| Plan Review Notes For Permit 14120580 |
| Permit Number |
14120580 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-02-02 15:32:05 | PLAN DENIED | | | 1) PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR | | | CLOTH DRYERS | | | AND FIRE DAMPERS PER SECTION 304.1 GENERAL 2010 FBC (M) | | | 2) REFER TO SECTION 501.2 EXHAUST DISCHARGE AND 501.2.1 | | | LOCATION OF EXHAUST OUTLETS. 2010 FBC (M) | | | 3) PROVIDE GRILL SIZE ON ALL FRESH AIR GRILLS 107 FBC | | | 2010 | | | 4) PROVIDE ALL AIR CONDITIONING EQUIPMENT ON THE | | | EQUIPMENT | | | SCHEDULE IF NEW AND NOT EXISTING. | | | 5) SHOW LOCATION OF THE CONDENSERS FOR AIR HANDLERS 1 | | | THROUGH 4 | | | ON THE PLANS. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | | | | | | | |
|