2015-01-26 12:08:261/26/2015
 PROJECT: BROOKS BROTHERS
 PERMIT#: 14120546
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) SHEET E001.
 ADD NOTE TO ELECTRICAL RISER DIAGRAM INDICATING THE
 REQUIREMENT FOR ARC FLASH PROTECTION WARNING LABELS.
 NEC 110.16, 110.22
 VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A
 FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL
 CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
 CLARIFY THE INSTALLATION OF A MCB IN PANEL RP2. THE
 RISER DIGRAM INDICATES PANEL RP2 IS MLO ONLY. THE PANEL
 SCHEDULE CALLS FOR A MCB REMOVE THE INCONSISTANCY. NEC
 450.3(B)
 CLARIFY AND PROVIDE ADDITIONAL DETAIL FOR THE
 INSTALLATION OF THE GROUNDING OF THE RELOCATED 75KVA
 TRANSFORMER.
  
 2) SHEET E101. PLEASE CLARIFY HOW THE SITE SIGNAGE IS
 PROPOSED TO BE CONTROLED AND REMOVE THE CONFLICTING
 NOTES. WPB AMENDMENTS TO FBC 107.3
 A.) LIGHTING CONTROL NOTES. SITE SIGNAGE- TIMECLOCK:
 ADDITIONAL TIMECLOCK FOR SITE SIGNAGE. (NOT APPLICABLE
 TO THIS PROJECT.)
 B.) KEY NOTES: 10) NEW JUNCTION BOX FOR STORE FRONT
 SIGNAGE. COORDINATE REQUIREMENTS WITH PROJECT MANAGER.
 ROUTE ELECTRICAL CIRCUIT THROUGH TIMECLOCK.
 C.) SEE LIGHTING CONTROL SCHEMATIC THIS SHEET. THE
 SCHEMATIC DOES INDICATE PERIMETER DISPLAY LIGHTING AND
 SIGN ON CHANNEL 1 OF PROPOSED TIMECLOCK ON CIRCUIT RP
 28.
 D.) HOWEVER UNDER CONTROL DESCRIPTION NOTES SAYS
 TIMECLOCK FOR SITE SIGNAGE (NOT USED.)
  
 3) SHEET E102
 VERIFY AND INDICATE THE EXISTING OUTLETS FOR THE
 EXISTING ELECTRIC DRINKING FOUNTAINS SHALL BE GFI
 PROTECTED. NEC 422.52
  
 4) SHEET E102A
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR AUDIO/VIDEO. ACCESS/EGRESS CONTROL,
 SECURITY, CCTV, NETWORK, DATA, AND, COMMUNICATION
 SYSTEMS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  