2015-01-07 13:29:416601 NORTH JOG ROAD - ASH MANAGEMENT BUILDING
 TRACKING #14120236
 PERMIT #13100957
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS INDICATE AN ADDRESS OF 6701 NORTH JOG ROAD
 WHICH IS ALREADY ASSIGNED TO THE MAINTENANCE BUILDING.
  
 THESE PLANS WERE SUBMITTED AS AS-BUILT REVISIONS TO
 SPRINKLER PERMIT #13100957; HOWEVER, NO REVISION
 TRIANGLES OR DELTAS COULD BE LOCATED ON THE PLANS
 INDICATING WHAT HAS BEEN CHANGED.
  
 CROKER MODEL 5040 IS NOT A PRESSURE REDUCING TYPE ANGLE
 VALVE. THE PRESSURE-REGULATING DEVICE SHALL BE PROVIDED
 WITH INLET AND OUTLET PRESSURE GAUGES (NFPA 14 SECTION
 7.2.2).
  
 STANDPIPE DESIGN: SEVERAL 1-1/2" HOSE VALVES APPEAR TO
 HAVE PRESSURES THAT WILL EXCEED 100 PSI. PER NFPA 14
 SECTION 7.2.3.1, WHERE THE RESIDUAL PRESSURE AT A
 1-1/2" OUTLET ON A HOSE CONNECTION AVAILABLE FOR
 TRAINED PERSONNEL USE EXCEEDS 100 PSI, AN APPROVED
 PRESSURE-REGULATING DEVICE SHALL BE PROVIDED TO LIMIT
 THE RESIDUAL PRESSURE TO 100 PSI. ALSO PER NFPA 14
 SECTION 7.2.3.2, AN APPROVED PRESSURE-REGULATING DEVICE
 SHALL BE PROVIDED TO LIMIT STATIC AND RESIDUAL
 PRESSURES AT THE OUTLET OF THE HOSE CONNECTION TO 100
 PSI FOR 1-1/2" HOSE CONNECTIONS AVAILABLE FOR TRAINED
 PERSONNEL USE AND 175 PSI FOR OTHER HOSE CONNECTIONS.
  
 TO AVOID PRESSURE REGULATING DEVICES I WOULD RECOMMEND
 A TRUE CLASS I STANDPIPE SYSTEM (2-1/2 FDVS ONLY) AND
 ELIMINATE THE 1-1/2" FDVS WITH HOSE AND REEL BECAUSE
 FIRE DEPARTMENT PERSONNEL WILL NOT USE THIS EQUIPMENT.
  