| Plan Review Notes For Permit 14120164 |
| Permit Number |
14120164 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-12-31 13:40:08 | 12/31/2014 | | | PROJECT: DUNKIN DONUTS | | | PERMIT#: 14120164 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 2NDELECTRICAL PLAN REVIEW | | | ACTION: APPROVED WITH EXCEPTION | | | | | | 1) 505.2.4 EXTERIOR LIGHTING CONTROLS. | | | PROVIDE AUTOMATED CONTROLS CAPABLE OF TURNING OFF | | | EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT IS AVAILABLE | | | OR WHEN THE LIGHTING IS NOT REQUIRED DURING NIGHTTIME | | | HOURS. LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN | | | OPERATION SHALL BE CONTROLLED BY EITHER A COMBINATION | | | OF A PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL | | | TIME SWITCH. A TIMER IS INDICATED ON THE PLAN BUT IT | | | MUST BE VERIFIED TO MEET THE CRITERIA OF THE FBC-ENERGY | | | 505.2 | | | | | | 2) 2010 FBC-BUILDING SECTION 1609 | | | PROVIDE ENGINEERED WIND LOAD CALCULATIONS FOR ALL NEW | | | LIGHT POLES INCLUDING ATTACHED LUMINAIRE INDICATING | | | COMPLIANCE WITH THE FBC 1609. PRIOR TO FINAL | | | INSPECTION. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|