| Plan Review Notes For Permit 14120431 |
| Permit Number |
14120431 |
|
| Review Stop |
FIRE |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2015-05-13 14:16:21 | 312 23RD STREET | | | PERMIT #14120431 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY | | | REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE | | | (2009 EDITION WITH FLORIDA AMENDMENTS.) | | | | | | RESPONSE COMMENT: THE VERTICAL STANDPIPE NEEDS TO BE | | | PROTECTED IN A RATED ENCLOSURE EQUAL TO THE STAIR | | | ENCLOSURE PROTECTION. SIMPLY PROTECTING THE FLOOR | | | PENETRATIONS IS NOT THE EQUIVALENT. | | | REPEAT COMMENT: VERTICAL STANDPIPE RISERS SUPPLYING THE | | | FIRE DEPARTMENT VALVES ARE REQUIRED TO BE LOCATED IN A | | | 2-HOUR FIRE BARRIER/SHAFT PER NFPA 14 SECTION 6.1.2.2. | | | | | | DISCLAIMER: FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT | | | ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED | | | WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, | | | ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE | | | TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT | | | THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A | | | CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR | | | VIOLATIONS OF THIS CODE. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|