| 2015-02-26 18:54:34 | |
| | *********REVIEW IN PROGRESS.... |
| | |
| | VERY IMPORTANT NEW COMMENT: |
| | REVISED SURVEY SHOWING THE PROPOSED DRAINAGE FLOW |
| | DIRECTIONAL ARROW ALSO SHOWS THE GARAGE WITH A FINISHED |
| | FLOOR ELEVATION OF 7.05". THIS PROPERTY IS LOCATED IN |
| | FLOOD ZONE A5 WITH A BASED FLOOD ELEVATION OF 7.0'. THE |
| | MIN. GARAGE FINISH FLOOR ELEVATION REQUIRED IS 7.6". |
| | OTHERWISE COMPLY WITH THE REQUIREMENTS OF SEC. R322 OF |
| | 2010 FBC. REVISE ALL PLANS AS REQUIRED. |
| | |
| | FROM PREVIOUS COMMENTS: |
| | 1- SHEET A-2: WINDOW #19 BY THE SITTING AREA NEEDS TO |
| | COMPLY WITH LIFE SAFETY ISSUES OF SEC. R612.2 OF 2010 |
| | FBC-RESIDENTIAL. REVISE PLANS AS REQUIRED. NOT |
| | ADDRESSED CORRECTLY. LIFE-SAFETY ISSUE IS FALLING FROM |
| | WINDOW NOT SAFETY GLASS. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) SHINGLES SELF ADHERING UNDERLAYMENT AS SPECIFIED ON |
| | PLANS. NOA 11-0815.05 SUBMITTED WAS SUPERSEDED BY |
| | MIAMI-DADE. NEED CURRENT NOA. |
| | |
| | B) ALL USP STRUCTURAL CONNECTORS SPECIFIED ON PLANS AND |
| | SECTION/DETAILS. PROVIDE PRODUCT APPROVAL COVER PAGE |
| | AND PAGE SHOWING THE SPECIFIED CONNECTOR OR LIST THE |
| | FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE SPECIFIED |
| | CONNECTOR. |
| | NOTE: THERE ARE TWO SITE SPECIFIC CONNECTORS SHOWN ON |
| | SHEET S-4. NEED TO PROVIDE COMPLETE ENGINEERING PACKAGE |
| | FOR SITE SPECIFIC CONNECTORS APPROVAL. AND, THE |
| | ENGINEER (JAMES F. COLLINS JR.) NEED TO USE CURRENT |
| | SEAL THAT READS "LICENSE" INSTEAD OF "CERTIFICATE" AS |
| | REQUIRED BY FLORIDA BOARD OF PROFESSIONAL ENGINEERS |
| | WHEN SUBMITTING ENGINEERING PACKAGE FOR SITE SPECIFIC |
| | APPROVAL. |
| | |
| | C) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | D) ROOF SHINGLES. NOA 13-0419.04 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. |
| | |
| | E) NEW COMMENT: "FIBERGLASS SHINGLE ROOF ADHESIVE" AS |
| | SPECIFIED ON SHEET A-4 WALL SECTIONS. |
| | |
| | 3- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT |
| | APPROVALS. SEC. SEC. 107.3.4.1 CITY AMENDMENTS TO FBC. |
| | |
| | 4- GEO-TECHNICAL REPORT SUBMITTED: REVISE PROJECT |
| | DESCRIPTION. PLANS SUBMITTED ARE FOR A TWO STORY |
| | CONCRETE BLOCK HOUSE NOT ONE STORY RESIDENCE. REVISE |
| | ANY RECOMMENDATIONS IF REQUIRED BY THE CORRECT SCOPE OF |
| | WORK. SEC. R401.2 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 5- TRUSS PACKAGE: |
| | A) TRUSS PACKAGE TO BE REVIEWED BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL. |
| | B) NEED ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS |
| | REQUIRED BY CHAPTER 471 FL. ST. |
| | C) PROVIDE COMPLETE INFORMATION FOR THE ENGINEER OF |
| | RECORD. SEC. 61G15-31.003. |
| | D) TRUSS LAYOUT NEED TO BE SIGNED AND SEALED. SEC. |
| | 61G15-31.003 |
| | |
| | NOTE: PROPERTY IS LOCATED IN FLOOD ZONE A5. ELEVATION |
| | CERTIFICATES WILL BE REQUIRED DURING CONSTRUCTION. |
| | |