| 2015-01-05 16:52:14 | PLAN REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) FLORIDA STATUTES 471 AND FAC 61G15-23.002 REQUIRE |
| | THE ENGINEER TO SIGN BY HAND THE LICENSEE'S HANDWRITTEN |
| | SIGNATURE (FACSIMILES ARE NOT ACCEPTABLE) AND SEAL ON |
| | DOCUMENTS ARE SUBMITTED FOR PUBLIC RECORD. THE PLANS |
| | FROM WERE SUBMITTED APPEAR TO HAVE A SIGNATURE THAT HAS |
| | BEEN COPIED. |
| | |
| | 2) THE MASONRY AND ELECTRICAL NOTES ON SHEET 1 DO NOT |
| | APPLY TO THIS PROJECT. FBC 107.2.1 |
| | |
| | 3) SUBMIT TWO COPIES OF A SURVEY AS REQUESTED BY |
| | ZONING. FBC 107.2.1.4 |
| | |
| | 4) PROVIDE A NORTH DIRECTIONAL ARROW ON THE SITE PLAN. |
| | FBC 107.2.1 |
| | |
| | 5) THE WRONG EDITION OF NEC IS SITED ON SHEET 1. |
| | CHAPTER 43 OF THE 2010 FLORIDA BUILDING CODE REFERENCES |
| | NEC 2008. |
| | |
| | 6) SPECIFY THE REQUIRED COMPONENT AND CLADDING |
| | PRESSURES ON THE PLANS. FBC-R 301.2.1 |
| | |
| | 7) SHOW COMPLIANCE WITH R317.1 PROTECTION OF WOOD AND |
| | WOOD BASED PRODUCTS FROM DECAY SHALL BE PROVIDED IN THE |
| | FOLLOWING LOCATIONS BY THE USE OF NATURALLY DURABLE |
| | WOOD OR WOOD THAT IS PRESERVATIVE-TREATED IN ACCORDANCE |
| | WITH AWPA U1 FOR THE SPECIES, PRODUCT, PRESERVATIVE AND |
| | END USE. PRESERVATIVES SHALL BE LISTED IN SECTION 4 OF |
| | AWPA U1. |
| | |
| | -1. WOOD JOISTS OR THE BOTTOM OF A WOOD STRUCTURAL |
| | FLOOR WHEN CLOSER THAN 18 INCHES (457 MM) OR WOOD |
| | GIRDERS WHEN CLOSER THAN 12 INCHES (305 MM) TO THE |
| | EXPOSED GROUND IN CRAWL SPACES OR UNEXCAVATED AREA |
| | LOCATED WITHIN THE PERIPHERY OF THE BUILDING |
| | FOUNDATION. |
| | -5. WOOD SIDING, SHEATHING AND WALL FRAMING ON THE |
| | EXTERIOR OF A BUILDING HAVING A CLEARANCE OF LESS THAN |
| | 6 INCHES (152 MM) FROM THE GROUND OR LESS THAN 2 INCHES |
| | (51 MM) MEASURED VERTICALLY FROM CONCRETE STEPS, PORCH |
| | SLABS, PATIO SLABS, AND SIMILAR HORIZONTAL SURFACES |
| | EXPOSED TO THE WEATHER. |
| | |
| | 8) SHOW COMPLIANCE WITH R318.1 TERMITE PROTECTION. |
| | TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED |
| | TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES, |
| | BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR |
| | OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED |
| | FOR USE AS A PREVENTATIVE TREATMENT TO NEW |
| | CONSTRUCTION. SEE SECTION 202, REGISTERED TERMITICIDE. |
| | UPON COMPLETION OF THE APPLICATION OF THE TERMITE |
| | PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL |
| | BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED |
| | PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING |
| | STATEMENT: ?THE BUILDING HAS RECEIVED A COMPLETE |
| | TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES. |
| | TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS |
| | ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE |
| | AND CONSUMER SERVICES.? |
| | |
| | 9) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | EXTERIOR DOORS, WINDOWS, ROOFING MATERIALS AND |
| | STRUCTURAL CONNECTORS THAT ARE SPECIFIED ON THE PLANS. |
| | DCA RULE 9N-3 |
| | |
| | 10) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| | THE PROJECT. FBC 107.3.4.1 |
| | |
| | IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE |
| | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER |
| | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN |
| | ADDRESSED. |
| | |
| | |
| | |