Plan Review Notes
Plan Review Notes For Permit 14120514
Permit Number 14120514
Review Stop B
Sequence Number 2
Notes
Date Text
2015-02-26 18:54:34 
 *********REVIEW IN PROGRESS....
  
 VERY IMPORTANT NEW COMMENT:
 REVISED SURVEY SHOWING THE PROPOSED DRAINAGE FLOW
 DIRECTIONAL ARROW ALSO SHOWS THE GARAGE WITH A FINISHED
 FLOOR ELEVATION OF 7.05". THIS PROPERTY IS LOCATED IN
 FLOOD ZONE A5 WITH A BASED FLOOD ELEVATION OF 7.0'. THE
 MIN. GARAGE FINISH FLOOR ELEVATION REQUIRED IS 7.6".
 OTHERWISE COMPLY WITH THE REQUIREMENTS OF SEC. R322 OF
 2010 FBC. REVISE ALL PLANS AS REQUIRED.
  
 FROM PREVIOUS COMMENTS:
 1- SHEET A-2: WINDOW #19 BY THE SITTING AREA NEEDS TO
 COMPLY WITH LIFE SAFETY ISSUES OF SEC. R612.2 OF 2010
 FBC-RESIDENTIAL. REVISE PLANS AS REQUIRED. NOT
 ADDRESSED CORRECTLY. LIFE-SAFETY ISSUE IS FALLING FROM
 WINDOW NOT SAFETY GLASS.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SHINGLES SELF ADHERING UNDERLAYMENT AS SPECIFIED ON
 PLANS. NOA 11-0815.05 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. NEED CURRENT NOA.
  
 B) ALL USP STRUCTURAL CONNECTORS SPECIFIED ON PLANS AND
 SECTION/DETAILS. PROVIDE PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR LIST THE
 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE SPECIFIED
 CONNECTOR.
 NOTE: THERE ARE TWO SITE SPECIFIC CONNECTORS SHOWN ON
 SHEET S-4. NEED TO PROVIDE COMPLETE ENGINEERING PACKAGE
 FOR SITE SPECIFIC CONNECTORS APPROVAL. AND, THE
 ENGINEER (JAMES F. COLLINS JR.) NEED TO USE CURRENT
 SEAL THAT READS "LICENSE" INSTEAD OF "CERTIFICATE" AS
 REQUIRED BY FLORIDA BOARD OF PROFESSIONAL ENGINEERS
 WHEN SUBMITTING ENGINEERING PACKAGE FOR SITE SPECIFIC
 APPROVAL.
  
 C) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 D) ROOF SHINGLES. NOA 13-0419.04 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE CURRENT NOA.
  
 E) NEW COMMENT: "FIBERGLASS SHINGLE ROOF ADHESIVE" AS
 SPECIFIED ON SHEET A-4 WALL SECTIONS.
  
 3- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS. SEC. SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 4- GEO-TECHNICAL REPORT SUBMITTED: REVISE PROJECT
 DESCRIPTION. PLANS SUBMITTED ARE FOR A TWO STORY
 CONCRETE BLOCK HOUSE NOT ONE STORY RESIDENCE. REVISE
 ANY RECOMMENDATIONS IF REQUIRED BY THE CORRECT SCOPE OF
 WORK. SEC. R401.2 OF 2010 FBC-RESIDENTIAL.
  
 5- TRUSS PACKAGE:
 A) TRUSS PACKAGE TO BE REVIEWED BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL.
 B) NEED ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 471 FL. ST.
 C) PROVIDE COMPLETE INFORMATION FOR THE ENGINEER OF
 RECORD. SEC. 61G15-31.003.
 D) TRUSS LAYOUT NEED TO BE SIGNED AND SEALED. SEC.
 61G15-31.003
  
 NOTE: PROPERTY IS LOCATED IN FLOOD ZONE A5. ELEVATION
 CERTIFICATES WILL BE REQUIRED DURING CONSTRUCTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]