| 2015-03-30 06:57:41 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 14120431 |
| | ADD: 321 23RD ST. |
| | PCN:74-43-43-10-19-003-0143 |
| | CONT: PETROCCHI CONSTRUCTION |
| | TEL: (305)495-3745 |
| | E-MAI: [email protected] |
| | |
| | PARK PALM BEACH MULTIFAMILY RESIDENTIAL |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | 2ND REVIEW |
| | DATE: SAT. 27/ 2015 |
| | ACTION: DENIED |
| | NOTICE: CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES |
| | THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR |
| | TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED |
| | (3) OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A |
| | CODE VIOLATION. |
| | |
| | NOTICE: ART IN PUBLIC PLACES |
| | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES |
| | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR |
| | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT |
| | APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE TOTAL |
| | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| | $500,000. PER CITY OF WEST PALM BEACH ORDINANCE NO. |
| | 4504-14, AND CITY OF WEST PALM BEACH CODE OF |
| | ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION |
| | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS |
| | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. |
| | |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS |
| | |
| | 1) THE PERMIT APPLICATION LIST THE ADDRESS OF 321 23RD |
| | ST./ 74-43-43-10-19-003-0143, THIS IS A SINGLE LOT, |
| | THIS WILL REQUIRE MORE THAN A UNITY OF TITLE, THIS |
| | PROJECT WILL REQUIRE A REPLAT WITH A NEW PCN AND |
| | POSSIBLE ADDRESS CHANGE. |
| | 2) THIS PROJECT IS FOR A 4 STORY BUILDING THAT |
| | QUALIFIES AS A THRESHOLD BUILDING. FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. |
| | IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | 2A) 2ND. REQUEST. THE RESPONSE INDICATED THE WRITTEN |
| | STRUCTURAL INSPECTION PLAN WAS ATTACHED TO THE RESPONSE |
| | PACKAGE. NOTE I?VE GONE THROUGH ALL OF THE RESPONSE |
| | PACKAGES, ARCHITECTURAL, STRUCTURAL, AND MEP RESPONSE |
| | SHEETS; THERE IS NO WRITTEN STRUCTURAL INSPECTION PLAN. |
| | 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| | (WRITTEN/ TYPED) SPECIAL INSPECTOR TO PERFORM |
| | STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT |
| | TO A STRUCTURAL INSPECTION PLAN PREPARED BY THE |
| | ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST |
| | BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| | ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| | THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| | INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| | PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| | ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| | DOCUMENTS. |
| | 2B) COMPLIED. |
| | THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. AMENDMENT |
| | 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH ARE |
| | REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR |
| | ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 2C) 2ND. REQUEST. RESPONSE, OWNER WILL SUBMIT. FOR THE |
| | SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME' |
| | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, AN |
| | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | D) 2ND. REQUEST. RESPONSE, OWNER WILL SUBMIT. THE |
| | CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY FOR |
| | THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO KEN |
| | CONRAD BY E-MAIL. KEN CONRAD: [email protected] |
| | E) NOTE NO ACTION IS REQUIRED, WE ARE E-MAILING YOU THE |
| | THRESHOLD INSPECTOR DOCUMENTS AND FORMS TO THIS E-MAIL |
| | ADDRESS; E-MAIL: [email protected] JAN. |
| | 20/2015 |
| | F) NOTICE: THIS IS A DIGITAL PLAN, AFTER PERMIT |
| | ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS. |
| | |
| | G) NOTICE TO THRESHOLD INSPECTOR & CONTRACTOR. PLEASE |
| | CALL THE CITY OF WEST PALM BEACH?S AUTOMATED TELEPHONE |
| | INSPECTIONS LINE (561) 805-6700) FOR IN-PROGRESS |
| | INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS. |
| | H) 2ND. REQUEST. RESPONSE INFORMATIONAL ONLY, PLEASE |
| | INCORPORATE INTO THE PLANS UNDER FIRE STOPPING |
| | PENETRATIONS. 109.3.6 THRESHOLD BUILDINGS, OPERATING |
| | GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT |
| | THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| | PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | 3) RESPONSE SEE RESPONSE FROM OWNER AND CONTRACTOR, |
| | WHERE. THE PERMIT VALUATION OF $8,500,000.00 IS LOW |
| | COMPARED TO THE CALCULATED VALUE FROM THE ICC BUILDING |
| | VALUATION DATA AUGUST 2014 USING THESE TABLES THE |
| | CALCULATED VALUE OF $9,855,203.00. PLEASE NOTE ANY |
| | SUB-PERMIT THAT TAKES SEPARATE FEES AND REVIEWS PLEASE |
| | LIST PERMITS AND VALUES, THESE WILL BE DEDUCTED FROM |
| | THE PRIME VALUE. ANY PERMITS AND VALUES NOT INCLUDED IN |
| | THIS LIST WILL REQUIRE SEPARATE FEES & REVIEWS. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 108.3* BUILDING PERMIT |
| | VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | 4) COMPLIED. |
| | PLEASE NOTE UNDER THE FOLDER SUPPORTING DOCUMENTS, |
| | MISSING WAS THE SOILS REPORT PREPARED BY ANDAMAN FILE |
| | 03-2310 02/06/04. 2010 FBC-B |
| | 1803.5.2 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, |
| | STRENGTH OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR |
| | WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED |
| | IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| | PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| | BE CONDUCTED. |
| | 5) PAGE 003/ A-1.00 CODE SUMMARY SHEET: |
| | 5A) COMPLIED.. |
| | 5B) OCCUPANCY & MEANS OF EGRESS HEADING: CORRECTION, |
| | MERCANTILE 3,212 GRS SF / 30 SF PER OCC.=108 FBC-B |
| | TABLE 1004.1.1 |
| | 5C) OCCUPANCY & MEANS OF EGRESS HEADING: CORRECTION, |
| | A-2 COURTYARD/ POOL & DECK CORRECTION 13 +104= 117 |
| | OCCUPANTS. TYPO |
| | 5D) COMPLIED. |
| | ALLOWABLE EXTERIOR OPENINGS CANNOT BE VERIFIED, THE |
| | PROPERTY LINES HAVE NOT BEEN PROVIDED AND THE DISTANCE |
| | AWAY FROM THE PROPERTY LINE. FBC-B TABLE 602 EXTERIOR |
| | FIRE RATINGS AND TABLE 705.8 ALLOWABLE OPENINGS. |
| | |
| | 6) PAGE 004/ A-1.01 (NOTE K)/ 008- A-1.05 ON BOTH |
| | SHEETS THERE ARE NOTES TO COMPLY WITH 1207.2 AIR-BORNE |
| | SOUND AND 1207.3 STRUCTURE BORNE SOUND. IN NEITHER CASE |
| | HAS TESTING REPORTS SUBMITTED PROVIDING CODE |
| | COMPLIANCE. PAGE 008 HAD A NOTE OF REPORT NGC7005033 |
| | BUT NOT SUBMITTED. |
| | THERE ARE GOING TO BE (2) ISSUES WITH THE RESPONSE |
| | ABOUT AIR-BORNE TESTING AND STRUCTURE BORNE TESTING. |
| | 6A)(1) THE 1ST ISSUE IS FOR FIELD TESTING OF FLOOR |
| | SYSTEMS TO ASTM E90 AND ASTM E492 (2010 FBC-B 1207.3) |
| | FOR EACH FLOOR SYSTEM WITH DIFFERENT ASSEMBLIES WILL BE |
| | REQUIRED. STC/ IIC 45 FIELD TESTED. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1 107.3.3 CONTRACTOR IS AT OWN RISK, NO |
| | ASSURANCES THAT A CERTIFICATE OF OCCUPANCY CAN BE |
| | ISSUED WITHOUT CODE COMPLIANCE. |
| | 6A(2) THERE WILL BE ADDITIONAL TESTING OF AIR-BORNE |
| | SOUND (2010 FBC-B 1207.2 & 1207.2.1) FOR EACH TYPE OF |
| | WALL ASSEMBLY, SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 45 WHEN FIELD TESTED. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1 107.3.3 CONTRACTOR IS AT OWN RISK, NO |
| | ASSURANCES THAT A CERTIFICATE OF OCCUPANCY CAN BE |
| | ISSUED WITHOUT CODE COMPLIANCE |
| | 6A)(3) CONCRETE MASONRY ASSEMBLIES SHALL BE CALCULATED |
| | IN ACCORDANCE WITH TMS 0302 OR DETERMINED THROUGH |
| | TESTING IN ACCORDANCE WITH ASTM E 90. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1 107.3.3 CONTRACTOR IS AT OWN RISK, NO |
| | ASSURANCES THAT A CERTIFICATE OF OCCUPANCY CAN BE |
| | ISSUED WITHOUT CODE COMPLIANCE |
| | 6B) THE SECOND ISSUE THE ABOVE TESTING DOES NOT TAKE |
| | PLACE UNTIL THE UNITS ARE FINISHED AND CREDITS ARE |
| | BASICALLY TAKEN INTO ACCOUNT FOR FINISHES THAT ABSORB |
| | SOUND TRANSFER. THE ISSUE WILL BE COMPLIANCE WITH |
| | SECTION 2010 FBC-B 719.2 CONCEALED INSULATION OF |
| | INSULATING MATERIALS, SHALL HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT |
| | MORE THAN 450. BEFORE THE INSULATION IS INSTALLED IN |
| | WALLS OR FLOOR DECKS OR WITHIN FLOOR ASSEMBLIES THIS |
| | CODE SECTION HAS TO BE MET. |
| | 6C) NEW COMMENT DEALS WITH THE ENERGY CALCULATIONS AND |
| | CREDITS TAKEN FOR FLOORS, THE 2ND FLOOR RESIDENTIAL |
| | UNITS WITH THE GARAGE BENEATH AS WELL AS UNITS OVER THE |
| | AIR CONDITIONED SPACE TAKE CREDIT FOR 1 FT. OF SOIL |
| | CONCRETE FLOORS CARPET AND RUBBER PAD. SHEET 008/A-1.05 |
| | FLOOR/ WALL ASSEMBLIES DETAIL # 40 SHOWS THE FLOOR/ |
| | CEILING ASSEMBLY 1ST FLOOR RESIDENTIAL /GARAGE CEILING |
| | ASSEMBLY NO R-VALUE ASSIGNED TO THE ASSEMBLY THROUGH |
| | THE ENERGY CALCS. NOTE THERE IS AN OPTIONAL HIGH HAT |
| | AND 5/8 INCH GYPSUM WALL BOARD. |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH DRAWINGS |
| | AND SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE |
| | FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | |
| | 7) PAGE 005/ A-1.02 OCCUPANCY & EGRESS PLAN / FIRE WALL |
| | SEPARATION. |
| | PAGE 023/ A-3.41 SOUTH STAIRS |
| | PAGE 024/ A-4.11 FIRST FLOOR PLAN |
| | |
| | 7A)(1) COMPLIED. 4/01/2015 SPOKE WITH THE DESIGNER OF |
| | RECORD, RESOLVED ISSUE WITH SECTION 1027.1 EXCEPTION |
| | 1.1-1.3. |
| | |
| | 7A)(2) NEW COMMENT. THE LISTED ABOVE SHEETS DO NOT |
| | PROVIDE DOOR IDENTIFICATION TAGS TO VERIFY FIRE |
| | RESISTANCE RATINGS. 2010 FBC-B TABLE 715.4. |
| | |
| | 7B-H) COMPLIED. |
| | |
| | 8) COMPLIED. |
| | 9) PAGE 42/ A-6.20 : |
| | 9A) 2ND REQUEST. TRASH ROOM 2ND THROUGH THE 4TH FLOOR |
| | SHOW THE WHOLE OF THE TRASH ROOM/ ENCLOSURE AS BEING |
| | WITHIN THE 2 HOUR RATING FOR A SHAFT. DETAIL # 6 LABELS |
| | THE REFUSE CHUTE ITSELF AS THE SHAFT, THIS IS JUST THE |
| | TRASH CHUTE ITSELF. |
| | FBC-B 708.13.1 REFUSE AND LAUNDRY CHUTE ENCLOSURES. A |
| | SHAFT ENCLOSURE CONTAINING A REFUSE OR LAUNDRY CHUTE |
| | SHALL NOT BE USED FOR ANY OTHER PURPOSE AND SHALL BE |
| | ENCLOSED IN ACCORDANCE WITH SECTION 708.4. OPENINGS |
| | INTO THE SHAFT, INCLUDING THOSE FROM ACCESS ROOMS AND |
| | TERMINATION ROOMS, SHALL BE PROTECTED IN ACCORDANCE |
| | WITH THIS SECTION AND SECTION 715. OPENINGS INTO CHUTES |
| | SHALL NOT BE LOCATED IN CORRIDORS. DOORS SHALL BE SELF- |
| | OR AUTOMATIC-CLOSING UPON THE ACTUATION OF A SMOKE |
| | DETECTOR IN ACCORDANCE WITH SECTION 715.4.8.3, EXCEPT |
| | THAT HEAT-ACTIVATED CLOSING DEVICES SHALL BE PERMITTED |
| | BETWEEN THE SHAFT AND THE TERMINATION ROOM. |
| | |
| | 9B) 2ND REQUEST, SHAFT IS STILL ENCLOSING THE ACCESS |
| | ROOM SEPARATING THE SHAFT FROM CORRIDOR. WITH THE |
| | CORRECTED SHAFT THE ACCESS ROOM THAT LEADS FROM THE |
| | CORRIDOR TO THE REFUSE CHUTE, THIS AREA WILL NEED TO |
| | COMPLY WITH 708.13.3 A 1 HOUR FIRE BARRIER WITH 3/4 HR. |
| | DOOR SELF-CLOSING OR AUTOMATIC CLOSING UPON THE |
| | DETECTION OF SMOKE IN ACCORDANCE WITH SECTION |
| | 715.4.8.3. DOOR IS SHOWN AS ? HR. |
| | |
| | 9C) COMPLIED. |
| | DETAIL # 6 FOR THE TRASH COLLECTION ROOM FAILS TO |
| | PROVIDE A FIRE RATING AT THE BOTTOM OF THE SHAFT, (2ND |
| | FLOOR LEVEL). SEE FBC-B 708.11 ENCLOSURE AT THE BOTTOM. |
| | NOTE THAT THE 3 HOUR FIRE RATED WALLS WOULD MEET THE |
| | FIRE RATINGS REQUIRED, ONLY 2 HRS. REQUIRED BUT THE |
| | OPENING PROTECTIVES WOULD THEN NEED TO BE 1 1/2 HOUR |
| | FIRE RATING PER TABLE 715.4. |
| | |
| | 10-12) COMPLIED. |
| | 13-18) REFER BACK TO THE REQUIREMENT OF COMMENT # 6 AND |
| | RESPONSE TO BE AIR-BORNE & STRUCTURE BORN SOUND TO BE |
| | FIELD TESTED. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1 107.3.3 CONTRACTOR IS |
| | AT OWN RISK, NO ASSURANCES THAT A CERTIFICATE OF |
| | OCCUPANCY CAN BE ISSUED WITHOUT CODE COMPLIANCE |
| | 13A) PAGE 17/ A-3.10 THE EXIT ACCESS WALL COMMON TO |
| | THIS UNIT HAS A WALL TAG # 21 THIS WALL DOES NOT |
| | INDICATE COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| | ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| | CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| | EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| | OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| | THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| | ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| | FITTING TO THE FRAME AND SILL. |
| | |
| | 13B) PAGE 18/ A-3.11 THE EXIT ACCESS WALL COMMON TO |
| | THIS UNIT HAS A WALL TAG # 21 THIS WALL DOES NOT |
| | INDICATE COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| | ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| | CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| | EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| | OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| | THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| | ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| | FITTING TO THE FRAME AND SILL. |
| | |
| | 14A) PAGE 19/ A3.12 THE BATHROOM WALL NEXT TO THE |
| | GARDEN TUB DOES NOT HAVE A WALL IDENTIFICATION TAG, |
| | SHOW COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| | |
| | 14B) PAGE 19/ A3.12 THE KITCHEN WALL NEXT TO THE SINK |
| | HAS A WALL IDENTIFICATION TAG OF 33, THIS WALL DOES NOT |
| | HAVE ANY SOUND RATING, SHOW COMPLIANCE WITH FBC-B |
| | 1207.2 AIR-BORNE SOUND. |
| | |
| | 15) PAGE 20/ A3.20 THE EXIT ACCESS WALL COMMON TO THIS |
| | UNIT HAS A WALL TAG # 21 THIS WALL DOES NOT INDICATE |
| | COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| | |
| | 16A) A3.21 THE EXIT ACCESS WALL COMMON TO THIS UNIT HAS |
| | A WALL TAG # 21 THIS WALL DOES NOT INDICATE COMPLIANCE |
| | WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| | |
| | 16B) MASTER BATH GARDEN TUB WALL THAT BACKS UP TO |
| | SHAFT, NO SHAFT IS SHOWN WALL TAG# 30 , WALL TYPE 30 |
| | DOES NOT PROVIDE COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE |
| | SOUND. |
| | |
| | 17) A3.22 WALL TAGS 33 & 35, BOTH OF THESE WALLS DO NOT |
| | PROVIDE COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| | |
| | 18) PAGE 25, A4.12 HVAC SHAFT, THIS COMMENT STANDS FOR |
| | ALL FLOORS, WALL TAG # 30 DOES NOT SHOW COMPLIANCE WITH |
| | FBC-B 1207.2 AIR-BORNE SOUND. |
| | |
| | 19) 2ND REQUEST, THE DESIGNER OF RECORD HAS LISTED THE |
| | CODE SECTION ON THIS SHEET, NOT THE DESIGN PARAMETERS. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. SUCH INFORMATION SHALL BE |
| | SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR |
| | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | |
| | 1ST REVIEW COMMENT. PAGE 43/ A7.01 GUARD RAILINGS FOR |
| | BALCONIES. DETAILS 3, 10 & 11 SHOW GUARD RAIL |
| | ATTACHMENT TO THE STRUCTURE WITH EXPANSION BOLTS. THERE |
| | IS A NOTE ON THE PLANS THAT THE CONNECTION DETAILS ARE |
| | TO BE DESIGNED BY A ENGINEER LICENSED IN THE STATE OF |
| | FLORIDA. WHAT THE DESIGNER OF RECORD FAILED TO PROVIDE |
| | IS THE REQUIREMENTS OF THE CODE FOR THE ENGINEER TO |
| | FOLLOW. |
| | 2010 FBC-B 1607.7.1 HANDRAILS AND GUARDS. |
| | 1607.7.1.1 CONCENTRATED LOAD. |
| | 1607.7.1.2 COMPONENTS. |
| | 20) 2ND REQUEST. THE NEW NOTES QUOTE THE CODE SECTION, |
| | THEY DO NOT GIVE THE FABRICATOR TO WHICH DESIGN |
| | CRITERIA YOU ARE SPECIFYING FOR THESE ELEMENTS ON YOUR |
| | BUILDING. THE DESIGNER OF RECORD HAS LISTED THE CODE |
| | SECTION ON THIS SHEET, NOT THE DESIGN PARAMETERS. 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. SUCH INFORMATION SHALL BE |
| | SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR |
| | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | |
| | 1ST REVIEW COMMENT. PAGE 44/ A-7.02 & S-7.04 VARIOUS |
| | DETAILS AND DESIGN ARE SHOWN FOR CANOPY AND AWNINGS, |
| | THERE IS NO ATTACHMENT INFORMATION NOR IS THERE A |
| | PROPOSED WIND DESIGN PARAMETERS FOR THE SPECIALTY |
| | ENGINEER TO DESIGN. FBC-B 3105. |
| | 21)2ND REQUEST, ENERGY CALCULATIONS DATED 12/09/2014. |
| | PAGE 45/A-7.03 INDICATES AN INSULATION NOTE WAS ADDED |
| | BUT WHERE? PAGE 45/ A-7.03 ROOF DETAILS NOR THE ENERGY |
| | CALCULATIONS PROVIDE WHAT THE MINIMUM ROOF INSULATION |
| | IS THAT IS REQUIRED. NOTE THE ENERGY FORMS ARE NOT |
| | CORRECT, THE FRONT PAGE IS FOR A 1 STORY BUILDING, |
| | PAGES 33-34 BOTH SHOW A VALUE OF R-21.2 PLEASE PROVIDE |
| | HOW CODE COMPLIANCE WILL BE ACHIEVED. WHOLE BUILDING |
| | METHOD FL ENERGY 506.2.1. |
| | |
| | 22) SEMI ?COMPLIED. PAGE 53/ S1.01 ROOF ZONES 1, 2 & 3 |
| | THE PRESSURES ARE LOW FOR A MEAN ROOF HEIGHT OF 48 FT. |
| | WITH A EXPOSURE D COEFFICIENT. PAGE 47/ S 1.01 WALL |
| | PRESSURES OK ARE TAKEN AT THE PARAPET HEIGHT OF 54 FT. |
| | ELEVATION. |
| | |
| | 23) 2ND REQUEST. ARCHITECTS RESPONSE NOTE STATE SEE |
| | STRUCTURAL ENGINEERS NOTES FOR 22 & 23. THERE WAS NO |
| | RESPONSE TO COMMENT # 23. CELCORE LIGHTWEIGHT |
| | INSULATING CONCRETE NOA 13-0307.02 CIRCLE THE |
| | SUB-SYSTEM THAT IS TO BE USED ON THIS PROJECT AND THE |
| | ASSOCIATED PRESSURES. 107.2.1.3 ADDITIONAL INFORMATION |
| | IS REQUIRED. 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY |
| | THE CODE, THE CONSTRUCTION DOCUMENTS SHALL |
| | ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING |
| | SYSTEM, MATERIALS, FASTENING REQUIREMENTS, FLASHING |
| | REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE |
| | REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND |
| | INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND |
| | CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT |
| | BY AN ARCHITECT OR ENGINEER FOR THE SPECIFIC SITE MUST |
| | BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS. |
| | |
| | 24-27) DEFERRED SUBMITTALS. 107.3.4.2 DEFERRED |
| | SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| | BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | |
| | |
| | 28) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. FOR DIGITAL |
| | PLANS, YOU WILL NEED TO PRINT THE CODE SUMMARY SHEET |
| | AND FLOOR PLANS TO SUBMIT TO THE COUNTY FOR REVIEW. WE |
| | WILL NEED THE STAMPED SHEET AND THE RECEIPT. PLEASE |
| | CALL (561)233-5025 FOR MORE INFORMATION. |
| | |
| | 29) FOR DIGITAL REVIEW PLEASE SUBMIT A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |