| 2015-01-20 15:10:56 | BUILDING PLAN REVIEW |
| | PERMIT: 14120431 |
| | ADD: 321 23RD ST. |
| | PCN:74-43-43-10-19-003-0143 |
| | CONT: PETROCCHI CONSTRUCTION |
| | TEL: (305)495-3745 |
| | |
| | PARK PALM BEACH MULTIFAMILY RESIDENTIAL |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE:MON. JAN. 20/2015 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION LIST THE ADDRESS OF 321 23RD |
| | ST./ 74-43-43-10-19-003-0143, THIS IS A SINGLE LOT, |
| | THIS WILL REQUIRE MORE THAN A UNITIY OF TITLE, THIS |
| | PROJECT WILL REQUIRE A REPLAT WITH A NEW PCN AND |
| | POSSIBLE ADDRESS CHANGE. |
| | |
| | 2) THIS PROJECT IS FOR A 4 STORY BUILDING THAT |
| | QUALIFIES AS A THRESHOLD BUILDING. FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| | (WRITTEN/ TYPED) SPECIAL INSPECTOR TO PERFORM |
| | STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT |
| | TO A STRUCTURAL INSPECTION PLAN PREPARED BY THE |
| | ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST |
| | BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| | ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| | THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| | INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| | PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| | ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| | DOCUMENTS. |
| | |
| | 2B) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | C) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | D) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO |
| | KEN CONRAD BY E-MAIL. KEN CONRAD: [email protected] |
| | |
| | E) NOTE NO ACTION IS REQUIRED, WE ARE E-MAILING YOU THE |
| | THRESHOLD INSPECTOR DOCUMENTS AND FORMS TO THIS E-MAIL |
| | ADDRESS; |
| | E-MAIL: [email protected] JAN. 20/2015 |
| | |
| | F) NOTE THIS IS A DIGITAL PLAN, AFTER PERMIT ISSUANCE, |
| | THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND |
| | BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO |
| | SETS OF PLANS WILL NEED TO BE PRINTED IN COLLOR, (1) |
| | FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP |
| | INSPECTORS. |
| | |
| | G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | H) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | |
| | 3) THE PERMIT VALUATION OF $8,500,000.00 IS LOW |
| | COMPARED TO THE CALCULATED VALUE FROM THE ICC BUILDING |
| | VALUATION DATA AUGUST 2014 USING THESE TABLES THE |
| | CALCULATED VALUE OF $9,855,203.00. |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 108.3* BUILDING PERMIT |
| | VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 4) PLEASE NOTE UNDER THE FOLDER SUPPORTING DOCUMENTS, |
| | MISSING WAS THE SOILS REPORT PREPARED BY ARDAMIN FILE |
| | 03-2310 02/06/04. 2010 FBC-B |
| | 1803.5.2 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, |
| | STRENGTH OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR |
| | WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED |
| | IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| | PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| | BE CONDUCTED. |
| | |
| | 5) PAGE 003/ A-1.00 CODE SUMMARY SHEET: |
| | 5A) BUILDING CODES THE FLORIDA BUUILDING CODE |
| | ACCESSIBILITY IS ITS OWN CODE BOOK NOT CHAPTER 11 AS IN |
| | THE ICC. |
| | 5B) OCCUPANCY CLASSIFICATION CHAPTER 3 & TABLE 3-A, |
| | THERE IS NO TABLE 3-A IN THE 2010 FBC-B. |
| | 5C) OCCUPANCY CLASSIFICATION LIST RETAIL TO BE COVERED |
| | UNDER 311.3 THE SAME AS OPEN GARAGES PLEASE SEE FBC-B |
| | 304.1. |
| | 5D) ALLOWABLE EXTERIOR OPENINGS CAN NOT BE VARIFIED, |
| | THE PROPERTY LINES HAVE NOT BEEN PROVIDED AND THE |
| | DISTANCE AWAY FROM THE PROPERTY LINE. FBC-B TABLE 602 |
| | EXTERIOR FIRE RATINGS AND TABLE 705.8 ALLOWABLE |
| | OPENINGS. |
| | |
| | 6) PAGE 004/ A-1.01 (NOTE K)/ 008- A-1.05 ON BOTH |
| | SHEETS THERE ARE NOTES TO COMPLY WITH 1207.2 AIR-BORNE |
| | SOUND AND 1207.3 STRUCTURE BORNE SOUND. IN NEITHER CASE |
| | HAS TESTING REPORTS SUBMITTED PROVIDING CODE |
| | COMPLIANCE. PAGE 008 HAD A NOT OF REPORT NGC7005033 BUT |
| | NOT SUBMITTED. |
| | |
| | 7) PAGE 005/ A-1.02 OCCUPANCY & EGRESS PLAN / FIRE WALL |
| | SEPARATION. |
| | 7A)GROUND FLOOR EGRESS PLAN. BLDG. AREA (2) THE TYPICAL |
| | FLOOR PLAN SOUTH VERTICAL EXIT STAIR (2 HOUR RATED |
| | STAIR ENCLOSURE EMPTIES INTO A EXIT PASAGEWAY (1023.1) |
| | NOT A EGRESS CORRIDOR. WHEN YOU ENTER A VERTICAL EXIT, |
| | YOU HAVE TO CONTINUE THAT LEVEL OF PROTECTION THROUGH |
| | TO THE EXIT DISCHARGE. 1023.5 OPENINGS AND |
| | PENETRATIONS.EXCEPT AS PERMITTED IN SECTION 402.4.6, |
| | OPENINGS IN EXIT PASSAGEWAYS OTHER THAN EXTERIOR |
| | OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT |
| | ACCESS TO THE EXIT PASSAGEWAY FROM NORMALLY OCCUPIED |
| | SPACES AND FOR EGRESS FROM THE EXIT PASSAGEWAY. |
| | WHERE AN EXIT ENCLOSURE IS EXTENDED TO AN EXIT |
| | DISCHARGE OR A PUBLIC WAY BY AN EXIT PASSAGEWAY, THE |
| | EXIT PASSAGEWAY SHALL ALSO COMPLY WITH SECTION |
| | 1022.2.1. |
| | ELEVATORS SHALL NOT OPEN INTO AN EXIT PASSAGEWAY. |
| | |
| | 402.4.6 SERVICE AREAS FRONTING ON EXIT PASSAGEWAYS. |
| | MECHANICAL ROOMS, ELECTRICAL ROOMS, BUILDING SERVICE |
| | AREAS AND SERVICE ELEVATORS ARE PERMITTED TO OPEN |
| | DIRECTLY INTO EXIT PASSAGEWAYS, PROVIDED THE EXIT |
| | PASSAGEWAY IS SEPARATED FROM SUCH ROOMS WITH NOT LESS |
| | THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE |
| | WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED |
| | IN ACCORDANCE WITH SECTION 712, OR BOTH. THE MINIMUM |
| | FIRE PROTECTION RATING OF OPENINGS IN THE FIRE BARRIERS |
| | SHALL BE 1 HOUR. |
| | SUCH ROOMS OR AREAS SHALL BE PROTECTED BY AN APPROVED |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH SECTION 903; HOWEVER, THE EXCEPTION IN NFPA 13, |
| | STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, |
| | THAT PERMIT THE OMISSION OF SPRINKLERS FROM SUCH ROOMS |
| | SHALL NOT BE PERMITTED. |
| | |
| | PLEASE ALSO NOTE THAT WITH OPENING 208 BEING GATE THIS |
| | WILL BE REQUIRED TO BE THE EXIT DOOR WITH CLOSER, THE |
| | DOOR WITH A CLOSER AND LATCH WILL REQUIRE ACLEAR FLOOR |
| | SPACE SEE ACCESS. CODE FIGURE 404.2.4.1 (C). |
| | |
| | 7B) GROUND FLOOR EGRESS PLAN. THE INTERIOR SIDE OF THE |
| | LOT LINE IS NOT SHOWN NOR IS THE WEST PROPERTY LINE NOT |
| | SHOWN. THE POOL AND SUN DECK SHOWS (2) MEANS OF EGRESS |
| | FROM THE POOL BUT THE PLANS DO NOT SHOW HOW EGRESS TO |
| | THE PUBLIC WAY WILL BE COMPLIED WITH. PLEASE PROVIDE |
| | THE DISTANCE FROM THE BUILDING TO THE LOT LINE. THE |
| | WEST VERTICAL EXIT ALSO EMPTIES TO THE SIDE CLOSEST TO |
| | THE PROPERTY LINE PLEASE PROVIDE COMPLIANCE WITH FBC-B |
| | 1027.2-1027.6. |
| | |
| | 7C) CLUBHOUSE EGRESS PLAN. PLEASE NOTE THERE ARE |
| | VARIOUS ROOMS THAT ARE NOT IDENTIFIED ON THIS PLAN, |
| | USE, SQ. FOOTAGE AND OCCUPANCY LOADS CAN NOT BE |
| | CONFIRMED. 107.3.5.1 MINIUMUM CRITERIA FOR COMMERCIAL |
| | BUILDING PLAN REVIEW. |
| | |
| | 7D) THE FITNESS CENTER SHOWS THE MEANS OF EGRESS GOING |
| | THROUGH INTO THE 3 HR RATED VERTICAL EXIT, SHEET A-6.01 |
| | STAIR PLAN # 2 IST FLOOR, PLEASE |
| | PROVIDE THE HEAD ROOM FROM THE 1ST FLOOR SLAB TO THE |
| | MID-LANDING AS PART OF A MEANS OF EGRESS MINIMUM HEAD |
| | ROOM FBC-B 1208.2. 1006.3.9 |
| | SIGNS INSTALLED AS PROJECTIONS FROM A WALL OR CEILING |
| | WITHIN THE MEANS OF EGRESS SHALL PROVIDE VERTICAL |
| | CLEARANCE NO LESS THAN 80 INCHES (2134 MM) FROM THE |
| | WALKING SURFACE. |
| | |
| | 7E) PLEASE REVIEW RETAIL SUITES 200, 300 & 400 ALL ARE |
| | FIGURED AT 200 FT/ OCC. 1ST FLOOR RETAIL IS FIRURED AT |
| | 30 SQ. FT./ OCC. FBC-B TABLE 1004.1.1. |
| | |
| | 7F) THE MULTI-PURPOSE ROOM IS MISSING FROM THE 1ST |
| | FLOOR OCCUPANCY LOAD TABLE FBC-B TABLE 1004.1.1. |
| | |
| | 7G) THE CLUBHOUSE/ LEASING ROOM IS NOT DEFINED AS TO |
| | LOCATION SHEET A-4.11 DOES NOT REFERANCE SUCH AREA. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 7H) THE RETAIL SPACE WITH 1050 SQ. FT. /30= 52 |
| | OCCUPANTS, DOOR 103 WILL NEED TO SWING IN THE DIRECTION |
| | OF EGRESS TRAVEL. FBC-B 1008.1.2. |
| | |
| | 8) PAGE 13/ A-2.00 ARCHITECTURAL SITE REFERENCE PLAN: |
| | 8A) IT APPEARS THERE IS A DISCREPANCY IN THE 1ST FLOOR |
| | UNIT DESIGN, THE GRAPH SHOWS UNIT TYPES ON THE FIRST |
| | FLOOR AS RESIDENTIAL UNITS WHERE AS THE LOWER RIGHT |
| | PORTION OF THE PAGE SHOWS (3) RETAIL UNITS. 107.2.1.3 |
| | ADDITIONAL INFORMATION REQUIRED, DISCREPANCY IN PLANS. |
| | |
| | 9) PAGE 42/ A-6.20 : |
| | 9A) TRASH ROOM 2ND THROUGH THE 4TH FLOOR SHOW THE WHOLE |
| | OF THE TRASH ROOM/ ENCLOSRE AS BEING WITHIN THE 2 HOUR |
| | RATING FOR A SHAFT. DETAIL # 6 LABELS THE REFUSE CHUTE |
| | ITSELF AS THE SHAFT, THIS IS JUST THE TRASH CHUTE |
| | ITSELF. |
| | |
| | FBC-B 708.13.1 REFUSE AND LAUNDRY CHUTE ENCLOSURES. A |
| | SHAFT ENCLOSURE CONTAINING A REFUSE OR LAUNDRY CHUTE |
| | SHALL NOT BE USED FOR ANY OTHER PURPOSE AND SHALL BE |
| | ENCLOSED IN ACCORDANCE WITH SECTION 708.4. OPENINGS |
| | INTO THE SHAFT, INCLUDING THOSE FROM ACCESS ROOMS AND |
| | TERMINATION ROOMS, SHALL BE PROTECTED IN ACCORDANCE |
| | WITH THIS SECTION AND SECTION 715. OPENINGS INTO CHUTES |
| | SHALL NOT BE LOCATED IN CORRIDORS. DOORS SHALL BE SELF- |
| | OR AUTOMATIC-CLOSING UPON THE ACTUATION OF A SMOKE |
| | DETECTOR IN ACCORDANCE WITH SECTION 715.4.8.3, EXCEPT |
| | THAT HEAT-ACTIVATED CLOSING DEVICES SHALL BE PERMITTED |
| | BETWEEN THE SHAFT AND THE TERMINATION ROOM. |
| | |
| | 9B) WITH THE CORRECTED SHAFT THE ACCESS ROOM THAT LEADS |
| | FROM THE CORRIDOR TO THE REFUSE SHUTE, THIS AREA WILL |
| | NEED TO COMPLY WITH 708.13.3 A 1 HOUR FIRE BARRIER WITH |
| | 3/4 HR DOOR SELF CLOSING OR AUTOMATIC CLOSING UPON THE |
| | DETECTION OF SMOKE IN ACCORDANCE WITH SECTION |
| | 715.4.8.3. |
| | |
| | 9C) DETAIL # 6 FOR THE TRASH COLLECTION ROOM FAILS TO |
| | PROVIDE A FIRE RATING AT THE BOTTOM OF THE SHAFT, (2ND |
| | FLOOR LEVEL). SEE FBC-B 708.11 ENCLOSURE AT THE BOTTOM. |
| | NOTE THAT THE 3 HOUR FIRE RATED WALLS WOULD MEET THE |
| | FIRE RATINGS REQUIRED, ONLY 2 HRS REQUIRED BUT THE |
| | OPENING PROTECTIVES WOULD THEN NEED TO BE 1 1/2 HOUR |
| | FIRE RATING PER TABLE 715.4. |
| | |
| | 10) PAGE 40 - 41/ A-8.10- A-8.11 NEITHER ELEVATOR SHOWS |
| | COMPLIANCE WITH THE AMBULANCE STRETCHER |
| | REQUIREMENTSFBC-B 3002.4. THE ELEVATOR CAR SHALL BE OF |
| | SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE AN AMBULANCE |
| | STRETCHER 24 INCHES BY 76 INCHES (610 MM BY 1950 MM) |
| | WITH NOT LESS THAN 5-INCH (127 MM) RADIUS CORNERS, IN |
| | THE HORIZONTAL, OPEN POSITION AND SHALL BE IDENTIFIED |
| | BY THE INTERNATIONAL SYMBOL FOR EMERGENCY MEDICAL |
| | SERVICES (STAR OF LIFE). THE SYMBOL SHALL NOT BE LESS |
| | THAN 3 INCHES (76 MM) HIGH AND SHALL BE PLACED INSIDE |
| | ON BOTH SIDES OF THE HOISTWAY DOOR FRAME. |
| | |
| | 11) PAGE 25 / A-4.12 THIS COMMENT IS COMMON FOR THE 2ND |
| | FLOOR THRU 4TH FLOOR. DETAIL # 4 DOOR # 209 ON THE DOOR |
| | SCHEDULE IS INDICATED AS A 45 MINUTE REATED DOOR, |
| | PLEASE REVIEW FBC-B 509.5 A FIRE-RESISTANCE RATING OF |
| | NOT LESS THAN 3 HOURS AND THE FLOOR AREA IS SUBDIVIDED |
| | BY 2-HOUR FIRE-RESISTANCE-RATED FIRE WALLS INTO AREAS |
| | OF NOT MORE THAN 3,000 SQUARE FEET . OPENING |
| | PROTECTIVES 715.4 2HR FIRE WALL/ 1 1/2 OPENING |
| | PROTECTIVES. |
| | |
| | 12) PAGE 16/ A-3.10. THIS SHEET IS ACTUALLY A-3.41 , |
| | SHOULD BE PAGE 23, OUT OF ORDER OF THE INDEX.THE NEXT6 |
| | SHEETS ARE NOW OUT OF ORDER TO THE INDEX OF SHEETS. |
| | |
| | 13 PAGE 17/ A-3.10 THE EXIT ACCESS WALL COMMON TO THIS |
| | UNIT HAS A WALL TAG # 21 THIS WALL DOES NOT INDICATE |
| | COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION ASSEMBLIES |
| | FOR PIPING; ELECTRICAL DEVICES; RECESSED CABINETS; |
| | BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR EXHAUST |
| | DUCTS SHALL BE SEALED, LINED, INSULATED OR OTHERWISE |
| | TREATED TO MAINTAIN THE REQUIRED RATINGS. THIS |
| | REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT ENTRANCE |
| | DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT FITTING TO |
| | THE FRAME AND SILL. |
| | |
| | 13) PAGE 18/ A-3.11 THE EXIT ACCESS WALL COMMON TO THIS |
| | UNIT HAS A WALL TAG # 21 THIS WALL DOES NOT INDICATE |
| | COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION ASSEMBLIES |
| | FOR PIPING; ELECTRICAL DEVICES; RECESSED CABINETS; |
| | BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR EXHAUST |
| | DUCTS SHALL BE SEALED, LINED, INSULATED OR OTHERWISE |
| | TREATED TO MAINTAIN THE REQUIRED RATINGS. THIS |
| | REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT ENTRANCE |
| | DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT FITTING TO |
| | THE FRAME AND SILL. |
| | |
| | 14A) PAGE 19/ A3.12 THE BATHROOM WALL NEXT TO THE |
| | GARDEN TUB DOES NOT HAVE A WALL IDENTIFICATION TAG, |
| | SHOW COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| | |
| | 14B) PAGE 19/ A3.12 THE KITCHEN WALL NEXT TO THE SINK |
| | HAS A WALL IDENTIFICATION TAG OF 33, THIS WALL DOES NOT |
| | HAVE ANY SOUND RATING, SHOW COMPLIANCE WITH FBC-B |
| | 1207.2 AIR-BORNE SOUND. |
| | |
| | 15) PAGE 20/ A3.20 THE EXIT ACCESS WALL COMMON TO THIS |
| | UNIT HAS A WALL TAG # 21 THIS WALL DOES NOT INDICATE |
| | COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| | |
| | 16A) A3.21 THE EXIT ACCESS WALL COMMON TO THIS UNIT HAS |
| | A WALL TAG # 21 THIS WALL DOES NOT INDICATE COMPLIANCE |
| | WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| | |
| | 16B) MASTER BATH GARDEN TUB WALL THAT BACKS UP TO |
| | SHAFT, NO SHAFT IS SHOWN WALL TAG# 30 , WALL TYPE 30 |
| | DOES NOT PROVIDE COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE |
| | SOUND. |
| | |
| | 17) A3.22 WALL TAGS 33 & 35, BOTH OF THESE WALLS DO NOT |
| | PROVIDE COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| | |
| | 18) PAGE 25, A4.12 HVAC SHAFT, THIS COMMENT STANDS FOR |
| | ALL FLOORS, WALL TAG # 30 DOES NOT SHOW COMPLIANCE WITH |
| | FBC-B 1207.2 AIR-BORNE SOUND. |
| | |
| | 19) PAGE 43/ A7.01 GUARD RAILINGS FOR BALCONIES. |
| | DETAILS 3, 10 & 11 SHOW GUARD RAIL ATTACHMENT TO THE |
| | STRUCTURE WITH EXSPANSION BOLTS. THERE IS A NOTE ON THE |
| | PLANS THAT THE CONNECTION DETAILS ARE TO BE DESIGNED BY |
| | A ENGINEER LICENSED IN THE STATE OF FLORIDA. WHAT THE |
| | DESIGNER OF RECORD FAILED TO PROVIDE IS THE |
| | REQUIREMENTS OF THE CODE FOR THE ENGINEER TO FOLLOW. |
| | 2010 FBC-B 1607.7.1 HANDRAILS AND GUARDS. |
| | 1607.7.1.1 CONCENTRATED LOAD. |
| | 1607.7.1.2 COMPONENTS. |
| | |
| | 20) PAGE 44/ A-7.02 & S-7.04 VARIOUS DETAILS AND DESIGN |
| | ARE SHOWN FOR CANOPY AND AWNINGS, THERE IS NO |
| | ATTACHMENT INFORMATION NOR IS THERE A PROPOSED WIND |
| | DESIGN PARAMETERS FOR THE SPECIALTY ENGINEER TO DESIGN. |
| | FBC-B 3105. |
| | |
| | 21) PAGE 45/ A-7.03 ROOF DETAILS NOR THE ENERGY |
| | CALCULATIONS PROVIDE WHAT THE MINIMUM ROOF INSULATION |
| | IS THAT IS REQUIRED. NOTE THE ENERGY FORMS ARE NOT |
| | CORRECT, THE FRONT PAGE IS FOR A 1 STORY BUILDING, |
| | PAGES 33-34 BOTH SHOW A VALUE OF R-21.2 PLEASE PROVIDE |
| | HOW CODE COMPLIANCE WITLL BE ACHIEVED. WHOLE BUILDING |
| | METHOD FL ENERGY 506.2.1. |
| | |
| | 22) PAGE 49/ S1.01 THE GENERAL NOTE # 3 PROVIDES THE |
| | WIND DESIGN CRITERIA BUT DOES NOT EXPLAIN MORE THAN |
| | COMPONENTS AND CLADDING (VASD) +54.14/ -70.75 PSF. THIS |
| | PRESSURE DOES NOT INDICATE FOR WHAT SQ. FT. THIS |
| | DESIGNED FOR, NOR DOES IT PROVIDE FOR WHAT ZONE, ROOF |
| | OR WALL. |
| | PLEASE PROVIDE A VULT AND VASD SCHEDULE FOR ZONES, 1, |
| | 2, 3, 4 & 5 FOR 10 SQ. FT., 20 SQ. FT, 50 SQ. FT. & 100 |
| | SQ. FT. THE TABLES IN THE CODE BOOKS ARE NOT GOOD ABOVE |
| | 60 FT. FBC-B TABLE 1609.6.2./ COMPONENTS AND CLADDING |
| | 1709.6.4.4.1. |
| | NOTE WITHOUT THIS INFORMATION THE SUBMITTED PRODUCT |
| | APPROVALS CAN NOT BE REVIEWED FOR CODE COMPLIANCE. |
| | |
| | 23) CELCORE LIGHTWEIGHT INSULATING CONCRETE NOA |
| | 13-0307.02 CIRCLE THE SUS-SYSTEM THAT IS TO BE USED ON |
| | THIS PROJECT AND THE ASSOCIATED PRESSURES. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.2 FOR ROOF |
| | ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION |
| | DOCUMENTS SHALL |
| | ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING |
| | SYSTEM, MATERIALS, FASTENING REQUIREMENTS, FLASHING |
| | REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE |
| | REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND |
| | INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND |
| | CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT |
| | BY AN ARCHITECT OR ENGINEER FOR THE SPECIFIC SITE MUST |
| | BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS. |
| | |
| | 24) JOHNS MANVILLE NOA 13-0129.20 MODIFIED OVER |
| | CONCRETE DECK, CIRCLE WHICH SUB-SYSTEM IS TO BE |
| | INSTALLED ON THIS PROJECT, PLEASE NOTE THE DESIGN |
| | PRESSURES AND IF LIMITATION 7 OR 9 APPLIES. LIMITATION |
| | 7 MAY REQUIRE CALCULATIONS FROM A DESIGN PROFESSIONAL. |
| | |
| | 25) ALL GLAZED OPENINGS BOTH WINDOWS AND DOORS AND |
| | MULLIONS CIRCLE THE TYPE OF GLAZING TO BE INSTALLED, |
| | WIDTH, HEIGHT AND ASSOCATED PRESSURES FOR REVIEW. |
| | 107.2.1.3 |
| | |
| | 26) NYSTROM ROOF HATCH NOA 12-0320.30 GOOD FOR +/- |
| | 100PSF VASD. SHEET A-6.00 IT APPEARS THERE IS OVER A |
| | 3'-0" PARAPET ELIMINATING ZONE 3, THIS UNITWILL NEED TO |
| | MEET THE ROOF ZONE PRESSURES FOR ROOF ZONE 3 WILL BE |
| | REVIEWED ONCE PRESSURES ARE PROVIED. |
| | |
| | 27A) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 27B) THE PRODUCT APPROVALS THAT MAKE UP THE ENVELOPE OF |
| | THE BUILDING IF THE CONTRACTOR OR DESIGN PROFESSIONAL |
| | ELECT CAN BE A NO FEE DEFERRAL. THIS DOES ALLOW THE |
| | CONTRACTOR TO BID OUT THE PROJECT AND SUBMIT THE ACTUAL |
| | PRODUCTS THAT WILL BE INSTALLED ON THEIRE PROJECT. A |
| | WRITTEN RESPONCE WILL BE REQUIRED IF THIS OPTION IS |
| | DESIRED. |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE |
| | BEEN APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | 28) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. FOR DIGITAL |
| | PLANS, YOU WILL NEED TO PRINT THE CODE SUMMARY SHEET |
| | AND FLOOR PLANS TO SUBMIT TO THE COUNTY FOR REVIEW.WE |
| | WILL NEED THE STAMPED SHEET AND THE RECEIPT. PLEASE |
| | CALL (561)233-5025 FOR MORE INFORMATION. |
| | |
| | 29) FOR DIGITAL REVIEW PLEASE SUBMIT A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | |