| Date |
Text |
| 2015-01-29 13:13:24 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PROVISO: | | | | | | VENT PIPE APPEARS TO BREECH THE GENERATOR ROOM RATED | | | WALL. CONFIRM THAT THE WALL IS RATED WHICH REQUIRES A | | | FIRE DAMPER. ADDITIONALLY, PROVIDE A U.L. RATING | | | LISTING TO PROTECT THE AREA AROUND THE VENT ON EACH | | | SISE OF THE WALL. | | | | | | SEPARATE SHOP DRAWING ARE REQUIRED FOR THE PRE-ACTION | | | SYSTEM. |
|