| 2014-12-17 08:43:46 | 1) TTHE GREASE INTERCEPTOR SHALL BE DESIGNED AND | | | INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S | | | INSTRUCTIONS. SUBMIT SIZING CALCULATIONS BY THE | | | MANUFACTURER THAT THE SPECIFIED SCHIER UNIT GB-15 IS | | | ADEQUATE FOR THE PROPOSED USE.YOU CAN CONTACT SCHIER'S | | | REPRESENTATIVE LEE SCHNEEWEISS AT 561-632-3123. | | | 2) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE SCHIER | | | UNIT TO BE INSTALLED. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|