| 2014-12-13 09:02:28 | BUILDING PLAN REVIEW |
| | PERMIT: 14120224 |
| | ADD: 701 S. ROSEMARY AVE. # 159 |
| | CONT: TRAV-DANIELS CONSTRUCTION SVCS. |
| | TEL: (561)239-0484 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. DEC. 13/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED PLANS ARE NOT SIGNED NOR SEAL BY A |
| | FLORIDA ARCHITECT. THE ARCHITECURAL DESIGN CAN NOT BE |
| | USED IN ADVERTISING AS A ARCHITECT |
| | . FL. S. 481.223?PROHIBITIONS; PENALTIES; INJUNCTIVE |
| | RELIEF. (1)?A PERSON MAY NOT KNOWINGLY: |
| | |
| | (A)?PRACTICE ARCHITECTURE UNLESS THE PERSON IS AN |
| | ARCHITECT OR A REGISTERED ARCHITECT; HOWEVER, A |
| | LICENSED ARCHITECT WHO HAS BEEN LICENSED BY THE BOARD |
| | AND WHO CHOOSES TO RELINQUISH OR NOT TO RENEW HIS OR |
| | HER LICENSE MAY USE THE TITLE ?ARCHITECT, RETIRED? BUT |
| | MAY NOT OTHERWISE RENDER ANY ARCHITECTURAL SERVICES. |
| | |
| | (C)?USE THE NAME OR TITLE ?ARCHITECT? OR ?REGISTERED |
| | ARCHITECT,? OR ?INTERIOR DESIGNER? OR ?REGISTERED |
| | INTERIOR DESIGNER,? OR WORDS TO THAT EFFECT, WHEN THE |
| | PERSON IS NOT THEN THE HOLDER OF A VALID LICENSE ISSUED |
| | PURSUANT TO THIS PART. DOES NOT SHOW AS A REGISTERED |
| | ARCHITECT. |
| | |
| | 2) THE SUBMITTED PLANS ALSO HAVE ROBERT WALKER IN THE |
| | TITLE BLOCK AS A INSPECTOR, THIS NAME DOES NOT SHOW ON |
| | THE STATE DPBR WEBSITE UNLESS THE MAILING ADDRESS IS IN |
| | ORLANDO. |
| | |
| | 3) THE ADDRESS IS ALSO WRONGFOR THE LOCATION. 2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED. THE NEW PLANS WITH |
| | CORRECTED ADDRESS WILL ALSO NEED CIY PLACE STAMP OF |
| | APPROVAL BEFORE PERMIT ISSUANCE. |
| | |
| | 4) PLEASE PROVIDE WHAT TYPE OF BUSINESS IS GOING TO BE |
| | WITHIN THE TENANT SPACE, THE OCCUPANCY CLASSIFICATION |
| | IS DECLARED AS A "BUSINESS OCCUPANCY"? |
| | 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED, 2010 |
| | FBC-B 304.1. PLEASE DESCRIBE THE TYPE OF BUSINESS USAGE |
| | TYPE FOUND UNDER THE HEADING OF 304.1. |
| | |
| | 5) PLEASE EXPLAIN WHAT ACTIVITIES OCCUR IN THE VIP |
| | ROOM. NOTE IF THIS IS A MERCANTILE OCCUPANCY AND THIS |
| | IS A DRESSING ROOM, PLEASE PROVIDE CODE COMPLIANCE WITH |
| | THE 2010 FL ACCESS, CODE 803. 1-5. |
| | |
| | 7) IF THIS IS A MERCANTILE OCCUPANCY THE PLANS FAIL TO |
| | PROVIDE COMPLIANCE WITH 2010 FL ACCESS. CODE 904.4 |
| | SALES AND SERVICE COUNTERS. |
| | SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH |
| | 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE |
| | COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR |
| | SERVICE COUNTER TOP. |
| | |
| | 8) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) |
| | FBC-B 803.9 & TABLE 803. |
| | |
| | 9A) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| | INCLUDE THE FOLLOWING COMPONENTS: FIRE-RESISTANT |
| | SEPARATIONS / PROTECTION OF OPENINGS AND PENETRATIONS |
| | OF RATED WALLS |
| | 2010 FBC-B 713.3.1.2 THROUGH-PENETRATION FIRESTOP |
| | SYSTEM. THROUGH PENETRATIONS SHALL BE PROTECTED BY AN |
| | APPROVED PENETRATION FIRESTOP SYSTEM INSTALLED AS |
| | TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A |
| | MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH |
| | (2.49 PA) OF WATER AND SHALL HAVE AN F RATING OF NOT |
| | LESS THAN THE REQUIRED FIRE-RESISTANCE RATING OF THE |
| | WALL PENETRATED. |
| | |
| | 9B) 2010 FBC-B 713.6 FIRE WALLS, FIRE BARRIERS, FIRE |
| | PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY |
| | OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE |
| | AND SMOKE BARRIER ? PROTECT ALL OPENINGS.? |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |