| Plan Review Notes For Permit 14120532 |
| Permit Number |
14120532 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-01-02 12:34:58 | 1. SHOW LOCATION OF PANELS A & B AND IDENTIFY ON PLANS. | | | BRANCH CIRCUITS IN AREA BEING SERVED ORIGINATE IN BOTH | | | PANELBOARDS. | | | 2. N.E.C. 700.12(F) SHOW LOCATION OF ALL EMERGENCY | | | LIGHTS NEEDED FOR 1 FT. CANDLE FOR EGRESS. | | | 3. N.E.C. 210.63. LOCATION OF RECEPTACLE OUTLET WITHIN | | | 25 FEET OF AIR CONDITIONING EQUIPMENT AND GFCI | | | PROTECTED PER N.E.C. 210.8(B). |
|