2015-01-07 16:52:00NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- A/C EQUIPMENT SIZING CALCULATIONS SUBMITTED ARE DONE
 FOR WORST CASE SCENARIO. SEC. 403.6 OF 2010 FBC-ENERGY
 CONSERVATION DOESN'T ALLOW WORST CASE SCENARIO.
 CALCULATIONS NEED TO BE REVISED BASED ON THE ACTUAL
 BUILDING ORIENTATION.
  
 ***NOTE: PROVIDE CORRECT ADDRESS. THIS IS NOT LOT 18
 GREGORY RD.
  
 2- A/C PLAN:
 A) PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  
 B) FAMILY ROOM NEEDS TO COMPLY WITH THE BALANCED RETURN
 AIR AS REQUIRED BY SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL. THIS ROOM CAN BE CLOSED WHEN ALL DOORS
 ARE CLOSED.
  
 C) SIZE OF TRANSFER DUCT SPECIFIED FOR THE MASTER
 BEDROOM DOESN'T COMPLY WITH SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL. NEED TO CONSIDER ALL THE SUPPLY AIR
 INTO THE MASTER SUITE, INCLUDING CLOSETS AND BATHROOM
 TO SIZE THE TRANSFER DUCT. REVISE SIZE AS REQUIRED.
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  