Plan Review Notes
Plan Review Notes For Permit 14120164
Permit Number 14120164
Review Stop E
Sequence Number 2
Notes
Date Text
2014-12-31 13:40:0812/31/2014
 PROJECT: DUNKIN DONUTS
 PERMIT#: 14120164
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2NDELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 1) 505.2.4 EXTERIOR LIGHTING CONTROLS.
 PROVIDE AUTOMATED CONTROLS CAPABLE OF TURNING OFF
 EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT IS AVAILABLE
 OR WHEN THE LIGHTING IS NOT REQUIRED DURING NIGHTTIME
 HOURS. LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN
 OPERATION SHALL BE CONTROLLED BY EITHER A COMBINATION
 OF A PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL
 TIME SWITCH. A TIMER IS INDICATED ON THE PLAN BUT IT
 MUST BE VERIFIED TO MEET THE CRITERIA OF THE FBC-ENERGY
 505.2
  
 2) 2010 FBC-BUILDING SECTION 1609
 PROVIDE ENGINEERED WIND LOAD CALCULATIONS FOR ALL NEW
 LIGHT POLES INCLUDING ATTACHED LUMINAIRE INDICATING
 COMPLIANCE WITH THE FBC 1609. PRIOR TO FINAL
 INSPECTION.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]