| Plan Review Notes For Permit 14120428 |
| Permit Number |
14120428 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-01-05 17:23:36 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | ELECTRICAL | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS. | | | | | | 2) FBC 107.3.5.3 - SUBMIT A PANEL SCHEDULE. | | | | | | 3) NEC 110.9 - SPECIFY THE A.I.C. RATING OF THE | | | ELECTRICAL EQUIPMENT ON THE PLANS. | | | | | | 4) SHOW THE LOCATION OF THE EXISTING SERVICE THAT WILL | | | BE PROVIDING THE ELECTRIC FOR THE NEW WORK ON THE | | | PLANS.FBC107.2.1 | | | | | | 5) SHOW THE LOCATION OF THE PANEL THAT WILL BE | | | SUPPLYING THE NEW CARPORT AND SHED. FBC107.2.1 | | | | | | 6) PROVIDE AN ELECTRIC SERVICE RISER WITH WIRE SIZES, | | | CONDUIT DETAIL AND GROUNDING DETAIL. FBC 107.3.5.3 | | | | | | 7) NEC 210.70 (2) - PROVIDE AT LEAST ONE WALL SWITCH | | | CONTROLLED LIGHTING OUTLET TO PROVIDE ILLUMINATION ON | | | THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXISTS WITH | | | GRADE LEVEL ACCESS. | | | | | | - IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE | | | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER | | | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN | | | ADDRESSED. |
|