Plan Review Notes
Plan Review Notes For Permit 14120164
Permit Number 14120164
Review Stop E
Sequence Number 1
Notes
Date Text
2014-12-05 13:50:4012/5/2014
 PROJECT: DUNKIN DONUTS
 PERMIT#: 14120164
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) 2010 WPB AMENDMENTS TO FBC 107.2.1
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE IN DETAIL THE LOCATION, NATURE AND EXTENT
 OF THE WORK PROPOSED. PROVIDE A LIGHTING CIRCUITRY
 DIAGRAM INDIACTING THE WIRING METHOD, THE ELECTRICAL
 PANEL USED PLUS IT'S LOCATION, THE CIRCUIT NUMBER(S)
 USED AND SHOWN ON THE PLAN, THE SIZE AND TYPE OF
 CONDUCTORS PROPOSED.
  
 2) 505.2.4 EXTERIOR LIGHTING CONTROLS.
 PROVIDE AUTOMATED CONTROLS CAPABLE OF TURNING OFF
 EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT IS AVAILABLE
 OR WHEN THE LIGHTING IS NOT REQUIRED DURING NIGHTTIME
 HOURS. LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN
 OPERATION SHALL BE CONTROLLED BY EITHER A COMBINATION
 OF A PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL
 TIME SWITCH.
  
 3) 2010 FBC-BUILDING SECTION 1609
 PROVIDE ENGINEERED WIND LOAD CALCULATIONS FOR ALL NEW
 LIGHT POLES INCLUDING ATTACHED LUMINAIRE INDICATING
 COMPLIANCE WITH THE FBC 1609.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  