| 2015-01-07 14:40:31 | 1/7/2015 |
| | PROJECT: #RD FL SPEC SUITE |
| | PERMIT#: 14120246 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) INDICATE ON THE PLAN THE RELOCATION OF RADIENT HEAT |
| | PANELS CIRCUITRY AS WELL AS THE REQUIRED CIRCUITRY AND |
| | DISCONNECTS FOR THE INSTALLATION OF VAV BOXES SHOWN ON |
| | MECHANICAL PLANS. |
| | |
| | 2) PROVIDE REVISED ELECTRICAL CIRCUIT DIRECTORY TO |
| | IDENTIFY ANY MODIFICATION OF EXISTING CIRCUITRY AND |
| | ADDITION OF ANY NEW CIRCUITRY REQUIRED FOR INSTALLATION |
| | OF NEW EQUIPMENT. EVERY CIRCUIT AND CIRCUIT |
| | MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS |
| | CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4 |
| | |
| | 3) PROVIDE A LOAD CALCULATION TO TAKE INTO |
| | CONSIDERATION THE ADDITION OR INSTALLATION OF ANY NEW |
| | CIRCUITRY. NEC 220 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |