| 2014-12-17 12:51:46 | 12/17/2014 |
| | PROJECT: ADORE |
| | PERMIT#: 14120224 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) FBC-WPB AMENDMENTS 107.3.5.1.2. MINIMUM ELECTRICAL |
| | PLAN REVIEW CRITERIA SHALL INCLUDE BUT NOT BE LIMITED |
| | TO THE FOLLOWING: |
| | "SERVICES" A SITE PLAN INDICATING THE LOCATION OF THE |
| | ELECTRICAL UTILITY, DISCONNECT(S) AND PANEL(S). |
| | "FEEDERS" PROVIDE A RISER DIARAM INDICATING THE SIZE |
| | AND TYPE OF ALL DISCONNECTS, SERVICE ENTRANCE, |
| | GROUNDING ELECTRODE SYSTEM, FEEDERS AND OVERCURRENT |
| | PROTECTION. "WIRING MEATHODS AND MATERIALS" PROVIDE A |
| | DETAILED FLOOR PLAN INDICATING ALL BRANCH CIRCUIT |
| | WIRING WITH NUMBERED CIRCUITRY ON THE FLOOR PLAN AND |
| | CEILING PLAN. |
| | |
| | 2) SEE BUILDING REVIEW COMENTS. |
| | ONCE A MORE DETAILED SIGNED SEALED SET OF CONSTRUCTION |
| | DOCUMENTS IS SUBMITTED A MORE COMPREHENSIVE REVIEW OF |
| | THE ELECTRICAL SYSTEM CAN BE COMPLETED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |