE |
| | SEC.603.3. |
| | 3) SHT.A7.1 - ELEV.#4 - THE GRAB BARS SHALL BE MEASURED |
| | FROM THE FINISH FLOOR TO THE TOP OF THE GRIPPING |
| | SURFACE, NOT TO THE CENTERLINE AS SHOWN PER THE FAC |
| | SEC.609.4. |
| | 4) SHT.A7.1 - ELEV.#4 - THE SEAT HEIGHT SHALL BE 17-19 |
| | INCHES MAX. ABOVE THE FINISH FLOOR MEASURED TO THE TOP |
| | OF THE SEAT.THE ELEVATION SHOWS THE MEASUREMENT TO THE |
| | TOP OF THE WATER CLOSET BOWL.FAC SEC.604.4. |
| | 5) SHT.A7.1 - ELEV.# 4 - THE TOILET PAPER DISPENSER |
| | SHALL BE LOCATED 7-9 INCHES IN FRONT OF THE WATER |
| | CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER. |
| | 6) SHT. A7.2 - DETAIL #1 - THE HEIGHT OF THE ROBE HOOK |
| | SHALL COMPLY WITH FAC SEC. 308. THE MAXIMUM HEIGHT |
| | SHALL BE 48 INCHES ABOVE THE FINISH FLOOR. |
| | 7) SHT. A7.2 - ELEV.#7 - THE SEAT HEIGHT SHALL BE 17-19 |
| | INCHES MAX. ABOVE THE FINISH FLOOR MEASURED TO THE TOP |
| | OF THE SEAT.THE ELEVATION SHOWS THE MEASUREMENT TO THE |
| | TOP OF THE WATER CLOSET BOWL.FAC SEC.604.4. |
| | 8) SHT.A7.2 - ELEV.#6 & #7 - SHOW THE DISTANCE OF THE |
| | SIDE GRAB BAR FROM THE REAR WALL AND THE REAR GRAB BAR |
| | FROM THE SIDE WALL. COMPLY WITH FAC SEC.604.5.1 & |
| | 604.5.2. |
| | 9) SHT.A7.2 - ELEV.#6 - SHOW THE HEIGHT OF THE LAVATORY |
| | ABOVE THE FINISH FLOOR. COMPLY WITH FAC SECS.305 & 606. |
| | 10) SHT. A7.2 - ELEV.#1 - SHOW THE FIXTURE CLEARANCE OF |
| | THE WATER CLOSET FROM THE SIDE WALL. COMPLY W/ FAC SEC. |
| | 604.2. |
| | 11) SHT. A7.2 - ELEV.#5 - SHOW THE HEIGHT OF THE SHOWER |
| | CONTROLS. COMPLY WITH FAC SEC.608.5.2. |
| | 12) SHT.A8.0 - THE THRESHOLD AT THE SHOWER SHALL BE A |
| | MAX. OF 1/2/INCH PER THE FAC SEC.608.7. |
| | 13) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE GAS |
| | APPLIANCES PER THE 2010 FUEL GAS CODE SEC. 304. |
| | 14) SUBMIT VENTING DETAILS FOR THE WATER HEATERS. |
| | COMPLY WITH FGC SECS.502 & 503. THE PLANS REFER TO THE |
| | MECHANICAL DRAWINGS FOR VENTING DETAILS BUT THERE ARE |
| | NO DETAILS ON THE MECHANICAL PLANS. |
| | 15) SUBMIT MANUFACTURER'S SPECS FOR ALL GAS APPLIANCES. |
| | APPLIANCES SHALL BE LISTED AND LABELED PER THE FGC SEC. |
| | 301.3. |
| | 16) SUBMIT DETAILS FOR THE LINT INTERCEPTORS. COMPLY |
| | WITH FL.PLUMBING CODE SEC.1003.6. |
| | 17) SHT. P2.1 - THE DISHWASHER AT THE FOOD PREPARATION |
| | AREA # 158 SHALL DISCHARGE TO THE GREASY WASTE SYSTEM |
| | PER FPC SEC.1003.3.1. |
| | 18) SUBMIT A CONDENSATE RISER FOR REVIEW. WPB AMEND. TO |
| | 2010 FPC SEC.107.2.1. |
| | 19) SUBMIT GREASE TRAP SIZING CALCULATIONS. COMPLY WITH |
| | FPC SECS.1003.2, 1003.3.4. |
| | 20) SUBMIT DETAILS FOR THE GREASE TRAP. COMPLY WITH FPC |
| | SEC.1003.5.2, 1003.5.3. |
| | 21) SHT. P2.1 REFERS TO CIVIL DRAWINGS FOR THE |
| | CONTINUATION OF THE GREASE AND SANITARY LINES. CIVIL |
| | DRAWINGS ARE NOT PART OF THIS SUBMITTAL. CLARIFY. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |