| 2014-12-16 09:23:22 | 12/16/2014 |
| | PROJECT: FARINO RESIDENCE |
| | PERMIT#: 14120500 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED. |
| | |
| | FBC-WPB AMENDMENTS 107.3.5 |
| | NO ELECTRICAL PLANS, DETAILS OR SPECIFICATIONS |
| | PROVIDED. PROVIDE THE FOLLOWING FOR MINIMUM PLAN REVIEW |
| | CRITERIA: |
| | |
| | 1) PROVIDE DETAILS FOR THE DEMOLITION PLAN TO INDICATE |
| | THE FOLLOWING: |
| | A. THE LOCATION OF THE ELECTRICAL SERVICE, ASSOCIATED |
| | DISCONNECTS AND PANELS. |
| | B. HOW THE ELECTRICAL DEMOLITION IS PROPOSED TO TAKE |
| | PLACE. SUCH AS WHAT ELEMENTS ARE EXISTING TO REMAIN AND |
| | WHAT IS TO BE REMOVED. |
| | C. FOR THOSE ELECTRICAL ELEMENTS PROPOSED TO BE |
| | REMOVED, INDICATE THE LOCATION THAT THE CIRCUIT OR |
| | FEEDER IS PROPOSED TO TERMINATE. |
| | |
| | 2) PROVIDE DETAILS FOR THE NEW CONSTRUCTION TO INDICATE |
| | THE FOLLOWING: |
| | A. A DETAILED ELECTRICAL SERVICE RISER TO INCLUDE A |
| | GROUNDING ELECTRODE SYSTEM, THE UTILITY METERING |
| | DEVICE(S) SERVICE DISCONNECT(S), PANEL(S), AND ALL |
| | CONDUIT AND WIRE SIZES FOR SERVICE ENTRANCE AND |
| | FEEDERS. NEC 215.5 |
| | B. A COMPLETE DETAILED LOAD CALCULATION. NEC 220 |
| | C. EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE |
| | LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND |
| | SPECIFIC PURPOSE OR USE. NEC 408.4 |
| | D. PROVIDE A COMPLETE FLOOR PLAN INDICATING ALL OUTLETS |
| | AND LIGHTING AS REQUIRED BY THE 2008 EDITION OF THE |
| | NATIONAL ELECTRICAL CODE AND THE 2010 EDITION OF THE |
| | FBC 107.3.5, NEC 210.52 |
| | E. ALL CIRCUITS NUMBERS IN THE PANEL DIRECTORIES TO BE |
| | INDICATED ON THE FLLOOR PLAN. FBC-WPB AMENDMENTS |
| | 107.3.5 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |