| 2015-01-13 17:28:29 | BUILDING PLAN REVIEW |
| | PERMIT: 14120580 |
| | ADD: 901 45TH ST./ QUANTUM HOUSE |
| | CONT: HEDRICK BROTHERS |
| | TEL: ( |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JAN. 13/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE A SURVEY FOR THIS LOCATION. THE |
| | EXISTING STRUCTURE MAY OR MAY NOT BE LOCATED IN A AH |
| | FLOOD ZONE LOOKING BETWEEN THE FIMA FLOOD MAPS AND THE |
| | COUNTY GIS, THERE IS SOME DISCREPANCY BETWEEN THE TO, |
| | THE FEMA FLOOD MAP PANEL 120192- 0015-B DATED 3/01/79 |
| | IS THE CURRENT MAP. THE BASE FLOOD ELEVATION SHOWN ON |
| | THIS MAP IS 17'-0" NGVD. |
| | |
| | PLEASE REVIEW SECTION 1612.4 DESIGN AND CONSTRUCTION |
| | DOCUMENTS IF THE EXISTING BUILDING IS LOCATED WITHIN |
| | THE AH FLOOD ZONE. ASCE 24 FOR A STRUTURE CATEGORYII |
| | DFE + 1FT OR DFE, WHICHEVER IS HIGHER. |
| | |
| | IF THE EXISTING BUILDING IS LOCATED IN THE AH FLOOD |
| | ZONE, THEN SUBSTANIAL IMPROVEMENT ON THE EXISTING |
| | BUILDING THAT WILL BE ANOTHER FACTOR, SEE W.P.B. |
| | MUNI-CODE 94-611 DEFINITION FOR SUBSTANIAL IMPROVEMENT. |
| | |
| | 2) PAGE 44 SHEET S-3.1 THE FOUNDATION NOTE # 1.A |
| | INDICATES THERE IS A SOILS REPORT TO BE PREPARED BY |
| | ARDAMAN & ASSOCIATES. NO SOILS REPORT WAS INCLUDED IN |
| | THIS SUBMITTAL. FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE |
| | THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE |
| | SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR |
| | TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL. |
| | |
| | 3) PAGE 002 SHEET LIFE SAFETY 1: |
| | 3A) UNDER THE CLASSIFICATION OF WORK THE PLANS INDICATE |
| | A LEVEL II ALTERATION THE PERMIT APPLICATION SCOPE OF |
| | WORK UNDER THIS PERMIT LIST THE CONSTRUCTION OF A |
| | 20,000 SQ. FT. ADDITION, THERE APPEARS TO BE A |
| | DISCREPANCY IN THE SCOPE OF WORK TO TAKE PLACE UNDER |
| | THIS PERMIT? IS THE EXISTING BUILDING TO HAVE A LEVEL |
| | II ALTERATION? 107.2.1.3 DISCREPANCY, ADDITIONAL |
| | INFORMATION REQUIRED. FOR THIS REVIEW WE ARE GOING TO |
| | REVIEW TO A 20,000 SQ. FT. ADDITION AND A LEVEL II |
| | ALTERATION TO THE EXISTING STRUCTURE. |
| | |
| | 3B) OCCUPANT LOADS INTHE GROUP HEADINGS OF A2 & STORAGE |
| | OCCUPANCIES THE OCCUPANT LOAD WAS ROUNDED DOWN AND NOT |
| | TO THE NEXT FULL OCCUPANT, OCCUPANT LOADS ARE ALWAYS |
| | ROUNDED UP, NO PARTS OF OCCUPANT. FBC-B 1004.1. AND SEE |
| | BOAF INFORMAL INTERPRETATION # 5479. UPDATTE OCCUPANT |
| | LOADS. |
| | |
| | 3C) CONSTRUCTION TYPE INDICATES: III-B SPRINKLERED, |
| | PLEASE SPECIFY COMPLIANCE WITH FBC-B 903.3.1.1 NFPA 13 |
| | OR 903.3.1.2 NFPA 13R. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION,107.3.5 MINIMUM PLAN |
| | REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: 5. FIRE SUPPRESSION |
| | SYSTEMS SHALL INCLUDE: EARLY WARNING SMOKE EVACUATION |
| | SYSTEMS, SCHEMATIC FIRE SPRINKLERS. |
| | |
| | 4) THIS BUILDING QUALIFIES FOR THE RESIDENT INSPECTOR |
| | PROGRAM WITH AN AREA OF 20,000 SQ. FT. 2010 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION, 110.3.9 OTHER INSPECTIONS SERVICES. |
| | THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY |
| | OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109. HE/SHE |
| | MAY ACCEPT REPORTS OF INSPECTORS OF RECOGNIZED |
| | INSPECTION SERVICES, PROVIDED THAT AFTER INVESTIGATION |
| | HE/SHE IS SATISFIED AS TO THEIR QUALIFICATIONS AND |
| | RELIABILITY. A CERTIFICATE CALLED FOR BY ANY PROVISION |
| | OF THE TECHNICAL CODES SHALL NOT BE BASED ON SUCH |
| | REPORTS UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY |
| | A RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING |
| | OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION |
| | SERVICE IN THE FOLLOWING INSTANCES: (5.) FOR BUILDINGS |
| | WITH AREA GREATER THAN 20,000 SQUARE FOOT. RESIDENT |
| | INSPECTOR FORMS WILL BE E-MAILED OUT TO THE CONTRACTOR |
| | CONTACT. |
| | |
| | SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES |
| | WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE |
| | BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED |
| | ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER |
| | CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH |
| | INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS |
| | INCLUDING THE DAILY INSPECTIONS TO THE BUILDING |
| | OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF |
| | THE RESIDENT INSPECTOR. |
| | |
| | NOTE: WHEN THE PERMIT IS ISSUED, AND THE PROJECT DOX |
| | LIBRARIAN E-MAILS YOU THAT YOU CAN DOWNLOAD YOUR |
| | APPROVED PLANS FOR PRINTING, THE CITY WILL REQUIRE 2 |
| | COLOR SETS OF PLANS, ONE FOR THE RESIDENT INSECTOR, THE |
| | OTHER FOR THE CITY MEP INSPECTORS. |
| | |
| | NOTE: EVEN WITH AN ONSITE RESIDNET INSPECTOR, THE |
| | CONTRACTOR IS STILL REQUIRED TO CALL IN THE STRUCTURAL |
| | INSPECTIONS FOR AUDITING PURPOSES, PLUS NO ACTIVITY |
| | WILL EXPIRE THE PERMIT WITH NO ACTIVITY. |
| | |
| | 5) THE PERMIT APPLICATION INDICATES A TOTAL OF |
| | 2,800,000.00 FOR THE TOTAL PROJECT PLEASE BREAK OUT THE |
| | VARIOUS PERMIT VALUES FOR ; |
| | SIGNAGE, LANDSCAPING, SITE WORK, PAVING, IRRIGATION, |
| | FIRE SPRINKLER, FIRE ALARM LOW VOLTAGE, ALL PERMITS |
| | THAT WILL NOT BE INCLUDED UNDER THE PRIME PERMIT. |
| | THE MEP & ROOFING ARE A NO FEE SUB-PERMIT. THIS WAY WE |
| | CAN FIGURE THE ACTUAL PERMIT FEES FOR THE BUILDING |
| | PERMIT. W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF |
| | PERMIT FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| | MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS |
| | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| | 108.3* BUILDING PERMIT VALUATION. |
| | |
| | 6) PLEASE PROVIDE WHAT THE MEAN ROOF HEIGHT IS FOR THIS |
| | PROJECT, NEITHER THE A3.00 SERIES NOR SHEET S-5 PROVIDE |
| | WHAT THE MEAN ROOF HEIGHT. SHEET S-5 THE ROOF PRESSURES |
| | ARE LOW FOR A 4:12 PITCH ROOF IN A C EXPOSURE. WILL THE |
| | ROOF PRESSURES FOR OVER THE CLEAR STORY BE ON A |
| | SEPARATE PRESSURE CHART? AGAIN PROVIDE THE MEAN ROOF |
| | HEIGHT FOR THE CLEARSSTORY. FBC-B 1609.6.4.4.1/ TABLE |
| | 1609.6.2(2) |
| | |
| | 6A) WILL THE ROOF PRESSURES FOR OVER THE CLEAR STORY BE |
| | ON A SEPARATE PRESSURE CHART? AGAIN PROVIDE THE MEAN |
| | ROOF HEIGHT FOR THE CLEARSTORY. FBC-B 1609.6.4.4.1/ |
| | TABLE 1609.6.2(2) |
| | |
| | 6B) THE ROOF ZONES 2 & 3 BOTH INDICATE THE SAME |
| | PRESSURES AS IF THERE WAS A 3 FOOT PARAPET AROUND THE |
| | PERMITER ELIMENATING ROOF ZONE # 3 THE ROOF SCHEMATIC |
| | SHOWS A ROOF ZONE 3 AND A CORNER DISTANCE OF 6 FT. |
| | FBC-B 1609.6.4.4.1/ TABLE 1609.6.2(2) |
| | |
| | 6C) THE ROOF OVER HANG ZONES HAVE NOT BEEN SHOWN ON |
| | SHEET S-5 EITHER. FBC-B 1609.6.4.4.1/ TABLE |
| | 1609.6.2(2). |
| | |
| | 7) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | NOTE: IF EITHER THE DESIGNER OF RECORD OR THE |
| | CONTRACTOR WOULD PREFER TO SUBMIT THE PRODUCT APPROVALS |
| | AFTER THE PERMIT ISSUANCE AS A DEFERRED SUBMITTAL |
| | PLEASE IN YOUR RESPONSE LETTER NOTE AS SUCH. 107.3.4.2 |
| | DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, |
| | DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE |
| | DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL |
| | THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY |
| | THE BUILDING OFFICIAL. |
| | |
| | 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 9) PAGE 12 SHEET A1.4 PARTIAL NORTH, DOOR 153, 154 & |
| | 159 ARE WITHIN A 1 HOUR FIRE RATED CORRIDOOR TABLE |
| | 1018.1/ TABLE 715.4.ALSO SEE PAGE 31 SHEET A6.0 DOOR |
| | SCHEDULE NO FIRE RATING. |
| | |
| | 10) PAGE 08 SHEET A1.0 INDICATE THE 1 HOUR FIRE RATED |
| | CORRIDORS IN THE R1 OCCUPANCY, CORRIDORS 308 & 412. |
| | THIS PLAN DOES NOT SHOW HOW THE 1 HOUR FIRE RATED |
| | CORRIDORS SHALL BE CONTINUOUS TO AN EXIT. SEE FBC-B |
| | 1018.6 CORRIDOR CONTINUITY, THE EXCEPTION ALLOWS FOR |
| | FOYERS, LOBBIES OR RECEPTION ROOMS TO BE CONSTRUCTED AS |
| | CORRIDORS. THE PROBLEM IS IN THE CORIDOR 308 & 412 |
| | DUMPING INTO ANOTHER OCCUAPNCY (A2 OR B) THAT DOES NOT |
| | REQUIRE A RATED CORRIDOR FOR A SPRINKLERED BUILDING. |
| | |
| | 11) A SIMILAR SITUATION OCCURS ON THE SOUTH GUEST WING |
| | WHERE THE R1 OCCUPANCY RUNS INTO A BUSINESS OCCUPANCY |
| | AND INTO THE EXISTING KITCHEN WHICH IS HIGHLIGHTED AS |
| | WORK TO BE ACCCOMPLISHED UNDER THIS PERMIT. |
| | |
| | 12) PLEASE PROVIDE THE DISTANCE FROM THE DINING ROOM |
| | 157 WALL TO THE PROPERTY LINE, IT APPEARS TO BE RIGHT |
| | AT 20 FT. IF UNDER 20 FT. SEE FBC-B TABLE 705.8 |
| | PROVIDE CALCULATIONS FOR ALLOWABLE WALL AREA. |
| | UNPROTECTED, SPRINKLRED, 75 %. |
| | |
| | 13) THE 500 SERIES WALL SECTIONS SHOW THE USE OF |
| | ICYNENE SPRAY INSULATION, MINIMUM OF R-19. PLEASE |
| | PROVIDE COMPLIANCE WITH 2603.4.1.6 PROTECTION AGAINST |
| | IGNITION. THERMAL BARRIER REQUIREMENTS 2603.4. ALSO |
| | PROVIDE THE EVALUATION REPORT FOR THIS PRODUCT WITH |
| | INSTALATION INSTRUCTIONS, CIRCLE THE SUB-SYSTEM THAT |
| | WILL BE USED FOR THIS APPLICATIONAND THE MAXIMUM |
| | AMOUNTS THIS INSTALATION CAN BE APPLIED IN THICKNESS. |
| | |
| | 14) SHEET SP1.0: |
| | 14A) THE PORT COCHERE IS A COVERED DROP OFF AREA BUT |
| | THE PLANS ALSO SHOW THE LOADING ZONE INFRONT OF THE |
| | PORT COCHERE. THE PASSENGER LOADING ZONE NEEDS TO |
| | COMPLY WITH BOTH SECTIONS OF THE 2010 FL ACCESS. CODE |
| | 503.2 VEHICLE PULL-UP SPACE AND 503.3 AN ACCESS AISLE. |
| | THESE ELEMENTS SHOULD BE UNDER THE PORT COCHERE TO MEET |
| | EQUIVALENT FACILITATION 103. |
| | |
| | 14B) THE VERTICAL DISTANCE REQUIRED FOR THE PASSENGER |
| | LOADING ZONE IS 114 INCHES MINIMUM 2010 FL ACCESS. CODE |
| | 503.5. |
| | |
| | 14C) WILL THERE BE EITHER A BUS OR VAN SERVICE THAT |
| | WILL SHUTTLE FAMILIES FROM QUANTUM HOUSE TO THE MAIN |
| | HOSPITAL CAMPUS? 2010 FL ACCESS. CODE |
| | 209.2.2 BUS LOADING ZONES. IN BUS LOADING ZONES |
| | RESTRICTED TO USE BY DESIGNATED OR SPECIFIED PUBLIC |
| | TRANSPORTATION VEHICLES, EACH BUS BAY, BUS STOP, OR |
| | OTHER AREA DESIGNATED FOR LIFT OR RAMP DEPLOYMENT SHALL |
| | COMPLY WITH 810.2. BUS BOARDING AND ALIGHTING AREAS. |
| | |
| | 14D) THE SITE PLAN SHOWS (2) AREAS WHERE THE 4'-0" WIDE |
| | WALK PATH (THE NORTH & EAST) EXCEED THE 200 FT. WITHOUT |
| | A PASSING ZONE, SEE 2010 FL ACCESS. CODE 403.5.3. |
| | |
| | 14E) FUTURE GAZEBO NOT PART OF THIS PREMIT. |
| | |
| | 15) THE PORT COCHERE SHOWS INSULATION AT THE ROOF LEVEL |
| | BUT NOT UNDER THE CEILING OF THE PORT COCHERE, NOR AT |
| | THE BUILDING LINE AS SHOWN AT THE BACK OF THE BUILDING |
| | SEE DETAIL3 SHEET A-5.0. NOTE DETAIL 3 SHEET A-5.0 |
| | SHOWS THE USE OF ICYNENE SPRAY INSULATION IN THE |
| | VERTICAL WALL APPLICATION. PLEASE PROVIDE THE |
| | MANUFACTURERS SPECIFICATION FOR THIS PRODUCT AND |
| | LIMITATIONS OF USE IN THE VERTICAL PLANE. FBC-B |
| | 2603.1.AND SCOPE 2601. THESE PROVISIONS SHALL GOVERN |
| | THE MATERIAL, DESIGN AND APPLICATION OF THE FOAM |
| | PLASTIC INSULATION. |
| | |
| | 16A) SHEET A-7.0 LAUNDRY DETAILS DO NOT SHOW ANY |
| | VENDING MACHINES FOR SOAP POWDER IF OFFERED THE |
| | MACHINES NEED TO BE AT A ELEVATION IN COMPLIANCE WITH |
| | REACH RANCGES ACCESS. CODE 308 AND OPERABLE PARTS |
| | ACCESS. |
| | |
| | 16B) THE HEIGHT OF THE WASHER AND DRYER ARE TO MEET THE |
| | REQUIREMENTS OF ACCESS. CODE 611.4 AND OPERABLE PARTS, |
| | INCLUDING DOORS, LINT SCREENS, AND DETERGENT AND BLEACH |
| | COMPARTMENTS SHALL COMPLY WITH 309. |
| | |
| | 17) SHEET A7.3 FOOD PREPERATION DETAIL # 1 158 SHOWS A |
| | 48 INCH ISLAND COUNTER TOP SHOWS A DETAIL 5/A7.2 FOR |
| | THE ELEVATION AND HEIGHT OF THIS UNIT. THAT DETAIL IS |
| | OF A BATH AT GUEST ROOM. DISCREPANCY IN |
| | PLANS.107.2.1.3. |
| | |
| | 18) SHEET A7.2 PLEASE SHOW COMPLIANCE WITH FL ACCESS. |
| | CODE TRANSIENT LODGING GUEST ROOMS: |
| | 18A) 806.2.4 TOILET AND BATHING FACILITIES. |
| | |
| | 18B)806.3 GUEST ROOMS WITH COMMUNICATION FEATURES. |
| | |
| | 18C) GUEST ROOMS REQUIRED TO PROVIDE COMMUNICATION |
| | FEATURES SHALL COMPLY WITH 806.3. |
| | |
| | 18D) 806.3.1 ALARMS. |
| | |
| | 18E) 806.3.2 NOTIFICATION DEVICES. |
| | |
| | 18F) 224.2 GUEST ROOMS WITH MOBILITY FEATURES. IN |
| | TRANSIENT LODGING FACILITIES, GUEST ROOMS WITH MOBILITY |
| | FEATURES COMPLYING WITH 806.2 SHALL BE PROVIDED IN |
| | ACCORDANCE WITH TABLE 224.2. |
| | |
| | 19) SHEET ID-2 AND ID-3 SHOWS THE USE OF CARPET IN THE |
| | R-1 UNITS AND CORIDORS OF THE R-1 UNITS. PLEASE PROVIDE |
| | COMPLIANCE WITH 2010 FBC-B 804.4.1 MINIMUM CRITICAL |
| | REDIANT FLUX. SEE EXCEPTION FOR SPRINKLERED BUILDINGS. |
| | |
| | 20) PLEASE SHOW COMPLIANCE WITH 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| | ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| | CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| | EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| | OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| | THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| | ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| | FITTING TO THE FRAME AND SILL. |
| | |
| | 21) PLEASE SHOW COMPLIANCE WITH 1207.3 STRUCTURE-BORNE |
| | SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| | OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 22) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |