| Plan Review Notes For Permit 14120261 |
| Permit Number |
14120261 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-12-10 12:04:06 | 1) SUBMIT MANUFACTURER SPECIFICATION SHEETS FOR ALL GAS | | | EQUIPMENT. ALL EQUIPMENT SHALL BE LISTED AND LABELED | | | PER THE 2010 FL. GAS CODE SEC. 301.3. THIS INFORMATION | | | WAS REQUESTED AT THE INTERIOR BUILDOUT REVIEW AND WAS | | | NEVER SUBMITTED. | | | 2) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE | | | MOST REMOTE OUTLET. | | | 3) I AM THOROUGHLY CONFUSED REGARDING THE GAS PIPING | | | PRESSURE TABLE THAT WAS SUBMITTED ON THE GAS PLANS.I | | | DON'T UNDERSTAND THE TABLE.THE TABLE HAS A COLUMN THAT | | | LISTS "SECTION A, B, C", ETC.YET THESES SECTIONS ARE | | | NOT SHOWN ON THE GAS PIPING DRAWING. CLARIFY AS TO HOW | | | THIS SIZING TABLE MEETS THE INTENT OF THE 2010 FGC | | | SEC.402.3. | | | 4) THE SECTION OF PIPE THAT CROSSES THE CEILING IS | | | SIZED AS 1 1/2" WHICH COMPLIES WITH THE GAS CODE BUT | | | REDUCES TO 1 1/4" AT A 90 DEGREE TURN.THIS SECTION IS | | | STILL UNDER SIZED. IT MUST REMAIN 1 1/2" TO THE FIRST | | | BRANCH AND THEN CAN BE REDUCED AFTER THE FIRST | | | APPLIANCE.FGC 402.4.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|