| | PROJECT: BROOKS BROTHERS |
| | PERMIT#: 14120546 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET E001. |
| | ADD NOTE TO ELECTRICAL RISER DIAGRAM INDICATING THE |
| | REQUIREMENT FOR ARC FLASH PROTECTION WARNING LABELS. |
| | NEC 110.16, 110.22 |
| | VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A |
| | FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL |
| | CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 |
| | CLARIFY THE INSTALLATION OF A MCB IN PANEL RP2. THE |
| | RISER DIGRAM INDICATES PANEL RP2 IS MLO ONLY. THE PANEL |
| | SCHEDULE CALLS FOR A MCB REMOVE THE INCONSISTANCY. NEC |
| | 450.3(B) |
| | CLARIFY AND PROVIDE ADDITIONAL DETAIL FOR THE |
| | INSTALLATION OF THE GROUNDING OF THE RELOCATED 75KVA |
| | TRANSFORMER. |
| | |
| | 2) SHEET E101. PLEASE CLARIFY HOW THE SITE SIGNAGE IS |
| | PROPOSED TO BE CONTROLED AND REMOVE THE CONFLICTING |
| | NOTES. WPB AMENDMENTS TO FBC 107.3 |
| | A.) LIGHTING CONTROL NOTES. SITE SIGNAGE- TIMECLOCK: |
| | ADDITIONAL TIMECLOCK FOR SITE SIGNAGE. (NOT APPLICABLE |
| | TO THIS PROJECT.) |
| | B.) KEY NOTES: 10) NEW JUNCTION BOX FOR STORE FRONT |
| | SIGNAGE. COORDINATE REQUIREMENTS WITH PROJECT MANAGER. |
| | ROUTE ELECTRICAL CIRCUIT THROUGH TIMECLOCK. |
| | C.) SEE LIGHTING CONTROL SCHEMATIC THIS SHEET. THE |
| | SCHEMATIC DOES INDICATE PERIMETER DISPLAY LIGHTING AND |
| | SIGN ON CHANNEL 1 OF PROPOSED TIMECLOCK ON CIRCUIT RP |
| | 28. |
| | D.) HOWEVER UNDER CONTROL DESCRIPTION NOTES SAYS |
| | TIMECLOCK FOR SITE SIGNAGE (NOT USED.) |
| | |
| | 3) SHEET E102 |
| | VERIFY AND INDICATE THE EXISTING OUTLETS FOR THE |
| | EXISTING ELECTRIC DRINKING FOUNTAINS SHALL BE GFI |
| | PROTECTED. NEC 422.52 |
| | |
| | 4) SHEET E102A |
| | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR AUDIO/VIDEO. ACCESS/EGRESS CONTROL, |
| | SECURITY, CCTV, NETWORK, DATA, AND, COMMUNICATION |
| | SYSTEMS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |