| Date |
Text |
| 2014-12-11 13:36:26 | PERMIT #14120367 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PROVISO: |
| | |
| | 1) WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT |
| | SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED |
| | AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE |
| | MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM |
| | SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD |
| | INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY |
| | BE NEEDED. |
| | |
| | 2) ALL TENANT SPACES IN THIS BUILDING MUST BE TIED INTO |
| | THE MASTER FIRE ALARM PANEL FOR THE BUILDING. EACH |
| | TENANT SPACE WILL BE INTERCONNECTED AND UPON ACTIVATION |
| | OF AN ALARM IN ANY ONE SPACE, ALL SPACES WILL HAVE |
| | THEIR NOTIFICATION DEVICES ACTIVATE. AN FACP IN A |
| | TENANT SPACES WILL HAVE THE "RESET" AND "SILENCE" |
| | FUNCTIONS DEACTIVATED. RESET AND SILENCE OF AN ALARM IS |
| | LIMITED TO THE MASTER PANEL FOR THE BUILDING AND MAY |
| | ONLY BE DONE BY A LICENSED FIRE ALARM TECHNICIAN. |
| | SHOULD IT BE FOUND THAT TENANTS ARE ACCESSING THE |
| | PANELS IN THE TENANT SPACES AND/OR USING THE "RESET" OR |
| | "SILENCE" FUNCTIONS, THE OFFICE OF THE FIRE MARSHAL MAY |
| | REQUIRE THAT THE TENANT FACP BE REMOVED. |
| | |
| | 3) FIRE ALARM CIRCUIT BREAKER TO BE MARKED IN RED AND |
| | IDENTIFIED AS "FIRE ALARM." PROVIDE CIRCUIT BREAKER |
| | LOCK FOR DEDICATED BRANCH CIRCUIT. |
| | |
| | 4) PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL |
| | INITIATE A GENERAL FIRE ALARM CONDITION. |
| | |
| | 5) A CERTIFICATE OF COMPLETION AND A THIRD PARTY |
| | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL |
| | BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION. |
| | |
| | SUE ELLEN CALDERON |
| | FIRE INSPECTOR & INVESTIGATOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 644-7326 |
| | |