Notes
Date Text
2014-12-19 06:24:421) A DRINKING FOUNTAIN IS REQUIRED PER 2010 FL.
 PLUMBING CODE TABLE 403.1 AND FOOTNOTE (E).A MINIMUM OF
 TWO DRINKING FOUNTAINS SHALL BE PROVIDED PER THE 2010
 FL. ACCESSIBILITY CODE SEC.211.2.
 2) SHT. A4.1 - ELEVATIONS # 2 & #3 - THE GRAB BAR SHALL
 BE MOUNTED AT 36" TO THE TOP OF THE BAR, NOT TO THE
 CENTER AS SHOWN.RESTROOM NOTES SPECIFY 36" TO TOP. 2010
 FL.ACCESSIBILITY CODE SEC.609.4.
 3) SHT. A4.1 - THE REAR GRAB BAR SHALL BE LOCATED IN
 ACCORDANCE WITH THE 2010 FL. ACCESSIBILITY CODE
 SEC.604.5.2.
 4) SHT. A4.1 - DETAIL 3 SHOWS A VERTICAL GRAB BAR. GRAB
 BARS SHALL BE INSTALLED IN THE HORIZONTAL POSITION PER
 THE FL. ACCESSIBILITY CODE SEC. 609.4.
 5) SHT. A4.1 - DETAIL #4- THE TOILET PAPER DISPENSER
 SHALL BE LOCATED 7 INCHES MINIMUM AND 9 INCHES MAXIMUM
 IN FRONT OF THE WATER CLOSET MESURED TO THE CENTERLINE
 OF THE DISPENSER.FAC SEC.604.7.
 6) THE FLUSH HANDLE SHALL BE LOCATED ON THE OPEN SIDE
 OF THE WATER CLOSET PER THE 2010 FAC SEC.604.6.
 7) SHT.A4.1 - DETAILS # 2 & #3 REFER TO SHT A2.3. THERE
 IS NO SUCH SHEET IN THIS SET OF PLANS.
  