Plan Review Notes
Plan Review Notes For Permit 14120514
Permit Number 14120514
Review Stop B
Sequence Number 3
Notes
Date Text
2015-03-18 18:22:21BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- A) FLOOD VENTS: "AT LEAST TWO OPENINGS ON DIFFERENT
 SIDES OF EACH ENCLOSED AREA" ARE REQUIRED BY SEC.
 R322.2.2 OF 2010 FBC-RESIDENTIAL. REVISE PLANS AS
 REQUIRED.
 B) PROVIDE COMPLETE INFORMATION FOR THE DESIGN OF THE
 FLOOD VENTS. SEE FEMA TECHNICAL BULLETIN 1 FOR LOCATION
 AND DESIGN REQUIREMENTS OF FLOOD VENTS.
 C) PROVIDE ICC FLOOD VENTS EVALUATION REPORT (2
 COPIES).
  
 2- WINDOW #19 NEEDS TO COMPLY WITH LIFE SAFETY ISSUES
 OF SEC. R612.2 OF 2010 FBC-RESIDENTIAL. REVISE BUILDING
 SECTION A-A/A4 AND SECOND FLOOR ELECTRICAL PLAN.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) USP TRUSS CONNECTOR TC-4 (HGAM10). FL819 IS NOT FOR
 2010 CODE VERSION. PROVIDE 2010 CODE VERSION OR APPLY
 FOR LOCAL PRODUCT APPROVAL.
  
 B) PRECAST LINTELS. NOA 12-0209.13 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA.