| 2015-01-26 16:40:54 | PERMIT #14120546 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PROVISO: |
| | PER NFPA 101, SECTION 36.2.5.11 EXIT ACCESS IN CLASS A |
| | AND CLASS B MERCANTILE OCCUPANCIES THAT ARE PROTECTED |
| | THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC |
| | SPRINKLER SYSTEM IN ACCORDANCE WITH 9.7.1.1(1), AND |
| | EXIT ACCESS IN ALL CLASS C MERCANTILE OCCUPANCIES, |
| | SHALL BE PERMITTED TO PASS THROUGH STOREROOMS, PROVIDED |
| | THAT ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1)NOT MORE THAN 50 PERCENT OF EXIT ACCESS SHALL BE |
| | PROVIDED THROUGH THE STOREROOM. |
| | (2)THE STOREROOM SHALL NOT BE SUBJECT TO LOCKING. |
| | (3)THE MAIN AISLE THROUGH THE STOREROOM SHALL BE NOT |
| | LESS THAN 44 IN. (1120 MM) WIDE. |
| | (4)THE PATH OF TRAVEL THROUGH THE STOREROOM SHALL BE |
| | DEFINED, DIRECT, AND CONTINUOUSLY MAINTAINED IN AN |
| | UNOBSTRUCTED CONDITION. |
| | |
| | ADDITIONAL EMERGENCY LIGHTING MAY BE NEEDED FOR |
| | DRESSING ROOMS AREA. TO BE DETERMINED IN THE FIELD. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED BY EMAIL ([email protected]) |
| | ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND |
| | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| | 500 NORTH DIXIE HIGHWAY. |
| | |
| | ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A |
| | LOCK/UNLOCK INDICATOR. |
| | |
| | EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH |
| | SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL |
| | OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN |
| | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE |
| | SPACED NOT MORE THAN 15 FEET ON CENTER. |
| | |
| | PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN |
| | STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE |
| | MAINTAINED AT ALL TIMES. |
| | |
| | AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY |
| | EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL |
| | EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED |
| | WITH RESPECT TO THEIR DUTIES UNDER THE PLAN. |
| | |
| | EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED |
| | IN THE USE OF PORTABLE FIRE EXTINGUISHERS. |
| | |
| | SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE |
| | FIRE ALARM AND SPRINKLER SYSTEM. |
| | |
| | WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT |
| | SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED |
| | AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE |
| | MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM |
| | SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD |
| | INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY |
| | BE NEEDED. |
| | |
| | |