| 2015-03-07 17:38:04 | ****PROVISO**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | CONTRACTOR HAS ELECTED NOT TO SUBMIT FIXTURE CALCS | | | DURING PLAN REVIEW. | | | | | | CONTRACTOR TO PROVIDE FIXTURE CALCS AT INSPECTION. | | | SUBJECT TO FIELD INSPECTOR'S DISCRETION, A REVISION | | | (WITH FEES) MAY BE REQUIRED. IF THIS IS NOT ACCEPTABLE | | | TO THE CONTRACTOR, HE SHOULD NOT PICK UP THE PERMIT AND | | | SHOULD RESUBMIT WITH FIXTURE CALCS. | | | | | | PER ENGINEER'S CALCS: | | | | | | FIXTURE TO BE MOUNTED AT 25' ABOVE BOTTOM OF BASE PLATE | | | OR TRANSFORMER PLATE | | | FIXTURE EPA NOT TO EXCEED 2.4 SF | | | FIXTURE WEIGHT NOT TO EXCEED 54# | | | | | | | | | |
|