| Plan Review Notes For Permit 14120368 |
| Permit Number |
14120368 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-12-11 07:50:41 | BUILDING PLAN REVIEW | | | PERMIT: 14120368 | | | ADD: 600 S. DIXIE HWY SUITE # 705 | | | CONT: MOSS DEVCO INC. | | | TEL: (561)644-0302 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: THURS. DEC. 11/2014 | | | ACTION: DENIED | | | | | | 1) THE SUBMITTED PRODUCT ECO-ULTRA QUIET SOUND | | | TRANSMITION CLASS/ RATING WAS TESTED TO THE WRONG ASTM, | | | IT WAS TESTED TO ASTM E90-04. PLEASE REVIEW: 2010 FBC-B | | | 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES | | | BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A | | | PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE | | | AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS | | | THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE | | | WITH ASTM E 492. | | | | | | THE CORRECT FLAME SPREAD TEST WAS PROVIDED. ASTM E84. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|