Plan Review Notes
Plan Review Notes For Permit 14120442
Permit Number 14120442
Review Stop B
Sequence Number 1
Notes
Date Text
2014-12-11 17:51:28RE-ROOF, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC
  
 1- PROVIDE SIGNED AND SEALED RAS 117 FOR NAIL ENHANCING
 AT PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF BUILT UP ROOF SYSTEMS
 OVER WOOD DECKS NOA 13-1022.15 SUBMITTED. NEED THE
 CALCULATIONS TO MEET THE DESIGN PRESSURES OF SEC. 1609
 OF 2010 FBC.
 ***NOTE: PROVIDE 2 COPIES WITH ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 FL. ST.
  
 2- GEORGIA- PACIFIC INSULATION NOA 01-0820.07 SUBMITTED
 EXPIRED ON 02/02/02. NEED TO PROVIDE CURRENT NOA (2
 COPIES) AS REQUIRED BY DCA RULE 9N-3.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION TO
 INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND
 PROFIT AND DESIGN PROFESSIONAL FEES. VALUATION WAS
 UPDATED TO $12,374. THE PERMIT FEE BALANCE IS $329.48.
  
 4- SKETCH SUBMITTED SHOWS 130 L.F. OF ALUMINUM
 GUARDRAIL AND CONCRETE POSTS. THIS IS NOT PART OF THE
 SCOPE OF WORK OF A ROOFING CONTRACTOR. NEED SEPARATE
 PERMIT WITH COMPLETE INFORMATION UNDER A SEPARATE
 PERMIT. SEC. 489.113 FL. ST.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712