| 2014-12-30 16:26:24 | 12/30/2014 |
| | PROJECT: SITE LIGHTING AUTOZONE |
| | PERMIT#: 14120391 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET E-1 IS PART OF APPLICATION #14110892 FOR THE |
| | RENNOVATION OF THE AUTOZONE STORE AND HAS NO BEARING ON |
| | THE INSTALLATION OF THE SITE LIGHTING. |
| | |
| | 2) SHEET E-4 IS ALSO PART OF APPLICATION #14110892 FOR |
| | THE RENNOVATION OF THE AUTOZONE STORE AND HAS NO |
| | BEARING ON THE INSTALLATION OF THE SITE LIGHTING. |
| | |
| | 3) IT APPEARS THERE IS A NEW SITE LIGHTING CIRCUIT |
| | PROPOSED FROM PANEL A" PROVIDE A PANEL SCHEDULE FOR |
| | PANEL A. |
| | |
| | 4) THERE IS A SYMBOL INDICATED FOR WALL PACKS ON THE |
| | EXTERIOR OF THE NEW AUTOZONE ADITION. IS THIS A PART OF |
| | THE SITE LIGHTING SCOPE? IF SO INCLUDE THE CIRCUITRY |
| | THAT FEEDS THEM. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |