2015-01-15 09:29:15BUILDING PLAN REVIEW
 REVISION: 14120566
 PERMIT: 13070532
 ADD:6601 N. JOG RD.
 CONT: CDM
 TEL: (
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JAN. 15/ 2015
 ACTION: DENIED
  
 1) PLEASE SUBMIT ELEVATIONS OF THE BUILDING AND
 ASSOCIATED PRESSURES FOR THESE DOORS:
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 WIND REQUIREMENTS/ PRESSURES
 BUILDING ENVELOPE/ ELEVATIONS
  
 1A) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 1.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 2A) INGERSOLL RAND NOA 12-0305.14 W/ PANIC HARDWARE
 SHEET 4 OF 4 PLEASE CIRCLE WHICH DOOR APPLICATION TO BE
 INSTALLED WITH ASSOCIATED PRESSURES.
  
 2B) INGERSOLL RAND NOA 12-0335.16 SHEET 4 OF 6, WITH OR
 WITH OUT PANIC HARDWARE CIRCLE WHICH APPLICATION TO BE
 USED.
  
 2C) TIGER DOORS MISSING THE PRODUCT APPROVAL COVERSHEET
 AND INSTALLATION INSTRUCTIONS
  
 2D) TIGER DOORS FL 7026- R2 MISSING THE ACTUAL REPORT
 AND INSTALLATION INSTRUCTIONS, PLEASE IDENTIFY THE DOOR
 ASSEMBLY IF MORETHAN 1 IS WITHIN THE REPORT.
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  