2015-01-15 16:02:43BUILDING PLAN REVIEW
 PERMIT: 14120546
 ADD: 1781 PALM BEACH LAKES # W233
 CONT: TBD
 TEL: (561)373-3902
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JAN. 15/ 2015
 ACTION: DENIED
  
 1) THE COVER SHEET INDICATES A OCCUPANT LOAD OF 123
 WHICH REQUIRES 2 EXITS. THE 2ND EXIT IS THROUGH THE
 STOREAGE ROOM, PLEASE PROVIDE COMPLIANCE WITH :
  
 2010 FBC-B SECTION 1014.2 EGRESS THROUGH INTERVENING
 SPACES. EGRESS THROUGH INTERVENING SPACES SHALL COMPLY
 WITH THIS SECTION.
 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES.
 EXCEPTIONS:
  
 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
  
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
  
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
  
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
  
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED
 WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN
 THE REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL
 AREA TO THE EXIT WITHOUT OBSTRUCTIONS.
  
 2) SHEET A400 DETAIL 3 & 4 SHOW THE ACCESSIBLE BENCH,
 WHAT THE DETAIL IS MISSING IS COMPLIANCE WITH FL ACC.
 CODE 903.4 BACK SUPPORT.
 THE BENCH SHALL PROVIDE FOR BACK SUPPORT OR SHALL BE
 AFFIXED TO A WALL. BACK SUPPORT SHALL BE 42 INCHES
 (1065 MM) LONG MINIMUM AND SHALL EXTEND FROM A POINT 2
 INCHES (51 MM) MAXIMUM ABOVE THE SEAT SURFACE TO A
 POINT 18 INCHES (455 MM) MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES (64 MM)
 MAXIMUM FROM THE REAR EDGE OF THE SEAT MEASURED
 HORIZONTALLY.
  
 3) SHEET A104 THE FLOOR PLAN INDICATES A CASH WRAP BUT
 THERE ARE NO PLANS SHOWING COMPLIANCE WITH;
 2010 FL ACCESSIBILITY CODE 904.4 SALES AND SERVICE
 COUNTERS. SALES COUNTERS AND SERVICE COUNTERS SHALL
 COMPLY WITH 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION
 OF THE COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE
 SALES OR SERVICE COUNTER TOP.
  
 4) SHEET A106 INDICATES ROOF FRAMING FOR ADDITIONAL
 ROOF TOP AIR HANDLERS, SHEET MP 001 INDICATES THERE ARE
 (2) EXISTING UNITS, SHEET MP101 ONLY SHOWS (2) DOWN
 UNITS? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  