| 2014-12-20 03:28:38 | 1) YOU HAVE SUBMITTED A COPY OF THE SIZING TABLE FOR PE |
| | PIPE YET PE PIPE IS NOT SHOWN ON THE PLANS AS BEING |
| | INSTALLED. SUBMIT A COPY OF THE SIZING TABLE FROM THE |
| | 2010 FL. BUILDING CODE, RESIDENTIAL, SECTION G2413.3 |
| | AND TABLES G2413.4 (5) OR 2413.4 (6) FOR THE TYPE OF |
| | PIPE MATERIAL BEING USED.THE PLAN INDICATES FSP ? I |
| | ASSUME THIS IS CSST. IF SO, PLEASE REFER TO IT AS SUCH |
| | ON THE PLAN. |
| | 2) IF CSST IS BEING INSTALLED, SHOW THE CORRESPONDING |
| | EHD NUMBER FOR THE PIPE SIZE IN ACCORDANCE WITH 2010 |
| | FBCR, SEC.G2413.3 AND THE APPLICABLE SIZING TABLE. |
| | 3) INDICATE THE GAS PRESSURE ( PSI ) ON THE PLANS AND |
| | THE LOCATION OF THE 2ND STAGE REGULATOR IF APPLICABLE. |
| | REGULATORS LOCATED ON THE EXTERIOR OF THE BUILDING |
| | SHALL BE APPROVED FOR OUTDOOR INSTALLATION.2010 FBCR, |
| | SEC. G2421.1. |
| | 4) SUBMIT TWO CLEAN COPIES OF THE GAS PLAN THAT CLEARLY |
| | SHOWS THE TYPE OF PIPING THROUGH THE ATTIC SPACE, THE |
| | TOTAL BTU LOAD ON THE SYSTEM ( SINCE THE BRANCH LINE |
| | FOR THE GENERATOR IS BEING CONNECTED TO THE EXISTING |
| | SYSTEM, ALL THE APPLIANCES CONNECTED TO THE SYSTEM |
| | SHALL BE INCLUDED IN THE TOTAL BTU. IS THE LOAD OF |
| | 300,000 THE TOTAL LOAD OR JUST THE GENERAROR LOAD? |
| | INDICATE ON THE PLANS. THE PLANS HAVE ITEMS CROSSED OUT |
| | AND ARE SOMEWHAT VAGUE IN NATURE.IN ORDER FOR A |
| | COMPLETE REVIEW TO BE DONE, 2 COPIES OF CLEAN DRAWINGS |
| | SHALL BE SUBMITTED. I WILL NOT APPROVE THESE PLANS AS |
| | THEY ARE. |
| | 5) THE NOTE ON THE GAS DRAWING STATES THE TOTAL FOOTAGE |
| | OF PIPE IS 30 FEET BUT THE DIMENSIONS SHOWN ON THE |
| | SURVEY CLEARLY INDICATE THAT THE TOTAL RUN FROM THE GAS |
| | METER TO THE GENERATOR IS MORE THAN 30 FEET. SHOW THE |
| | DISTANCE FROM THE GAS METER TO THE FURTHEST OUTLET |
| | /GENERATOR. |
| | **NOTE** - I SUGGEST THAT SOMEONE CONTACT ME AT |
| | 561-805-6692 TO SET UP AN APPOINTMENT TO COME INTO THE |
| | BUILDING DIVISION AND MEET WITH ME TO DISCUSS THESE |
| | COMMENTS AND ARRIVE AT A RESOLUTION SO WE CAN GET THIS |
| | PERMIT ISSUED. THANK YOU. |
| | |