2014-12-13 09:56:29BUILDING PLAN REVIEW
 PERMIT: 14120353
 ADD: 2611 MERCER AVENUE
 CONT: ELEITE DRYWALL
 TEL: (561)746-3551
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. DEC. 13/ 2014
 ACTION: DENIED
  
 1) SHEET A2.1 PROVIDES A FLOOR LAYOUT OF WHAT THE
 PROPOSED CONFIGURATION OF WALLS WILL LOOK LIKE BUT
 THERE IS NO PROPOSED INTERIOR DEMOLITION PLANS OF WHAT
 THE SITE LOOKS LIKE BEFORE THE START OF DENOLITION.
 NOTE THERE IS A INTERIOR DEMO PLAN, PLEASE SUBMIT AS
 PART OF PERMIT PACKAGE FOR REFERANCE ONLY.2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.L. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 2) COVERSHEET C1 INDICATES THIS IS A BUSINESS
 OCCUPANCY. IT APPEARS TO BE A MIXED OCCUPANCY SINCE THE
 WAREHOUSE APPEARS TO BE ABOUT 40% OF THE OVER ALL SQ.
 FOOTAGE OF THE BUILDING. PLEASE PROVIDE IF THE STORAGE
 AREA IS A S1 OR S2 OCCUPANCY DESCRIBE THE MATERIALS TO
 BE STORED. DEPENDING ON THE TYPE OF STORAGE OCCUAPNCY
 FBC-B TABLE 508.4 MAY OR MAY NOT REQUIRE A OCCUPANCY
 FIRE SEPARATION WALL.
 DATE: TUE JUL 1 2014
 REPORT: 7357
 CODE: BUILDING CODE YEAR: 2010
 SECTION: TABLE 508.4
 QUESTION:
 IS IT THE INTENT OF TABLE 508.4 TO REQUIRE A (1HR (S),
 2HR (NS)) SEPARATION BETWEEN B AND S-2 OCCUPANCY AND NO
 SEPARATION
 REQUIREMENT BETWEEN B AND S-1 OCCUPANCY?
 COMMENT:
 PER CHAPTER 3, S-2 OCCUPANCY ARE DEFINED AS LOW- HAZARD
 STORAGE, WHERE AS S-1 OCCUPANCY IS DEFINED AS
 MODERATE-HAZARD
 OCCUPANCY. THE STORED MATERIALS LIST FOR S-1 OCCUPANCY
 IS MUCH MORE HAZARDOUS THAN THE LIST FOR S-2 OCCUPANCY
 AND ONE WOULD
 THINK THAT THE S-1 OCCUPANCY WOULD REQUIRE THE
 SEPARATION AND THE S-2 OCCUPANCY WOULD NOT.
 ANSWER:
 BASED ON THE INFORMATION REVIEWED, IT APPEARS YOU ARE
 CORRECT THAT A TYPO EXISTS. THE BEST APPROACH FOR THIS
 PARTICULAR ISSUE
 WOULD BE EITHER A FORMAL INTERPRETATION WHICH HAS
 STANDING OR A DEC STATEMENT FROM THE FLORIDA BUILDING
 COMMISSION. PLEASE
 SEE THE COMMENTARY BELOW.
 COMMENTARY:
 TABLE 508.4 DOES APPEAR TO HAVE A TYPO. THE 2001
 FLORIDA BUILDING CODE, TABLE 704.1 REQUIRED A 3 HOUR
 SEPARATION FOR S1 AND A 2
 HOUR SEPARATION FOR S2. IN THE 2004 CODE TABLE 706.3.7
 ALSO REQUIRES 3 HOURS FOR S1 AND 2 HOURS FOR S2. THE
 TYPO APPEARS TO
 HAVE BEEN INTRODUCED WITH TABLE 508.4 IN THE 2007 CODE.
 TABLE 508.4 APPEARS TO HAVE BEEN WRONG SINCE ITS
 INCEPTION.
 SUBMITTING A REQUEST FOR A FORMAL INTERPRETATION WOULD
 PERMIT APPLICATION OF CORRECTION TO THIS ISSUE UNTIL A
 CODE CHANGE CAN BE
 MADE, IF IT IS NOT ALREADY IN THE WORKS.
  
 3A) SHEET A2.3 THE LIFE SAFETY SHEET DOES NOT SHOW EXIT
 DIRECTIONAL SIGNAGE FBC-B 1006.3.8.
  
 3B) SHEET A2.3 THE LIFE SAFETY SHEET ALSO IS MISSING
 EXIT SIGNAGE FBC-B 1006.3.
  
 3C) SHEET A2.3 THE LIFE SAFETY SHEET DOES NOT SHOW
 COMPLIANCE WITH FBC-B 1006.3.4 EXIT DOOR OR TACTILE
 SIGNAGE.1006.3.4 EXIT STAIR DOOR OR TACTILE SIGNAGE.
 TACTILE SIGNAGE STATING ?EXIT? AND COMPLYING WITH
 ICC/ANSI A117.1, AMERICAN NATIONAL STANDARD FOR
 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES, SHALL
 BE INSTALLED ADJACENT TO THE LATCH SIDE OF THE DOOR 60
 INCHES (1524 MM) ABOVE THE FINISHED FLOOR TO THE CENTER
 LINE OF THE SIGN.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER