| Notes |
| Date |
Text |
| 2015-01-07 16:52:00 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- A/C EQUIPMENT SIZING CALCULATIONS SUBMITTED ARE DONE | | | FOR WORST CASE SCENARIO. SEC. 403.6 OF 2010 FBC-ENERGY | | | CONSERVATION DOESN'T ALLOW WORST CASE SCENARIO. | | | CALCULATIONS NEED TO BE REVISED BASED ON THE ACTUAL | | | BUILDING ORIENTATION. | | | | | | ***NOTE: PROVIDE CORRECT ADDRESS. THIS IS NOT LOT 18 | | | GREGORY RD. | | | | | | 2- A/C PLAN: | | | A) PROVIDE THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1 | | | CITY AMENDMENTS TO FBC. | | | | | | B) FAMILY ROOM NEEDS TO COMPLY WITH THE BALANCED RETURN | | | AIR AS REQUIRED BY SEC. M1602.4 OF 2010 | | | FBC-RESIDENTIAL. THIS ROOM CAN BE CLOSED WHEN ALL DOORS | | | ARE CLOSED. | | | | | | C) SIZE OF TRANSFER DUCT SPECIFIED FOR THE MASTER | | | BEDROOM DOESN'T COMPLY WITH SEC. M1602.4 OF 2010 | | | FBC-RESIDENTIAL. NEED TO CONSIDER ALL THE SUPPLY AIR | | | INTO THE MASTER SUITE, INCLUDING CLOSETS AND BATHROOM | | | TO SIZE THE TRANSFER DUCT. REVISE SIZE AS REQUIRED. | | | | | | *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|