| 2014-12-16 08:49:20 | BUILDING PLAN REVIEW |
| | REVISION: 14120241 |
| | PERMIT: 14050913 |
| | ADD: 1016 CLARE SUITE # 3 |
| | CONT: RIELLY CONSTRUCTION |
| | TEL: (561)262-6876 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. DEC. 16/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET LS 1.1 SHOWS THE REMOVAL OF THE LIFT TO THE |
| | SECOND FLOOR. THE FIRST LETTER OF DISPROPORTIONATE COST |
| | LETTER SHOWED THAT THE OWNERS WERE APPLYING MORE THAN |
| | THE 20% DISPROPORTIONATE COST WITH THE INCLUSION OF A |
| | VERTICAL LIFT. THE LIFT HAS BEEN REMOVED FROM THE |
| | SUBMITTED REVISION. THE NEW LETTER SHOWING THE COST |
| | BREAK DOWN WHERE THE DISPROPORTIONATE COST HAVE BEEN |
| | MET NEEDS TO BE UPDATED SINCE THE REVISION SHOWS THE |
| | REMOVAL OF ACCESSIBLE ELEMENTS.. |
| | |
| | LS1.1 PLEASE PROVIDE A COST BREAK DOWN WHERE 20% OR |
| | $70.00 DOLLARS IN ACCESSIBLE UPGRADES TO THE BUILDING. |
| | 2010 FL ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES |
| | IN THE EVENT OF DISPROPORTIONALITY. |
| | WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| | OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| | DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| | THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| | EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| | DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| | ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| | ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| | FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| | ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| | ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| | RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| | DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| | ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| | ALARMS. |
| | |
| | 2) SHEET A1.1 NOTE # 2 SHOWS THE ELEVATOR WITH A 6'-0" |
| | X 8'-9" ELEVATOR DOOR ON LS1.1 WHERE AS THE DOOR |
| | SCHEDULE SHOWS IT AS A 4'-0" X 7'-0" DOOR. |
| | SHEET A1.1 SHOWS A 3'-0" DOOR OPENING, PLEASE CORRECT |
| | THE DETAIL AND PROVIDE HOW THIS DOOR IS GOING TO OPEN. |
| | NOTE 3002.1.1 OPENING PROTECTIVES. |
| | OPENINGS IN HOISTWAY ENCLOSURES SHALL BE PROTECTED AS |
| | REQUIRED IN CHAPTER 7. FBC-B TABLE 715.4. |
| | |
| | SHEET A 1.2 SHOWS THE SAME 3'-0" DOOR OPENING ON THE |
| | ELEVATOR, PLEASE PROVIDE A DETAIL HOW THE LINTEL OR |
| | BEAM WILL TIE INTO THE SIDE WALLS. NOTE THIS DOOR DOES |
| | NOT SHOW UP ON THE DOOR SCHEDULE SHEET A3.1. |
| | |
| | 3) SHEET A5.1 NEW NOW THE SHAFT PENETRATES THE ROOF, |
| | THE SECTION THRU THE SHAFT INDICATES THE USE OF A NEW 3 |
| | PLY MODIFIED BITUMENON TAPERED RIGID INSULATION BY JOHN |
| | MANSVILLE OR EQUAL. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | |
| | 4) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, PLEASE |
| | IDENTIFY WHICH SUB-SYSTEM IS TO BE APPLIED. |
| | |
| | 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 6) SHEET A5.1 & S3 NEITHER PROVIDE THE WIND DESIGN |
| | CRITERIA FOR THE NEW ROOF: |
| | |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 6.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 6.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 6.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 6.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 6.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 7) WHILE THE BUILDING CODE DOES NOT INDICATE THE |
| | REQUIREMENT FOR SUMP PITS IN ELEVATOR HOISTWAY PITS |
| | THIS BEING A FIRE SPRINKLERED BUILDING, SUMP PUMPS WILL |
| | PUMP OT THE PIT IF THE FIRE SPRINKLERS ARE ACTIVATED. |
| | THE OTHER ISSUE WOULD BE IF A HYDROLIC ELEVATOR IS USED |
| | PLEASE REVIEWFBC-P 1003.4 AAND EXCEPTION. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |