Plan Review Notes
Plan Review Notes For Permit 14120224
Permit Number 14120224
Review Stop B
Sequence Number 1
Notes
Date Text
2014-12-13 09:02:28BUILDING PLAN REVIEW
 PERMIT: 14120224
 ADD: 701 S. ROSEMARY AVE. # 159
 CONT: TRAV-DANIELS CONSTRUCTION SVCS.
 TEL: (561)239-0484
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. DEC. 13/ 2014
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS ARE NOT SIGNED NOR SEAL BY A
 FLORIDA ARCHITECT. THE ARCHITECURAL DESIGN CAN NOT BE
 USED IN ADVERTISING AS A ARCHITECT
 . FL. S. 481.223?PROHIBITIONS; PENALTIES; INJUNCTIVE
 RELIEF. (1)?A PERSON MAY NOT KNOWINGLY:
  
 (A)?PRACTICE ARCHITECTURE UNLESS THE PERSON IS AN
 ARCHITECT OR A REGISTERED ARCHITECT; HOWEVER, A
 LICENSED ARCHITECT WHO HAS BEEN LICENSED BY THE BOARD
 AND WHO CHOOSES TO RELINQUISH OR NOT TO RENEW HIS OR
 HER LICENSE MAY USE THE TITLE ?ARCHITECT, RETIRED? BUT
 MAY NOT OTHERWISE RENDER ANY ARCHITECTURAL SERVICES.
  
 (C)?USE THE NAME OR TITLE ?ARCHITECT? OR ?REGISTERED
 ARCHITECT,? OR ?INTERIOR DESIGNER? OR ?REGISTERED
 INTERIOR DESIGNER,? OR WORDS TO THAT EFFECT, WHEN THE
 PERSON IS NOT THEN THE HOLDER OF A VALID LICENSE ISSUED
 PURSUANT TO THIS PART. DOES NOT SHOW AS A REGISTERED
 ARCHITECT.
  
 2) THE SUBMITTED PLANS ALSO HAVE ROBERT WALKER IN THE
 TITLE BLOCK AS A INSPECTOR, THIS NAME DOES NOT SHOW ON
 THE STATE DPBR WEBSITE UNLESS THE MAILING ADDRESS IS IN
 ORLANDO.
  
 3) THE ADDRESS IS ALSO WRONGFOR THE LOCATION. 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED. THE NEW PLANS WITH
 CORRECTED ADDRESS WILL ALSO NEED CIY PLACE STAMP OF
 APPROVAL BEFORE PERMIT ISSUANCE.
  
 4) PLEASE PROVIDE WHAT TYPE OF BUSINESS IS GOING TO BE
 WITHIN THE TENANT SPACE, THE OCCUPANCY CLASSIFICATION
 IS DECLARED AS A "BUSINESS OCCUPANCY"?
 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED, 2010
 FBC-B 304.1. PLEASE DESCRIBE THE TYPE OF BUSINESS USAGE
 TYPE FOUND UNDER THE HEADING OF 304.1.
  
 5) PLEASE EXPLAIN WHAT ACTIVITIES OCCUR IN THE VIP
 ROOM. NOTE IF THIS IS A MERCANTILE OCCUPANCY AND THIS
 IS A DRESSING ROOM, PLEASE PROVIDE CODE COMPLIANCE WITH
 THE 2010 FL ACCESS, CODE 803. 1-5.
  
 7) IF THIS IS A MERCANTILE OCCUPANCY THE PLANS FAIL TO
 PROVIDE COMPLIANCE WITH 2010 FL ACCESS. CODE 904.4
 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 8) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 FBC-B 803.9 & TABLE 803.
  
 9A) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS: FIRE-RESISTANT
 SEPARATIONS / PROTECTION OF OPENINGS AND PENETRATIONS
 OF RATED WALLS
 2010 FBC-B 713.3.1.2 THROUGH-PENETRATION FIRESTOP
 SYSTEM. THROUGH PENETRATIONS SHALL BE PROTECTED BY AN
 APPROVED PENETRATION FIRESTOP SYSTEM INSTALLED AS
 TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A
 MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH
 (2.49 PA) OF WATER AND SHALL HAVE AN F RATING OF NOT
 LESS THAN THE REQUIRED FIRE-RESISTANCE RATING OF THE
 WALL PENETRATED.
  
 9B) 2010 FBC-B 713.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  