Plan Review Notes
Plan Review Notes For Permit 14120514
Permit Number 14120514
Review Stop E
Sequence Number 2
Notes
Date Text
2015-03-05 11:23:001) ALL NEW 120-VOLT, SINGLE PHASE, 15 AND 20 AMP BRANCH
 CIRCUITS SUPPLYING OUTLETS INSTALLED IN THE DWELLING
 UNIT SHALL BE PROTECTED BY A LISTED ARC-FAULT CIRCUIT
 INTERRUPTER FOR THE PROTECTION OF THE BRANCH CIRCUIT.
 NEC 210.12
  
 2) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 3) VERIFY THE WATER HEATER HAS THE REQUIRED ELECTRIC
 DISCONNECT. NEC 422.31
  
 4) SUFFICIENT ACCESS AND WORKING SPACE SHALL BE
 PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT
 TO PERMIT READY AND SAFE OPERATION AND MAINTENANCE OF
 SUCH EQUIPMENT. 110.26
  