| 2015-01-15 09:29:15 | BUILDING PLAN REVIEW |
| | REVISION: 14120566 |
| | PERMIT: 13070532 |
| | ADD:6601 N. JOG RD. |
| | CONT: CDM |
| | TEL: ( |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JAN. 15/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE SUBMIT ELEVATIONS OF THE BUILDING AND |
| | ASSOCIATED PRESSURES FOR THESE DOORS: |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS |
| | 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | WIND REQUIREMENTS/ PRESSURES |
| | BUILDING ENVELOPE/ ELEVATIONS |
| | |
| | 1A) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 1.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 2A) INGERSOLL RAND NOA 12-0305.14 W/ PANIC HARDWARE |
| | SHEET 4 OF 4 PLEASE CIRCLE WHICH DOOR APPLICATION TO BE |
| | INSTALLED WITH ASSOCIATED PRESSURES. |
| | |
| | 2B) INGERSOLL RAND NOA 12-0335.16 SHEET 4 OF 6, WITH OR |
| | WITH OUT PANIC HARDWARE CIRCLE WHICH APPLICATION TO BE |
| | USED. |
| | |
| | 2C) TIGER DOORS MISSING THE PRODUCT APPROVAL COVERSHEET |
| | AND INSTALLATION INSTRUCTIONS |
| | |
| | 2D) TIGER DOORS FL 7026- R2 MISSING THE ACTUAL REPORT |
| | AND INSTALLATION INSTRUCTIONS, PLEASE IDENTIFY THE DOOR |
| | ASSEMBLY IF MORETHAN 1 IS WITHIN THE REPORT. |
| | |
| | 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |