| 2014-12-10 06:54:36 | BUILDING PLAN REVIEW |
| | REVISION: 14120295 |
| | PERMIT: 14011176 (PRIME) |
| | ADD: 2836 N. FLAGLER DR. |
| | CONT: OWENS WALTER GROUP |
| | TEL: (561)856-6655 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. DEC. 10/2014 |
| | ACTION: DENIED |
| | |
| | 1) THE CONTRACTOR SUBMITTED A MIAMI-DADE NOA # |
| | 14-0224.03 CERTAIN TEED MODIFIED BITUMEN ROOFING |
| | SYSTEMS OVER WOOD DECK. NO SUB-SYSTEM HAS BEEN |
| | IDENTIFIED. EACH SUB-SYSTEM HAS ITS OWN PRESSURES AND |
| | LIMITATIONS EITHER 7 OR 9. DEPENDING ON WHICH |
| | SUB-SYSTEM IS IDENTIFIED ENHANCED FASTENING IN ROOF |
| | ZONES 2 & 3 WILL BE REQUIRED. IF LIMITATION # 7 IS |
| | IDENTIFIED FOR THE SUB-SYSTEM PICKED THEN RAS 117 |
| | CALCULATIONS WILL BE REQUIRED BY EITHER A ARCHITECT OR |
| | ENGINEER. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |