| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY |
| | REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE |
| | (2009 EDITION WITH FLORIDA AMENDMENTS.) |
| | |
| | GENERAL: SUBMIT PLANS FOR PERMIT FOR ANY CONSTRUCTION |
| | TRAILERS/MODULAR BUILDINGS. STRUCTURES SHALL NOT BE |
| | OCCUPIED UNTIL A PERMIT HAS BEEN ISSUED AND A FIRE |
| | DEPARTMENT FINAL INSPECTION (#131) HAS BEEN PASSED. |
| | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, |
| | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: |
| | TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF |
| | COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE |
| | CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, |
| | TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. |
| | PER TABLE 4.2.1: |
| | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| | |
| | GENERAL: PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN |
| | TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE |
| | PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE |
| | PROVIDED AS REQUIRED BY THE AUTHORITY HAVING |
| | JURISDICTION. |
| | |
| | GENERAL: PROVIDE DRAWING NOTE INDICATING ALL |
| | CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE |
| | REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS |
| | SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | GENERAL: PROVIDE DRAWING NOTE INDICATING (PER NFPA 241 |
| | SECTION 8.7.4.2.4) PROVIDE A FIRE DEPARTMENT CONNECTION |
| | AND AT LEAST ONE APPROVED HOSE VALVE FOR ATTACHING FIRE |
| | DEPARTMENT HOSE SHALL BE PROVIDED AT EACH INTERMEDIATE |
| | LANDING OR FLOOR LEVEL IN THE EXIT STAIRWAY; THE |
| | STANDPIPES SHALL BE EXTENDED UP WITH EACH FLOOR AND |
| | SHALL BE SECURELY CAPPED AT THE TOP. |
| | |
| | GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| | EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| | BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| | ORDERED FROM WWW.KNOXBOX.COM. |
| | |
| | CIVIL: PROVIDE PROJECT FIRE FLOW CALCULATIONS PER NFPA |
| | 1 SECTION 18.4. |
| | |
| | CIVIL: ARE THE EXISTING STREETS, SIDEWALKS, STREET |
| | PARKING AREAS, ETC, BEING MODIFIED? |
| | |
| | SHEET C2: PROVIDE DRAWING NOTE INDICATING (PER NFPA 241 |
| | SECTION 8.7.2.3) WHERE UNDERGROUND WATER MAINS AND |
| | HYDRANTS ARE TO BE PROVIDED, THEY SHALL BE INSTALLED, |
| | COMPLETED, AND IN SERVICE PRIOR TO CONSTRUCTION WORK. |
| | |
| | SHEET C2: NO NEW OR EXISTING FIRE HYDRANTS SHOWN ON |
| | PONCE DELEON AVENUE. |
| | |
| | SHEET C2: FIRE DEPARTMENT CONNECTION LOCATED MORE THAN |
| | 100 FEET FROM A FIRE HYDRANT. |
| | |
| | SHEET C2: PER NFPA 24 SECTION 6.2.1, ALL CONNECTIONS TO |
| | PRIVATE FIRE SERVICE MAINS FOR FIRE PROTECTION SYSTEMS |
| | SHALL BE ARRANGED IN ACCORDANCE WITH ONE OF THE |
| | FOLLOWING SO THAT THEY CAN BE ISOLATED: |
| | (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 |
| | FEET FROM THE BUILDING. |
| | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST |
| | INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED |
| | CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE |
| | BUILDING AS THE HEIGHT OF THE WALL FACING THE POST |
| | INDICATOR VALVE. |
| | (2) A WALL POST INDICATOR VALVE |
| | (3) AN INDICATING VALVE IN A PIT, INSTALLED IN |
| | ACCORDANCE WITH SECTION 6.4 |
| | (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING |
| | VALVE NOT LESS THAN 40 FEET FROM THE BUILDING. |
| | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A |
| | BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE |
| | SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET |
| | BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF |
| | THE WALL FACING THE BACKFLOW PREVENTER. |
| | (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM |
| | ACCESSIBLE FROM THE EXTERIOR |
| | (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE |
| | ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE |
| | AUTHORITY HAVING JURISDICTION |
| | |
| | SHEET C2: PROVIDE SEPARATE TAP AND WATER MAIN FOR FIRE |
| | PROTECTION SERVICES. THE CURRENT LAYOUT SHOWS A |
| | COMBINATION DOMESTIC/FIRE WATER LINE. |
| | |
| | ARCHITECTURAL: PROVIDE ROOM NUMBERS FOR FIRST FLOOR |
| | ROOMS. |
| | |
| | ARCHITECTURAL: THE PLANS SEEM TO INDICATED SEPARATED |
| | MIXED USE OCCUPANCIES; HOWEVER, PER SECTION 6.1.14.1.2, |
| | WHERE EXIT ACCESS FROM AN OCCUPANCY TRAVERSES ANOTHER |
| | OCCUPANCY, THE MULTIPLE OCCUPANCY SHALL BE TREATED AS A |
| | MIXED OCCUPANCY (NON-SEPARATED USE). |
| | |
| | SHEET A1.00: REMOVE CODE REFERENCE "INTERNATIONAL FIRE |
| | CODE 2006 EDITION." |
| | |
| | SHEET A1.00: THE ASSEMBLY MULTIPURPOSE ROOM DOES NOT |
| | APPEAR TO BE FIGURED INTO THE OCCUPANT LOAD. |
| | |
| | SHEET A1.02: SHOW THE EXIT DISCHARGE PUBLIC WAY |
| | LOCATIONS. |
| | |
| | SHEET A1.02: RETAIL SPACES ARE USING AN OCCUPANT LOAD |
| | OF 200 SQ.FT. PER PERSON. MERCANTILE SHALL USE AN |
| | OCCUPANT LOAD FACTOR OF 30 SQ.FT. PER PERSON. |
| | |
| | SHEET A1.02 CLUBHOUSE EGRESS PLAN: ASSEMBLY OCCUPANCY |
| | DEAD END CORRIDOR GREATER THAN 20 FEET IN LENGTH |
| | CREATED ADJACENT TO CAFE. |
| | |
| | SHEET A1.02: SOME OF THE ASSEMBLY OCCUPANCY AREAS SUCH |
| | AS THE MULTIPURPOSE ROOM ARE NOT OCCUPIED WITH TABLES |
| | AND CHAIRS. THESE AREAS SHALL USE AN OCCUPANT LOAD |
| | FACTOR OTHER THAN 15 SQ.FT. PER PERSON. |
| | |
| | SHEET A1.02: POOL OCCUPANTS ARE BEING ROUTED BEHIND THE |
| | PARKING GARAGE. SHEET A2.00 INDICATES THERE ARE |
| | LANDSCAPE BUFFERS AND TRANSFORMERS AT THESE LOCATIONS. |
| | |
| | SHEET A1.02: SOME ASSEMBLY OCCUPANTS AND BUSINESS/MAIL |
| | CENTER OCCUPANTS SHOW EXIT ACCESS TRAVERSING THROUGH A |
| | STORAGE OCCUPANCY (PARKING GARAGE). |
| | |
| | SHEET A1.02: FIRE RATED WALLS DESIGNATIONS ARE NOT |
| | COORDINATED. SHEET A3.41 SHOWS STAIR ENCLOSURES WITH |
| | 3-HOUR RATINGS. |
| | |
| | SHEET A1.02: SOUTH GARAGE DOOR SWINGS AGAINST THE FLOW |
| | OF TRAFFIC. |
| | |
| | SHEET A1.02: COULD NOT LOCATE A DRAWING SCALE. |
| | |
| | SHEET A2.00: STAIR 2 EXIT DOOR DANGEROUSLY SWINGS OVER |
| | THE SIDEWALK FOR OCCUPANTS EGRESSING FROM THE POOL |
| | AREA. |
| | |
| | SHEET A2.00: STAIR 1 DISCHARGES INTO A CORRIDOR; |
| | HOWEVER, THIS SPACE INDICATES BIKE STORAGE. STORAGE IN |
| | THIS CORRIDOR WILL ALWAYS BE AN ISSUE THAT WILL NOT BE |
| | MANAGEABLE WITH JUST SIGNAGE OR SUPERVISION. ALSO |
| | 7.2.4.3.3 INDICATES ALL REQUIRED EXITS, OTHER THAN |
| | HORIZONTAL EXITS, SHALL DISCHARGE DIRECTLY TO THE |
| | OUTSIDE. |
| | |
| | SHEET A4.11: MAINTENANCE SHOP TO BE SEPARATED FROM |
| | ASSEMBLY OCCUPANCIES UTILIZING A 1-HOUR FIRE RATED |
| | BARRIER PER SECTION 12.3.2.1.2. |
| | |
| | GROUND FLOOR EXIT SIGNAGE: THE EXIT STRATEGY AND EXIT |
| | SIGN LOCATIONS NEED TO BE COORDINATED BETWEEN ARCH & |
| | ELEC. ROUTING INTERIOR OCCUPANTS TO THE EXTERIOR POOL |
| | DECK WILL NOT BE ACCEPTABLE. |
| | |
| | FIRE ALARM: THE OCCUPANT LOAD ON THE GROUND FLOOR |
| | ASSEMBLY AREA IS APPROACHING OR EXCEEDING 300 PERSONS. |
| | A THRESHOLD OF 300 PERSONS WILL REQUIRE VOICE |
| | EVACUATION FOR THIS LEVEL. |
| | |
| | FIRE SPRINKLER 1ST FLOOR: NO SPRINKLER PROTECTION |
| | PROVIDED IN MAINTENANCE SHOP AND ADJACENT CLOSET. |
| | |
| | FIRE SPRINKLER: NO SPRINKLER PROTECTION PROVIDED IN |
| | UPPER FLOOR TRASH ROOMS OR TRASH CHUTE. |
| | |
| | FIRE SPRINKLER: DISTANCES BETWEEN FIRE DEPARTMENT HOSE |
| | VALVES EXCEEDS 200 FEET PER NFPA 14. NO STANPIPE OR |
| | FIRE HOSE VALVES PROVIDED AT HORIZONTAL EXITS. |
| | |
| | DISCLAIMER: FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT |
| | ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED |
| | WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, |
| | ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE |
| | TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT |
| | THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A |
| | CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR |
| | VIOLATIONS OF THIS CODE. |
| | |