2015-01-06 12:46:18NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- A) DESIGNER OF RECORD TO SPECIFY ALL LIVE AND DEAD
 LOADS, INCLUDING THE ATTIC LIVE LOAD REQUIRED BY TABLE
 R301.5 OF 2010 FBC-RESIDENTIAL.
 NOTE: ALSO, TAKE INTO CONSIDERATION THE 1" GYPCRETE
 SLAB SPECIFIED ON TYPICAL 2 STORY WALL SECTION ON SHEET
 A-4.
  
 B) STRUCTURAL DRAWINGS TO SHOW THE ADDITIONAL 1"
 GYPCRETE SLAB. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 3- POWDER ROOM ON FIRST FLOOR NEEDS A DOOR THAT PROVIDE
 29" CLEAR OPENING AS REQUIRED BY SEC. R320 OF 2010
 FBC-RESIDENTIAL. REVISE SIZE AS REQUIRED.
  
 4- PROVIDE SPECIFICATIONS FOR DOOR LEADING FROM GARAGE
 TO THE INTERIOR OF THE HOUSE SHOWING COMPLIANCE WITH
 SEC. R302.5.1 OF 2010 FBC-RESIDENTIAL.
  
 5- REVISE ATTIC ACCESS SECTION SECTION ON SHEET A-2.
 OPENING TO COMPLY WITH SECTION R807 OF 2010 FBC.
  
 6- SHEET A-2: WINDOW #19 BY THE SITTING AREA NEEDS TO
 COMPLY WITH LIFE SAFETY ISSUES OF SEC. R612.2 OF 2010
 FBC-RESIDENTIAL. REVISE PLANS AS REQUIRED.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SHINGLES SELF ADHERING UNDERLAYMENT AS SPECIFIED ON
 PLANS.
  
 B) ALL USP STRUCTURAL CONNECTORS SPECIFIED ON PLANS AND
 SECTION/DETAILS. PROVIDE PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR LIST THE
 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE SPECIFIED
 CONNECTOR. NOTE: ONLY ONE OF THE FLORIDA PRODUCT
 APPROVAL NUMBERS LISTED ON THE TRUSS SCHEDULE IS
 CURRENT. NEED TO REVISE THE REST OF THEM. ALSO, PROVIDE
 THE PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR ON ALL OTHER DETAILS.
  
 C) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 D) ROOF SHINGLES. NOA 11-1122.04 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE CURRENT NOA.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS TO FBC.
  
 9- TYPICAL WALL SECTIONS ON SHEET A-4: CLARIFY ROOFING
 MATERIAL. SHINGLES OR ROOF TILE. BOTH ARE SPECIFIED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 10- PROVIDE ICC EVALUATION REPORT (OR ANY OTHER
 APPROVED REPORT) FOR ICYNENE INSULATION AS SPECIFIED ON
 PLANS TO SHOW COMPLIANCE WITH SEC. R316 OF 2010
 FBC-RESIDENTIAL.
  
 11- PROVIDE HANDRAILS AND GUARDRAILS DETAILS SHOWING
 COMPLIANCE WITH THE LIVE LOADS OF TABLE R301.5 OF 2010
 FBC-RESIDENTIAL.
  
 12- PROVIDE SURFACE DRAINAGE PLAN SHOWING COMPLIANCE
 WITH SEC. R401.3 OF 2010 FBC-RESIDENTIAL.
  
 13- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES. VALUATION UPDATED TO $294,379. THE
 PERMIT FEE BALANCE IS $5065.67.
  
 14- GEO-TECHNICAL REPORT SUBMITTED:
 A) NEEDS THE ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 471 FL. ST.
  
 B) REVISE PROJECT DESCRIPTION. PLANS SUBMITTED ARE FOR
 A TWO STORY CONCRETE BLOCK HOUSE NOT ONE STORY
 RESIDENCE. SEC. R401.2 OF 2010 FBC-RESIDENTIAL.
  
 15- FOOTINGS SHOWN ON SHEET A-4 AND S-1 DON'T MATCH
 RECOMMENDATIONS SPECIFIED ON THE GEOTECHNICAL REPORT.
 SEE PAGE 8 OF 9 OF THE GEO-TECHNICAL REPORT FOR THE
 RECOMMENDED MIN. DEPTH BELOW FINISH GRADE AND
 STRUCTURAL SEPARATION BETWEEN FOOTINGS AND FLOOR SLAB.
 DESIGNER OF RECORD TO REVIEW REVISED REPORT (SEE
 COMMENT #14(B) ABOVE) AND PROVIDE MODIFICATIONS AS
 REQUIRED. ALSO, TAKE INTO CONSIDERATION THAT THIS
 PROPERTY IS LOCATED IN FLOOD ZONE A5. SEC. R401.2 OF
 2010 FBC-RESIDENTIAL.
  
 16- PROVIDE WINDOWS AND DOORS MANUFACTURER SPECS
 SHOWING COMPLIANCE WITH THE U-FACTOR AND SHGC FACTOR
 SPECIFIED ON THE ENERGY CALCULATIONS. SEE SEC. 303.1.3
 OF 2010 FBC-ENERGY CONSERVATION.
 ***NOTE: THIS IS ONLY REQUESTED WHEN THE ENERGY
 CALCULATIONS USE FENESTRATION FACTORS OTHER THAN THE
 DEFAULT FACTORS. THIS WILL AVOID CONFLICTS OR DELAYS
 DURING CONSTRUCTION.
  
 17- REVISE ENERGY CALCULATIONS. THE STREET IS NOT LOT
 18 GREGORY RD. PROVIDE CORRECT ADDRESS AND PROVIDE
 COMPLETE INFORMATION INCLUDING OWNER, BUILDER NAME,
 PERMIT OFFICE AND JURISDICTION NUMBER. SEC. 103.2.1.1.2
 OF 2010 FBC-ENERGY CONSERVATION.
  
 18-TRUSS PACKAGE:
 A) TRUSS PACKAGE TO BE REVIEWED BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL.
 B) NEED ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 471 FL. ST.
 C) PROVIDE COMPLETE INFORMATION FOR THE ENGINEER OF
 RECORD. SEC. 61G15-31.003.
 D) TRUSS LAYOUT NEED TO BE SIGNED AND SEALED. SEC.
 61G15-31.003
 NOTE: TRUSS PACKAGE DOES NO NEED TO BE RE-SUBMITTED TO
 THIS OFFICE. AFTER ALL CORRECTIONS ARE DONE, TRUSS
 PACKAGE MAY BE DELIVERED TO THE BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
  
 19- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 DECORATIVE SHUTTERS SHOWN ON ELEVATIONS. SPECIFY
 MATERIALS AND COMPLETE INSTALLATION DETAILS TO SHOW
 COMPLIANCE WITH SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
  
 NOTE: PROPERTY IS LOCATED IN FLOOD ZONE A5. ELEVATION
 CERTIFICATES WILL BE REQUIRED DURING CONSTRUCTION.
  
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REMOVE AND REPLACE ANY REVISED SHEET.
  